Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2019 | PLUMBING - INTERMEDIATE | Approved | ||
| 03/19/2019 | PLUMBING - INTERMEDIATE | Not ready for Inspection | bone cutting saw water lines not complete | |
| 03/18/2019 | PLUMBING - INTERMEDIATE | Partial Approval | Tower #4, Level #9, Room #107 Restroom. Ok to insulate, cover walls and add fixtures | |
| 02/25/2019 | PLUMBING - INTERMEDIATE | Partial Approval | ||
| 01/18/2019 | PLUMBING - INTERMEDIATE | Partial Approval | Kitchen area appliances (flex connectors/lines) from gas lines-tested at 58 psi | |
| 12/26/2018 | PLUMBING - INTERMEDIATE | Partial Approval | Level #4. Blood Bank; waste and vent lines (2" - 4"), 4 each floor drains under air test. | |
| 09/14/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, KITCHEN AREA: 2 EACH 3" CHILLED WATER LINES; SUPPLY AND RETURN LINES TO COMPRESSOR ROOM; 2 EACH 3/4" DOMESTIC WATER LINES FROM COMPRESSOR ROOM TO ICE MACHINES IN KITCHEN AREAS. | |
| 07/20/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, 8" COPPER ELEVATOR SUMP PUMP LINE - LESTED AT 100 PSI. | |
| 07/20/2018 | PLUMBING - INTERMEDIATE | Partial Approval | ||
| 07/05/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, CAFE AREA: WASTE AND VENT LINES AT 2" LINES; DOMESTIC WATER (HOT/COLD) LINES AT 3/4" - 1" LINES. | |
| 07/02/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, PHARMACY AREA - DOMESTIC WATER LINES (HOT/COLD) (1/2" - 1") | |
| 06/01/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, TOWER #4, GL: 14/B-G; WASTE LINES FOR FLOOR DRAINS (2" - 4"); LEVEL #3 TO LEVEL #2. | |
| 05/25/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, PHARMACY: WASTE AND VENT LINES AT 2" - 4": GL: H-I/6; H/8 - I/5: ALL LINES UNDER TEST. | |
| 05/24/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, GL: F/10-12 UP TO LEVEL #2. WASTE AND VENT LINES (2"-4") | |
| 05/23/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LOBBY/MAIN ENTRY AREA: RADDIENT HEATING LINES - TESTED AT 105 PSI. OK TO PLACE CONCRETE - DOWELING AND WIRE MESH RE-ENFORCEMENT. WASTE AND VENT LINES (2: - 4") AT LEVEL #1 WASHER ROOM; UP TO LEVEL #2 (2" - 4") IN NEPTUNE BOX IN SOIL ROOM. | |
| 05/14/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, KNUCKLE AREA - WASTE AND VENT LINES (2" - 4"); DOMESTIC HOT/COLD WATER LINES (2" - 3") - OK TO INSULATE LINES. | |
| 05/09/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #8, TOWER #4, STEAM LINES; TESTED AT 100 PSI. OK TO INSULATE. | |
| 04/17/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, GL: M/4.2 - 12: WASTE AND VENT LINES AT 2" - 4" | |
| 04/11/2018 | PLUMBING - INTERMEDIATE | Approved | LEVEL #9, KNUCKLE AREA: WASTE AND VENT LINES AT 2" - 4" (IN WALLS AND OVERHEAD). DOMESTIC HOT/COLD WATER LINES AT 1/2" - 1 1/2" TESTED AT 150 PSI. | |
| 04/04/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #8, KNUCKLE AREA; WASTE AND VENT LINES (2" AND 4") IN WALLS AND ABOVE CEILING. | |
| 04/03/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, KNUCKLE AREA (2" - 4") WASTE AND VENT LINES; MRI AREA AT GL: H-I/5-6 (2" - 4") WASTE AND VENT LINES. DOMESTIC WATER LINES (HOT AND COLD) AT 1/2" - 2" IN MRI AREA, TESTED AT 160 PSI. | |
