Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Apply Date:
05/25/2006
Applicant:
GODFREY, PRESTON NOEL
Description:
NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Architects:
  • FERRANTI, KIM MERRIMAN
Contractors:
  • LLOYD CONSTRUCTION COMPANY INC ,

Permit Reviews

Permit Number - T06CM03151
Permit Status: C of o
Permit Description: NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Start Date Submittal Complete Date Status  
01/24/2007 REVISION - - 1ST 02/07/2007 COMPLETED Review Details
02/20/2007 REVISION - - 3RD 02/20/2007 COMPLETED Review Details
03/08/2007 REVISION - - 4TH 03/15/2007 COMPLETED Review Details
03/23/2007 3RD PARTY REVIEW-REVISION/OTHER 04/02/2007 COMPLETED Review Details
04/11/2007 3RD PARTY REVIEW-REVISION/OTHER 04/11/2007 COMPLETED Review Details
04/26/2007 3RD PARTY REVIEW-REVISION/OTHER 04/26/2007 COMPLETED Review Details
05/08/2007 3RD PARTY REVIEW-REVISION/OTHER 05/11/2007 COMPLETED Review Details
05/25/2006 PLANS OK TO SUBMIT - COMM 05/25/2006 COMPLETED Review Details
05/25/2006 COMMERCIAL NEW 08/04/2006 COMPLETED Review Details
07/14/2006 OTHER 09/07/2006 COMPLETED Review Details
07/19/2007 3RD PARTY REVIEW-REVISION/OTHER 07/27/2007 COMPLETED Review Details
08/07/2007 POST 3RD PARTY REVIEW 08/31/2007 COMPLETED Review Details
10/11/2006 PLANS OK TO SUBMIT - SITE 10/13/2006 COMPLETED Review Details
10/11/2006 RESUBMITTAL 12/05/2006 COMPLETED Review Details
10/26/2007 REVISION - - 5TH 10/26/2007 COMPLETED Review Details
12/05/2006 SITE 12/20/2006 COMPLETED Review Details
12/13/2007 REVISION - - 6TH 12/13/2007 COMPLETED Review Details
12/20/2006 RESUBMITTAL 12/20/2006 COMPLETED Review Details
12/20/2006 RESUBMITTAL 12/28/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM03151
Permit Status: C of o
Permit Description: NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Total Outstanding Activity Conditions - 1
Date Name
05/25/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T06CM03151
Permit Description: NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Total Completed Inspections - 45
Date Description Inspector Results Comments
02/16/2007 SEWER - PRE CONSTRUCTION MTG BBENEDON Approved IVRS - Inspection :*
PETER W/LLOYD 471-8414

PAUL DOHERTY
RWS APPROVED PLAN
6" SDR REQUIRES TRACER WIRE
4" CLEANOUTS NOT TO EXCEED 100' TOTAL. INSTALL PER UPC.
1% FALL WILL REQUIRE VERIFICATION OF GRADE
CALL FOR DAILY PROGRESS INSPECTION.
CALL FOR INSP ON PRIVATE MANHOLE
02/27/2007 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
02/27/2007 PLUMBING - ROUGH, SOIL BBENEDON Approved IVRS - Inspection :*
06/01/2007 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection :*
ALL EXTERIOR WALL FRAMING OK
06/28/2007 STUCCO MESH AQUIROZ Approved IVRS - Inspection :*
08/17/2007 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
08/23/2007 ELECTRIC - CABLE DROP CCLEMENS Approved IVRS - Inspection :*
OVERHEAD TO PIPES
1. NEED BUSHING FOR PVC 352.46
2. #6 AND SMALLER GROUND TO BE GREEN ENTIRE LENGTH
NEC 250.119
3. PROVIDE TORQUE LETTER -- NEC 110.3B
4. IDENTIFY DISCONNECTS -- NEC 110, INSTALL FUSES
DO NOT ENERGIZE EQUIPMENT BEFORE SAFE TO DO SO
LOCKOUT AS NEEDED
08/23/2007 ELECTRIC - SERVICE UPGRADE CCLEMENS Approved IVRS - Inspection :*
08/24/2007 TEP CLEARANCE - AM BFLORES Approved TEC PER C.CLEMENS
08/30/2007 PLUMBING - SEWER HCS CONNECT BBENEDON Approved IVRS - Inspection :*
TEST OK
CONNECTION OK
VERIFICATION OF GRADE FROM SCHERRER ENGINEER
09/04/2007 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
09/04/2007 FRAMING AQUIROZ Approved IVRS - Inspection :*
10/01/2007 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
10/01/2007 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
10/01/2007 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection :*
10/01/2007 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
10/01/2007 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*
10/01/2007 STEM WALL/RETAINING WALL AQUIROZ Approved IVRS - Inspection :*
10/29/2007 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
3" PVC YARDWATER INSTALLED PER PLAN
OK TO COVER
11/14/2007 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
11/27/2007 FIRE - ALARM FINAL LTHOMAS Approved
11/28/2007 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
11/28/2007 FIRE SPKLR - FINAL LTHOMAS Approved
11/28/2007 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
11/28/2007 FIRE - FINAL LTHOMAS Approved
11/29/2007 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
11/29/2007 SIGN - FINAL JSONKIN Approved IVRS - Inspection :*
11/30/2007 MECHANICAL - PROGRESS MRAMBER Approved
11/30/2007 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
11/30/2007 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
PROVIDE POWER TO SMOKE DAMPERS
12/07/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
NOTE: CONTRACTOR TO DEMO (REMOVE) TEMPORARY WIRING TO CONSTRUCTION TRAILER AND ENERGIZE HOT WATER TANK
12/07/2007 ELECTRIC - OUTDOOR LIGHTING CCLEMENS Approved IVRS - Inspection :*
12/07/2007 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
12/07/2007 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
12/07/2007 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
12/10/2007 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
- NEED IRR. ASSEM. AND CERT.
- NEED BAC T REPORT
- NO HOSE THREADS W/OUT VAC BREAKERS - INSTALL AERATORS AT LAUNDRY
- HALL SINK IS MISSING CLIPS, IS LEAKING AND HANDLES ARE BACKWARDS
- CLAMP ALL DW HOSES 2" BELOW SINK W/PIPE CLAMPS
- ADJUST WATER TEMP. INSULATE AT WH
- INSTALL STRAINER IN FLOOR SINKS
- HAND HELD SHOWER HEADS.
- KIT. SINK CO AND PIPE
- TRAP PRIMER? CO COVERS
12/10/2007 PLUMBING - PROGRESS BBENEDON Approved IVRS - Inspection :*
12/10/2007 PLUMBING - ROOF DRAINS BBENEDON Approved IVRS - Inspection :*
12/10/2007 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :*
12/19/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
OK C OF O
12/19/2007 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :*
12/20/2007 PERMIT FINALED ACONNOR Approved
12/20/2007 NPPO - FINAL ACONNOR Approved
12/20/2007 LANDSCAPE - FINAL ACONNOR Approved
12/20/2007 ENGINEERING - FINAL MRUSSO Approved