Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16CM02176

Parcel: 12310001H


Addresses:

1625 N CAMPBELL AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/07/2019 PLUMBING - ROUGH, SOIL Approved
05/03/2018 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1, LAUNDRY ROOM - WASTE LINES (2" - 4"). OK TO COVER PROGRESS AREAS.
03/19/2018 PLUMBING - ROUGH, SOIL Partial Approval WASTE AND VENT LINES (2" - 4") AT GL: F-I/3-9. OK TO COVER PROGRESS AREA.
03/06/2018 PLUMBING - ROUGH, SOIL Partial Approval PHARMACY AREA AT GL: H/5-7; 2"- 4" LINES. OK TO COVER PROGRESS AREAS.
01/17/2018 PLUMBING - ROUGH, SOIL Partial Approval 4" GAS LINE AT SOUTH EAST CORNER OF BUILDING - TESTED AT 100 PSI. OK TO COVER PROGRESS AREA.
01/16/2018 PLUMBING - ROUGH, SOIL Partial Approval GAS LINE AT S.E. CORNER OF BUILDIDNG - 4" LINE FROM GAS METER TO BUILDING EXTERIOR. OK TO PRIME, TAPE AND COVER LINE; TRACER WIRE IN PLACE. OK TO COVER PROGRESS AREAS
10/27/2017 PLUMBING - ROUGH, SOIL Partial Approval PRIVATE WATER LINES (2 @ 12" AND 1 @ 8") FROM WARREN AVENUE NORTH APPROXIMATELY 150' TO AREA OF AMBULANCE CANOPY.
10/12/2017 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1, (2" - 6") LINES, GL: 6.5 - 7/I.5 - J. OK TO COVER PROGRESS AREA.
10/05/2017 PLUMBING - ROUGH, SOIL Partial Approval UNDERGROUND LINES 3" AND 4" AT GL: J.5/11 - 12 ON LEVEL #1. OK TO COVER PROGRESS AREA.
09/01/2017 PLUMBING - ROUGH, SOIL Partial Approval 12" CHILLED WATER LINE (NUDER GROUND) - TO TUNNEL FROM SOUTH EAST PORTION OF BUILDING. APPROXIMATELY 40': OK TO COVER PROGRESS AREA.
07/12/2017 PLUMBING - ROUGH, SOIL Partial Approval SANITARY WASTE LINE (6") AT GL: J/4.2 - 6. OK TO COVER PROGRESS AREA.
06/29/2017 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1; 8" WASTE LINE AT GL: I/4.2 - 6. OK TO COVER PROGRESS AREA. KITCHEN AREA; GL: F/4.2 - 5 (2 SETS) 1/2" COPPER LINES (INSULATED FOR PROTECTION IN GROUND.
06/28/2017 PLUMBING - ROUGH, SOIL Partial Approval LEVEL #1, WASTE AND VENT LINES (3" - 4") AT GL: K - M/7.5 - 10. OK TO COVER PROGRESS AREAS.
06/27/2017 PLUMBING - ROUGH, SOIL Partial Approval WASTE AND VENT LINES AT GGL: 6/K - L, K/11: 2" - 4" LINES. OK TO COVER PROGRESS AREAS.
06/21/2017 PLUMBING - ROUGH, SOIL Partial Approval 16" SANITARY SEWER INE CONNECTED TO MAIN LINE AT K/12. OK TO COVER AT PROGRESS AREAS.
06/20/2017 PLUMBING - ROUGH, SOIL Not ready for Inspection 16 WASTE STORM LINE IS NOT CONNECTED TO MAIN STORM LINE (TOWER #4, LEVEL #1).
06/19/2017 PLUMBING - ROUGH, SOIL Partial Approval WASTE LINES (4" 16" STORM); AREAS 3, 4, 5; GL: G/4.5 - 6.5; K - G/6.5; J.5/6 - 10.5; 9.5/I.5 -J; J/9.5 - 11.5; I - J/10.5 - 11.5. OK TO COVER PROGRESS AREAS.
06/09/2017 PLUMBING - ROUGH, SOIL Partial Approval COPPER WATER LINES (2 1/2" 0 3" COPPER) AT ZONE #2, LEVEL #1: 2 CHILLED WATER LINES, 2 HOT WATER LINES; 1 DOMESTIC LINE: TESTED AT 160 psi. GREASE WASTE LINES (2" - 4") AT GL: E - G/4.2 - 5, LINES FEED INTO 6" WASTE LINE.
06/08/2017 PLUMBING - ROUGH, SOIL Partial Approval TWO EACH 12" CHILLED WATER LINES TO BE TIED INTO EXISTING 16" LINES; TESTED AT 150psi. GL: 15/E - F. OK TO COVER PROGRESS AREA.
05/29/2017 PLUMBING - ROUGH, SOIL Partial Approval 36" STORM DRAIN AT GL: C/4.2 - E.5: JOINTS AND FASTENERS ALL SEALED.
05/24/2017 PLUMBING - ROUGH, SOIL Partial Approval PVC WASTE LINES (2' - 6") AT GL: 5 - 12/H -D. OK TO COVER PROGRESS AREAS.
05/23/2017 PLUMBING - ROUGH, SOIL Partial Approval GREASE LINES (2" - 4") NEW AGE PIPING. GL: D - G/5 - 11. OK TO COVER PROGRESS AREAS.
05/12/2017 PLUMBING - ROUGH, SOIL Partial Approval WASTE LINES (2" - 4" PIPING ((NEW AGE PIPE)), KITCHEN AREA AT GGL: 4.5 - 5/D - G. OK TO COVER PROGRESS AREAS.
04/21/2017 PLUMBING - ROUGH, SOIL Partial Approval 4 EACH 12" STORM DRAIN LINES AT GL: I/ 12. OK TO COVER PROGRESS AREA.