Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T16CM02176

Parcel: 12310001H


Addresses:

1625 N CAMPBELL AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/07/2019 PLUMBING - ROUGH, SOIL Approved
05/03/2018 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1, LAUNDRY ROOM - WASTE LINES (2" - 4"). OK TO COVER PROGRESS AREAS.
03/19/2018 PLUMBING - ROUGH, SOIL Partial Approval WASTE AND VENT LINES (2" - 4") AT GL: F-I/3-9. OK TO COVER PROGRESS AREA.
03/06/2018 PLUMBING - ROUGH, SOIL Partial Approval PHARMACY AREA AT GL: H/5-7; 2"- 4" LINES. OK TO COVER PROGRESS AREAS.
01/17/2018 PLUMBING - ROUGH, SOIL Partial Approval 4" GAS LINE AT SOUTH EAST CORNER OF BUILDING - TESTED AT 100 PSI. OK TO COVER PROGRESS AREA.
01/16/2018 PLUMBING - ROUGH, SOIL Partial Approval GAS LINE AT S.E. CORNER OF BUILDIDNG - 4" LINE FROM GAS METER TO BUILDING EXTERIOR. OK TO PRIME, TAPE AND COVER LINE; TRACER WIRE IN PLACE. OK TO COVER PROGRESS AREAS
10/27/2017 PLUMBING - ROUGH, SOIL Partial Approval PRIVATE WATER LINES (2 @ 12" AND 1 @ 8") FROM WARREN AVENUE NORTH APPROXIMATELY 150' TO AREA OF AMBULANCE CANOPY.
10/12/2017 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1, (2" - 6") LINES, GL: 6.5 - 7/I.5 - J. OK TO COVER PROGRESS AREA.
10/05/2017 PLUMBING - ROUGH, SOIL Partial Approval UNDERGROUND LINES 3" AND 4" AT GL: J.5/11 - 12 ON LEVEL #1. OK TO COVER PROGRESS AREA.
09/01/2017 PLUMBING - ROUGH, SOIL Partial Approval 12" CHILLED WATER LINE (NUDER GROUND) - TO TUNNEL FROM SOUTH EAST PORTION OF BUILDING. APPROXIMATELY 40': OK TO COVER PROGRESS AREA.
07/12/2017 PLUMBING - ROUGH, SOIL Partial Approval SANITARY WASTE LINE (6") AT GL: J/4.2 - 6. OK TO COVER PROGRESS AREA.
06/29/2017 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1; 8" WASTE LINE AT GL: I/4.2 - 6. OK TO COVER PROGRESS AREA. KITCHEN AREA; GL: F/4.2 - 5 (2 SETS) 1/2" COPPER LINES (INSULATED FOR PROTECTION IN GROUND.
06/28/2017 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1, WASTE AND VENT LINES (3" - 4") AT GL: K - M/7.5 - 10. OK TO COVER PROGRESS AREAS.
06/27/2017 PLUMBING - ROUGH, SOIL Partial Approval WASTE AND VENT LINES AT GGL: 6/K - L, K/11: 2" - 4" LINES. OK TO COVER PROGRESS AREAS.
06/21/2017 PLUMBING - ROUGH, SOIL Partial Approval 16" SANITARY SEWER INE CONNECTED TO MAIN LINE AT K/12. OK TO COVER AT PROGRESS AREAS.
06/20/2017 PLUMBING - ROUGH, SOIL Not ready for Inspection 16 WASTE STORM LINE IS NOT CONNECTED TO MAIN STORM LINE (TOWER #4, LEVEL #1).
06/19/2017 PLUMBING - ROUGH, SOIL Partial Approval WASTE LINES (4" 16" STORM); AREAS 3, 4, 5; GL: G/4.5 - 6.5; K - G/6.5; J.5/6 - 10.5; 9.5/I.5 -J; J/9.5 - 11.5; I - J/10.5 - 11.5. OK TO COVER PROGRESS AREAS.
06/09/2017 PLUMBING - ROUGH, SOIL Partial Approval COPPER WATER LINES (2 1/2" 0 3" COPPER) AT ZONE #2, LEVEL #1: 2 CHILLED WATER LINES, 2 HOT WATER LINES; 1 DOMESTIC LINE: TESTED AT 160 psi. GREASE WASTE LINES (2" - 4") AT GL: E - G/4.2 - 5, LINES FEED INTO 6" WASTE LINE.
06/08/2017 PLUMBING - ROUGH, SOIL Partial Approval TWO EACH 12" CHILLED WATER LINES TO BE TIED INTO EXISTING 16" LINES; TESTED AT 150psi. GL: 15/E - F. OK TO COVER PROGRESS AREA.
05/29/2017 PLUMBING - ROUGH, SOIL Partial Approval 36" STORM DRAIN AT GL: C/4.2 - E.5: JOINTS AND FASTENERS ALL SEALED.
05/24/2017 PLUMBING - ROUGH, SOIL Partial Approval PVC WASTE LINES (2' - 6") AT GL: 5 - 12/H -D. OK TO COVER PROGRESS AREAS.
05/23/2017 PLUMBING - ROUGH, SOIL Partial Approval GREASE LINES (2" - 4") NEW AGE PIPING. GL: D - G/5 - 11. OK TO COVER PROGRESS AREAS.
05/12/2017 PLUMBING - ROUGH, SOIL Partial Approval WASTE LINES (2" - 4" PIPING ((NEW AGE PIPE)), KITCHEN AREA AT GGL: 4.5 - 5/D - G. OK TO COVER PROGRESS AREAS.
04/21/2017 PLUMBING - ROUGH, SOIL Partial Approval 4 EACH 12" STORM DRAIN LINES AT GL: I/ 12. OK TO COVER PROGRESS AREA.