| 03/27/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, KNUCKLE AREA - WASTE AND VENT LINES (2" - 4") UNDER HYDRO TEST. | |
| 03/25/2018 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC HOT AND COLD WATER LINES (1/2" - 2"). LEVELS #3, 7, 8 KNUCKLE AREAS. TESTED AT 160 PSI; OK TO INSULATE PROGRESS AREAS. | |
| 03/20/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, MRI AREA: GL: K-L/5-6; WASTE AND VENT LINES AT 2" - 4". | |
| 03/19/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, RESTROOM AT GL: F/9 - WASTE AND VENT LINES (2" - 4") UNDER TEST. | |
| 03/16/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #9, TOWER #4, SHAFT #9: DOMESTIC HOT/COLD WATER LINES AT 1" - 4"; TESTED AT CITY WATER PRESSURE LEVEL. LEVE #8, KNUCKLE AREA; WATE AND VENT LINES AT 2" - 4" (LINES UNDER TEST TO LEVEL #7) | |
| 03/15/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, GL: L/6-7; 2" REVENT LINES UNDER TEST IN PRE-POST OP AREA. | |
| 03/14/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, PRE-POST OP AREA: GL: L/6-7; WASTE AND VENT LINES AT 2" - 4". LEVEL #2, MRI AREA (SOUTH), GL: 6/L-J AT 2" - 4" WASTE AND VENT LINES. | |
| 03/13/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #1 AND #2: WASTE LINES (3" - 4") AT GL: I/8-13. | |
| 03/12/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, POST-OP AREA; WASTE AND VENT LINES (2" - 4") AT GL: H/8 - I/7. LEVEL #1, WASTE LINES 2" - 4" AT GL: I/6. | |
| 03/08/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, KITCHEN AREAS; DOMESTIC WATER (HOT AND COLD) LINES AT 1/2" - 2" AT GL: F/9. | |
| 03/07/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #7, KNUCKLE AREA: HOT/COLD DOMESTIC WATER - LINES AT 1/2" - 1 1/2". | |
| 03/06/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1 AND #2; WASTE AND VENT LINES (2" - 4"). GL: K-L/9-10. | |
| 03/05/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, AT GL: I - J/8; K/8-10; WASTE AND VENT LINES (2" - 4"). DOMESTIC HOT/COLD WATER LINES 1/2" - 32" AT GL: H-L/10. | |
| 03/01/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #1 AND #2, POST-OP AREA AT GL: K/8 - WASTE AND VENT LINES AT 2" - 4". | |
| 02/28/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #1 AND #2, AREA 7, GL: I/7, WASTE AND VENT LINES (2" TO 4"), RESTROOMS AND POST OP ROOMS. | |
| 02/27/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #2 - 4; 3" - 4" WAST LINES AT GL: I/6. LEVELS #6 - 7, WASTE AND VENT LINES (2 1.2" - 4") IN KNUCKLE AREAS. | |
| 02/22/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, AREA #5; WASTE AND VENT LINES (2" - 4") AT GL: H/10. | |
| 02/21/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6, KNUCKLE AREA, DOMESTIC HOT/COLD WATER LINES IN 1/2" - 1 1/2" LINES TESTED AT 160 PSI. LEVEL #8, BURN ROOM #840130 - LINES AT 1/2" - 1 1/2" - TESTED AT 150 PSI. | |
| 02/20/2018 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2" - 4"); LEVEL #1, AREAS #1, 2, 4, 5. | |
