Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address NEW:
1625 N CAMPBELL AV
Apply Date:
03/23/2016
Applicant:
BRIAN HAGEDON
Description:
NEW HOSPITAL
Architects:
  • WATSON, ANGELA
Contractors:
  • D P R CONSTRUCTION A GENERAL PARTNERSHIP

Permit Reviews

Permit Number - T16CM02176
Permit Status: C of o
Permit Description: NEW HOSPITAL
Start Date Submittal Complete Date Status  
02/15/2017 REVISION - - 2ND 03/13/2017 COMPLETED Review Details
03/13/2017 REVISION - - 3RD 11/16/2017 ACTIVE Review Details
03/23/2016 PLANS OK TO SUBMIT - COMM 03/23/2016 COMPLETED Review Details
03/23/2016 COMMERCIAL - NEW 05/31/2016 COMPLETED Review Details
05/31/2016 RESUBMITTAL 06/28/2016 COMPLETED Review Details
06/28/2016 RESUBMITTAL 07/05/2016 COMPLETED Review Details
07/06/2016 REVISION - - 1ST 08/26/2016 COMPLETED Review Details
08/26/2016 REVISION - - 1ST 10/04/2016 COMPLETED Review Details
10/04/2016 REVISION - - 1ST 10/31/2016 COMPLETED Review Details
10/31/2016 REVISION - - 1ST 11/03/2016 COMPLETED Review Details
11/03/2016 REVISION - - 2ND 11/07/2016 COMPLETED Review Details
11/07/2016 REVISION - - 2ND 12/22/2016 COMPLETED Review Details
12/22/2016 REVISION - - 2ND 02/15/2017 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T16CM02176
Permit Status: C of o
Permit Description: NEW HOSPITAL
Total Outstanding Activity Conditions - 1
Date Name
03/23/2016 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T16CM02176
Permit Description: NEW HOSPITAL
Total Completed Inspections - 39
Date Description Inspector Results Comments
12/28/2016 ELECTRIC - ABOVE CEILING JBURGE Approved LEVEL #4 - 15 CONDUITS (3/4" TO 3 1/2") IN TWO RACKING SYSTEMS AT GL: 7/F - H
12/28/2016 SHEET ROCK NAILING JBURGE Approved LEVEL #4 MAIN CORRIDOR - SOUTH WALL TWO HOUR RATED AT 12' DOWN FROM DECK ABOVE - GL: F.5/4.5 - 9.5; LEVEL #3 SHAFT ELECTRIC ROOM #035980; LEVEL #2 ELECTRIC ROOMS #0259801 AND 0259802, INTERIOR/EXTERIOR - OK TO TAPE.
12/28/2016 BUILDING - PROGRESS JBURGE Approved LEVEL #R-2; SLAB - CLEAN AND PLACE CHAIRS - OK TO PLACE CONCRETE
02/24/2017 ELECTRIC - UFER JBURGE Approved LEVEL #4: FEEDER #5 AT GL: G - M; RACK #4 AT GL: F - M; IDF AT GL: F-M. (7 CONDUITS)
03/23/2017 ELECTRIC - TEMPORARY SERVICE JBURGE Approved PDU AT LEVEL 8, K; OK TO ENERGIZE UNIT.
04/05/2017 ELECTRIC - PROGRESS JBURGE Approved CONTINUING CONDUITS (1" - 4") AT NORMAL ELECTRIC ROOM; EMERGENCY ELECTRIC ROOM; FIRE PUMP ROOM; CORRIDOR #0450610.
07/21/2017 BUILDING - FINAL JBURGE Approved MASONRY PRE-GROUT: STEM WALLS FOR EQUIPMENT PADS: LEVEL #4, GL: 4.2/H - L. ENSURE ALL LOOSE CMU BLOCKS ARE SECURED WITH MORTAR.
10/13/2017 PLUMBING - GAS PRESSURE TEST JBURGE Approved LEVEL #1, 2" VACUUM LINES, 1" OXYGEN LINE, 1" MED GAS AT AMBULANCE BAY, EVS HALLWAY: TESTED AT 150 psi. LEVEL #3, 2" VACUUM LINES, 1" OXYGEN LINE, 1" MED GAS LINE: TESTED AT 150 psi (PEDIATRIC ROOMS).
10/13/2017 MECHANICAL - INTERMEDIATE JBURGE Approved LEVEL #1, TRAUMA AREA, GL: G.5/9 - 13, 10" HEATED HOT WATER SUPPLY AND RETURN.
10/27/2017 PLUMBING - ROUGH, SOIL JBURGE Approved PRIVATE WATER LINES (2 @ 12" AND 1 @ 8") FROM WARREN AVENUE NORTH APPROXIMATELY 150' TO AREA OF AMBULANCE CANOPY.
11/08/2017 REINFORCED MASONRY PRE-GROUT JBURGE Approved EQUIPMENT PAD CURBS (6 AREAS) ON LEVEL #4 - REBAR TO BE EPOXIED. OK TO GROUT PROGRESS AREAS.