| 02/15/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, AREAS #1 AND #4; WASTE AND VENT LINES AT 2" - 4". AREAS #8 AND #10; DOMESTIC HOT/COLD LINES: 1/2" - 2" LINES, ALL TESTED AT 150 PSI. | |
| 02/13/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5, KNUCKLE AREA: WASTE AND VENT LINES (2" - 4"). TESTED AT 160 PSI. LEVEL #6, KNUCKLE AREA - WASTE AND VENT LINES (2" - 4"); TESTED AT 160 PSI. LEVEL #2, AREAS #5 AND #10 - DOMESTIC HOT/COLD WATER LINES; AREA #5 AT 1/2" - 1 1/2", AREA #10: 1/2" - 3" LINES, TESTED AT 155 PSI | |
| 02/09/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, AREA #8, WASTE LINES (2" - 4") AT GL: 12/I - J. LEVEL #2, AREA #8 VENT LINES AT 2" - 4"; KITCHEN AREA WASTE AND VENT LINES AT 2" - 4". | |
| 02/07/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, AREA #5, WASTE AND VENT LINES AT 2" - 4" | |
| 02/06/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, WASTE AND VENT LINES: AREA #6; 2" - 4" LINES AT GL: H - J. AREA #7, 2" LINES AT J/4.2; AREA #10, LINES 1/2" - 2" DOMESTIC HOT AND COLD WATER SUPPLY AND RETURN LINES. | |
| 02/02/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, AREA #9; WASTE AND VENT LINES ( 2 1/2" - 4") AT GL: M/4.2 - 10. LEVEL #5, KNUCKLE AREA; DOMESTIC WATER HOT/COLD LINES ( 1/2" - 2"0 | |
| 01/31/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, AREA #3; WASTE AND VENT LINES: 1 1/2" - 4"; GL: H/10 - 12. | |
| 01/30/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, AREAS #7 - 9 - LINES AT 2" - 3", WASTE AND VENT LINES. LEVEL #2, AREA #3, DOMESTIC WATER IN RESTROOM. | |
| 01/29/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, MAIN ENTRY AREA: HOSE BIBS - 3/4" LINES - TTESTED AT 100 PSI. LEVEL #2, AREA #8, DOMESTIC WATER (HOT AND COLD) - LINES 1" - 3", TESTED AT 160 PSI: GL: E - K/10 -13. | |
| 01/25/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5, KNUCKLE AREA: VENT LINES AT 1 1/2" - 4" LINES - UNDER TEST. LEVEL #4, AREA #10, DOMESTIC WATER, SOFT WATER, R.O. (1/2" - 6" LINES) - TESTED AT 160 psi. | |
| 01/18/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #4, AREA #10, SOFT WATER (HOT AND COLD), R.O. WATER AT 3/4" - 1/2" -1", TESTED AT 160 PSI: BACK FLOW PREVENTORS, CART WASH AREA. WASTE AND VEN LINES IN AEA #3, 2" - 3". LEVEL #3, AREAS 7, 9, AND 10 AT 2" - 4". | |
| 01/17/2018 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (1 1/2" - 4"): LEVEL #2, AREAS 2, 3, 5, 6 - DOWN FROM LEVEL #3; LEVEL #8, TOWER #4, EAST, WEST, AND CENTER ROOMS (1 - 12, 23, 24). | |
| 01/16/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #8, TOWER #4, WASTE AND VENT LINES (2" - 4"), EAST AND MIDDLE SECTIONS; PATIENT ROOMS #13 - 24; DIALYSIS ROOMS, SHAFT #7 - R.O. WATER AT LEVELS #1 - 4. | |
| 01/11/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #8, TOWER #4, WASTE AND VENT LINES: 1 1/2" - 4"; WEST AND CENTER ROOMS. | |
| 01/10/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, AREA #5, WASTE AND VENT LINES (2" - 4"). LEVEL #1, SHAFT #7, SOFT WATER SYSTEM AT 4" LINES - TESTED AT 1`60 PSI. LEVEL #9, TOWER #4, WASTE AND VENT LINES AT 1 1/2" - 4" | |
| 01/04/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, AREAS #2 AND 3, WASTE AND VENT LINES AT 2" - 4". LEVEL #3, ROOM #407 - VALVE HANDLE NEEDS TO BE TURNED 180 DEGREES AWAY FROM WALL. | |
| 01/03/2018 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #1, 2, 3, AREAS #1 AND A PORTION OF #2: WASTE AND VENT LINES AT 1 1/2" TO 4". | |
| 12/21/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #2, AREA #3, DOMESTIC WATER LINES 1/2" - 2 1/2". | |
| 12/12/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #4, AREAS #4, 5, 7, 8: 4" FLOOR DRAINS DOWN TO LEVEL #3 (4" - 6"). LEVEL #3, AAREAS #4, 5, 7, 8; WASTE AND VENT LINES (2" -4") | |
| 11/17/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #7, TOWER #4 DOMESTIC WATER (HOT AND COLD) 1/2" - 4" LINES. TESTED AT 160 psi. WASTE AND VENT LINES IN DIALYSIS ROOMS AT 2" LINES THROUGHOUT: LEVELS 6 - 7, TOWER #4. | |
| 11/16/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #7, TOWER #4, SOFT WATER SYSTEM: 1/2" - 1 1/2" LINES - TESTED AT 150 psi. | |
| 11/14/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #7 AND 7, WASTE AND VENT LINES (2" LINES), TOWER #4. LEVEL #6, TOWER #4: PATIENT ROOMS # 1, 12, 13, 24. | |
| 11/08/2017 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER LINES: HOT; HOT RETURN, COLD. LEVEL #9, TOWER #5; LINES AT 1/2" - 3", TESTED AT 160 PSI. LEVEL #4, AREAS #6 - 10, LINES AT 1/2" - 6", ALL TESTED AT 160 PSI. | |
| 11/06/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, AREAS 4 - 6, VENT LINES AT 2 1/2" - 3". LEVEL #4, AREA #10; WASTE LINES AT 2" - 4" | |
| 11/01/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, AREA #5, WASTE AND VENT LINES (2 1/2" - 4") | |
| 10/27/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS 4 -3, AREAS 4 - 8; VENT LINES (2" - 4"). AREAS 6 - 8, WASTE LINES AT (2" - 4"). | |
| 10/26/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #4, VENT LINES AT (2" - 4"), AREAS #3 - 8. | |
| 10/23/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6, TOWER #4; PATIENT ROOMS #1 - 24; WASTE AND VENT LINES ALL AT 2" (LEVELS 5 - 7). DOMESTIC WATER LINES AT 1/2" - 4" LINES: ALL LINES TESTED AT 150 psi. | |
| 10/18/2017 | PLUMBING - INTERMEDIATE | Partial Approval | ADA RESTROOMS #1 AND #2; PATIENT ROOMS #22 AND #23 ON LEVEL #7, TOWER #4: WASTE AND VENT LINES AT 2" - 4" | |
| 10/17/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #7, TOWER #4: 3" WASTE AND VENT LINES (MIDDLE SECTION), ALL AREAS EXCEPT FOR RESTROOMS. | |
| 10/13/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6, TOWER #4, PATIENT ROOMS #1 - 12; 2" LINES TO 3" LINES. LEVEL #4, AREA 7 - 10, VENT LINES (2" - 4"); REHAB WASTE AT LEVEL #7, AREAS 2 AND 4. | |
| 10/12/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6, TOWER #4, MIDDLE SECTION - WASTE AND VENT LINES (2" - 6"); LEVEL #7, WASTE AND VENTS; TOWERE #4, (2" - 6"); PATIENT ROOMS #13 - 24. | |
| 10/12/2017 | PLUMBING - INTERMEDIATE | Partial Approval | ||
| 10/11/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2"), PATIENT ROOMS #1 - 12; LEVELS #6 - 7. | |
| 10/06/2017 | PLUMBING - INTERMEDIATE | Partial Approval | TOWER #4, RISERS FROM LEVELS 4 - 9; HOT AND COLD LINES TESTED AT 160 psi - LINES 1" - 6". LEVEL #3; HEATED HOT WATER; CHILLED WATER AT 3/4"- 1 1/2" LINES; TESTED AT 158 psi, AREAS #7 - 10. | |