12/05/2017 PLUMBING - ROOF DRAINS JBURGE Approved ROOF DRAIN LINES IN THE AMBULANCE CORRIDOR AND THE FUTURE TRAUMA AREA (6" - 8" LINES).
12/21/2017 FIREWALL/FIREBARRIER/FIRESTOP JBURGE Approved LEVEL #4, GL: N/12; EDGE OF SLAB: FIRE CAULKED - TWO INCHES FROM TOP OF SLAB. LEVEL #3, AREAS #3, 6, 8, 10; FLOOR PENETRATIONS
12/21/2017 FRAMING JBURGE Approved LEVEL #1, LOBBY AREA, COLUMNS AT MAIN ENTRY. LEVEL #7, TOWER #4, PATIENT BATHROOM CEILINGS. ALL BATHROOMS NEED TO BE CHECKED FOR FIRE CAULKING AROUND ELECTRIC CONDUITS. ADA ROOMS NOT READY (4 ROOMS).
12/26/2017 MECHANICAL - ABOVE CEILING JBURGE Approved LEVEL #4, TOWER #4, GL: H - K/8 - 10. ROUND DUCT SYSTEM AT 12" - 24" SYSTEM - OK TO INSULATE PROGRESS AREAS.
12/28/2017 PLUMBING - MEDICAL GAS/TEST JBURGE Approved LEVEL #8, TOWER #4 (3/4" - 2" LINES); MEDICAL GAS, MEDICAL VACUUM, OXYGEN (PATIENT BURN ROOMS). LEVEL #2, TOWER #4, 6 PATIENT ROOMS (3/4" - 2" LINES), OXYGEN, MEDICAL VACUUM, MEDICAL AIR.
12/29/2017 PLUMBING - ABOVE CEILING JBURGE Approved LEVEL #3, AREAS #7 - 10; DOMESTIC HOT AND COLD LINES (SUPPLY ONLY), LINES AT 1/2" T0 6", SHAFT #7, LEVEL #3 DOWN TO LEVEL #1. ALL LINES TESTED AT 150 PSI. OK T O
INSULATE PROGRESS AREAS.
12/29/2017 ELECTRIC - INTERMEDIATE JBURGE Approved MAIN ELECTRIC ROOM: PANEL #4NBBL-S1, ATS-36; SWITCH GEAR # 4CABH-S2, S4ABH-S-1, 4CAAH-S2, 4CCAAH-S1; EMERGENCY SWITCH GEAR - ESS-4A; BUSS CDUCT AND TAP BOX AT LEVELS #4 TO LEVEL #1.
07/20/2018 FIRE - FINAL JPEELDAVIS Approved Perfomed the commissioning of the fire pump. Test was performed by control head manufacturer representative, pump manufacturer representative and Kazal Fire. We could not verify the fire alarm signals from the fire pump.Electrical wiring was approved.
08/03/2018 BUILDING ABOVE CEILING JBURGE Approved LEVEL #4, CSPD ROOMS; RT OFFICES, MEDITATION ROOM. OK TO SET CEILING TILES.
12/19/2018 ELECTRIC - UNDERGROUND JBURGE Approved 1" conduits for 7 light pole caissons - South parking lot. Ok to cover progress areas.
12/26/2018 PLUMBING - INTERMEDIATE JBURGE Approved Level #4. Blood Bank; waste and vent lines (2" - 4"), 4 each floor drains under air test.
12/28/2018 EXCAVATION/LAYOUT REBAR & ZON JBURGE Approved Retention Basin #3: footings and rebar for retaining walls at 4' 9" - 5' 2". Ok to place concrete.
02/07/2019 PLUMBING - PROGRESS JBURGE Approved
02/07/2019 SITE - SEWER JBURGE Approved
02/07/2019 PLUMBING - MD GAS/PRECONST MTG JBURGE Approved
02/07/2019 PLUMBING - YARD WTR LINE/TEST JBURGE Approved
02/07/2019 ELECTRIC - TEMP POWER FOR TEST JBURGE Approved
02/07/2019 ELECTRIC - CONSTRUCTION POWER JBURGE Approved
02/07/2019 U VALUE FOR WINDOW JBURGE Approved
02/07/2019 STUCCO MESH JBURGE Approved
02/25/2019 MECHANICAL - HOODS JBURGE Approved
02/25/2019 OUTDOOR LIGHTING FINAL JBURGE Approved
04/05/2019 PLUMBING - FINAL JBURGE Approved
04/05/2019 PLUMBING - MEDICAL GAS/FINAL JBURGE Approved
04/05/2019 ELECTRIC - FINAL JBURGE Approved
04/05/2019 MECHANICAL - FINAL JBURGE Approved
04/10/2019 HEALTH DEPT - FINAL 724-7908 CTREVIL Approved
04/10/2019 ENGINEERING - FINAL CTREVIL Approved FINAL WORK UNDER ACTIVITY DP15-0185