| 10/04/2017 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER LINES (1/2" - 3"), TESTED AT 150 psi; LEVEL #8, TOWER #5. | |
| 10/03/2017 | PLUMBING - INTERMEDIATE | Partial Approval | 12" WASTE LINE; SHAFT #9, LEVEL #3 TO LEVEL #2, AREA 10. | |
| 09/29/2017 | PLUMBING - INTERMEDIATE | Partial Approval | 12" WASTE LINE FROM LEVEL #3 TO LEVEL #2, SHAFT #9, TOWER #4 | |
| 09/27/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #4 DOWN TO LEVEL #3, SHAFT #9, 12 " WASTE LINE: UNDER TEST. | |
| 09/22/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, AREAS #2, 3, 5, 6. WASTE AND VENT LINES (1 1/2" - 4": REVENT UP TO LEVEL #4. | |
| 09/20/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, AREA 10 GL: 13/M - N: 8" COPPER DOMESTIC WATER LINE - OK TO COVER. WASTE AND VEN LINES (1 1/2" - 4"); LEVEL #4, GL: F/8; LEVEL #3, TOWER #5: GL: C - G/ 7 - 8.25. | |
| 09/15/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #3, AREAS #3 - 4; WASTE AND VENT LINES (1 1/2" - 3") UP TO LEVEL #4. LEVEL #5, TOWER #4 - DOMESTIC WATER SYSTEM UNDER TEST AT 100 psi.. OK TO INSULATE PROGRESS AREAS.. | |
| 09/13/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #1, AREAS 6, 8, 10: WASTE LINES (2" - 3"); DOMESTIC WATER LINES (1" - 3"), TESTED AT 150 psi. | |
| 09/12/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #4 - 5, AREAS 8, 9, 10: VENT LINES AT 2" - 6", FROM LEVEL #4 UP TO LEVEL #5. | |
| 09/07/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #8, TOWER #4, PATIENT ROOMS #3 - 22. WASTE AND VENT LINES (1 1/2" - 4"). | |
| 09/05/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #8, TOWER #4: PATIENT ROOMS #1 - 24; WASTE ANDVENT LINES("1 1/2 - 4"LINES) | |
| 08/31/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENTS AT LEVEL #9 , RESTROOMS #104, 105 (3" - 4" LINES). | |
| 08/30/2017 | PLUMBING - INTERMEDIATE | Partial Approval | 8" FUEL WASTE LINE AT STAIRWELL #2; LEVELS 1 - 10. | |
| 08/28/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #9, TOWER #5, WASTE AND VENT LINES (2" - 6") ALL LINES EXCEPT FOR STAFF RESTROOMS. LEVEL #7, TOWER #5, DOMESTIC WATER LINES (1/2" - 3"): TESTED AT 150psi. | |
| 08/23/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES: LEVEL #9, TOWER #5; PATIENT ROOMS #9 - 12, 3 - 24 (2" - 4" LINES) | |
| 08/17/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS #7, 8, 9; WEST RESTROOMS #9104 - 105, 8104 - 105, 7104 - 105 (2" - 4") LINES. LEVEL #9, TOWER 5, PATIENT ROOMS 1 - 3; 18 - 24 LAVES (1 1/2" - 4") LINES. | |
| 08/16/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #9, TOWER #4; LAVES IN PATIENT ROOMS #13 - 17 WASTE AND VENT (2"). LEVEL #9, TOWER #4 EAST, PATIENT ROOMS #13 - 24; WASTE AND VENT LINES (2" - 4") | |
| 08/15/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6; TOWER #4: PATIENT ROOMS #1 - 12: WASTE AND VENT LINES (1 1/2" - 4") | |
| 08/07/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5, TOWER #4, WASTE AND VENT LINES (2" - 4") - EAST SIDE OF TOWER. | |
| 08/04/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2" - 4") ON LEVELS 6 - 7; RESTROOMS : 6104, 6105; 7104, 7105. | |
| 08/01/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS 5 AND 6; TOWER #4; WASTE AND VENT LINES (2 1/2" - 4"); WEST SIDE RESTROOMS. | |
| 07/28/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #8, WASTE AND VENT LINES ( 2 1/2" - 4" ), TOWER #5, MID SECTION. | |
| 07/26/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #7; WASTE AND VENTS (2" - 4") LAVES IN MIDDLE SECTION. | |
| 07/21/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6, TOWER 5; 3" WASTE AND VENT LINES; PATIENT ROOMS #1 - 3 LINES. PATIENT ROOMS #1 - 3, 13 - 24, 2 1/2" LAVE WASTE LINES. | |
| 07/06/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVELS 4 - 5, 4" WASTE LINE IN AREA 10, GL: L/12. | |
| 06/30/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5, AREAS #6, 8, 10; WASTE AND VENT LINES (2" - 4"); LDR 10, LDR - 12. GL: G.5 - M/11 - 13. LEVEL #8; AREAS #1 AND #2: CHILLED BEAM LINES, HOT HEATED WATER, COLD WATER LINES (1/2" - 2 1/2") TESTED AT 150 psi. | |
| 06/28/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2" - 4") AT LDR: 7 - 8; STAFF RESTROOMS AT SHAFT #14. | |
| 06/26/2017 | PLUMBING - INTERMEDIATE | Not ready for Inspection | DOMESTIC WATER LINES AT TOWER #5, LEVEL #5 WERE NOT UINDER TEST. | |
| 06/22/2017 | PLUMBING - INTERMEDIATE | Partial Approval | TOWER #4; WEST SIDE PATIENT ROOMS (WASTE AND VENT) 2" - 3" LINES AT LEVEL #5: 3 SINKS 2" - 3" LINES; AREAS 6, 8, 10. LEVEL #4 WASTE LINES AT 4" - 8". | |
| 06/07/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #4; SHAFT #6B, WASTE AND VENT LINES (2" - 2 1/2"): EXTENDED DOWN TO LEVEL #2. | |
| 06/02/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6: VENT LINES (2") FOR ROOMS #617 - 624. LEVEL #5, VENT LINES (2" - 2 1/2") FOR ROOMS 517 - 524. | |
| 05/31/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5: WASTE AND VENT LINES (2 1/2" - 4"); 3" RISERS IN ROOMS #13 - 24. STORM DRAIN AT LEVEL #5, AREA 5, PRIMARY DRAIN AT GL: 13/G - TO LEVEL #4 (6" AND 8" LINES) FLOW INTO 12" RISER LINE, 10" LINE AT SHAFT #9 FROM LEVEL #5 TO LEVEL #1. |
|
| 05/29/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6 (MID SECTION) WASTE AND VENT LINES; 2" - 4", LAVES FOR ROOMS 613 -616: ALL LINES UNDER TEST. | |
| 05/25/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #6, ROOM #0640101; WASTE AND VENT LINES (2" - 4"). LEVEL #5, ROOM 0540802: DOMESTIC WATER (HOT AND COLD), WASTE AND VENT LINES (2" - 4") ALL UNDER TEST. | |
| 05/24/2017 | PLUMBING - INTERMEDIATE | Partial Approval | ROOF DRAINS IN TOWER #4; LEVELS #10 - 4; 5 PRIMARY AND OVER-FLOW DRAINS (4" - 6"). | |
| 05/23/2017 | PLUMBING - INTERMEDIATE | Partial Approval | ROOF DRAINS IN AREA #5, 4" RISERS (5 EACH) PRIMARY AND OVER-FLOW DRAINS. LEVELS 10 - 4. | |
| 05/22/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5, WASTE AND VENT LINES (2" - 3") PATIENT ROOMS #1 - 12. ROOM #550130 - 2" - 3" WASTE LINES. LEVEL #6, PATIENT ROOMS (LAVS) #1 - 12 (2" - 3"). | |
| 05/18/2017 | PLUMBING - INTERMEDIATE | Partial Approval | TEMPORARY RESTROOMS AT LEVELS: 8 AND 9; DOMESTIC WATER LINES AT 1/2" - 2". WASTE AND VENT LINES AT 2" - 6". STORM DRAINS: AREA #3: PRIMARY DRAINS (3 EACH), AREA 6 (2 EACH) AT 6" - 10 AT LEVELS #5 - 2. | |
| 05/15/2017 | PLUMBING - INTERMEDIATE | Partial Approval | ROOF DRAIS IN SHAFT #3, LEVELS #2 - 5, OVER-FLOW DRAIN AT 6"; LEVELS 2 - 5; PRIMARY DRAINS AT 6" - 10" | |
| 05/12/2017 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER LINES (SUPPLY AND RETURN) IN SHAFT #7, LEVELS #1 - 4, UNDER TEST AT 150psi. | |
| 05/11/2017 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER LINES FOR MOCK-UP RESTROOMS # 9 - 12 AT LEVEL #5. | |
| 05/04/2017 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC HOT WATER LINES (SUPPLY AND RETURN TESTED AT 140 DEGREES) AIR TEST AT 110psi; AT LEVELS 1 - 4. | |
| 05/03/2017 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER LINES (3/4" - 2 1/2") AT TEMPORARY RESTROOMS ON LEVELS : 6 - 8. | |
| 05/01/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2 1/2" - 4") IN TEMPORARY RESTROOMS AT LEVELS 6 - 8. | |
| 04/27/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2" - 3") ON LEVEL #9; ROOMS #1 - 12 NORTH. LEVEL #8, WASTE AND VENT LINES (3" -4") ROOMS #1 - 12 NORTH. | |
| 04/26/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2" - 3") AT LEVEL #9 SOUTH, PATIENT ROOMS #13 -24. | |
| 04/25/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2' - 4") PATIENT ROOMS #13 - 24 ON LEVELS #7 AND #8 (SOUTH). TEMPORARY BATHROOMS ON LEVELS #5 AND #6 (2" - 4") LINES. | |
| 04/20/2017 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER LINES (3/4" - 2" LINES) AT TEMPORARY BATHROOMS, GL: F/11, LEVELS 4 - 5; TESTED AT 106 psi. | |
| 04/19/2017 | PLUMBING - INTERMEDIATE | Partial Approval | SHAFT #3;8 LINES TESTED AT 165 psi - LEVELS 1 - 4. SHAFT #7, 4 LINES TESTED AT 170 psi - LEVELS 1 - 3. NATURAL GAS LINE ON LEVEL #4, SHAFT #7. TEMPORARY RESTROOMS: WASTE AND VENT LIES ONLEVELS 3 - 5; HYDRONIC TESTED. | |
| 04/18/2017 | PLUMBING - INTERMEDIATE | Partial Approval | PATIENT ROOMS #1 - 12; WASTE AND VENT LINES (NORTH), LEVELS #6 AND #7. RISER LINE FOR TEMPORARY BATHROMS ON LEVELS #2, AND #3. | |
| 04/17/2017 | PLUMBING - INTERMEDIATE | Partial Approval | VENT AND WASTE LINES AT LEVELS 6 AND 7: 4" - 2" LINES. | |
| 04/13/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5, SHAFT #5: 2 EACH 4" GALVANIZED STORM LINES. LEVEL #5, AREA 9/10, OVER-FLOW ROOF DRAIN TESTED FROM LEVEL #5 TO LEVEL #2. | |
| 04/05/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #5 TO LEVEL #6: PATIENT ROOMS (SOUTH) #13 - 24. | |
| 04/02/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT LINES (2" - 4") AT LEVELS 5 AND 6 NORTH: PATIENT ROOMS 01 - 12. | |
| 03/19/2017 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE/VENT LINES AT LEVEL #4: G/4.2 -11.2 (NORTH); BATHROOMS #1 - 6. LEVEL #5 GL: D - G/4.2 - 11.2: MOCK-UP BATHROOMS, RESTROOM SINKS. | |
| 03/06/2017 | PLUMBING - INTERMEDIATE | Partial Approval | LEVEL #4, WASTE AND VENT LINES (2 1/2" - 6") IN HALLWAY AREA. LEVEL #5, SOUTH RESTROOMS (5) - 2" - 4" WASTE AND VENT LINES. |