Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06CM03151
Permit Details
Apply Date:
05/25/2006
Applicant:
GODFREY, PRESTON NOEL
Description:
NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Architects:
- FERRANTI, KIM MERRIMAN
Contractors:
- LLOYD CONSTRUCTION COMPANY INC ,
Permit Reviews
Permit Number - T06CM03151
Permit Status: C of o
Permit Description: NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/24/2007 | REVISION - - 1ST | 02/07/2007 | COMPLETED |
02/20/2007 | REVISION - - 3RD | 02/20/2007 | COMPLETED |
03/08/2007 | REVISION - - 4TH | 03/15/2007 | COMPLETED |
03/23/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 04/02/2007 | COMPLETED |
04/11/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 04/11/2007 | COMPLETED |
04/26/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 04/26/2007 | COMPLETED |
05/08/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 05/11/2007 | COMPLETED |
05/25/2006 | PLANS OK TO SUBMIT - COMM | 05/25/2006 | COMPLETED |
05/25/2006 | COMMERCIAL NEW | 08/04/2006 | COMPLETED |
07/14/2006 | OTHER | 09/07/2006 | COMPLETED |
07/19/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 07/27/2007 | COMPLETED |
08/07/2007 | POST 3RD PARTY REVIEW | 08/31/2007 | COMPLETED |
10/11/2006 | PLANS OK TO SUBMIT - SITE | 10/13/2006 | COMPLETED |
10/11/2006 | RESUBMITTAL | 12/05/2006 | COMPLETED |
10/26/2007 | REVISION - - 5TH | 10/26/2007 | COMPLETED |
12/05/2006 | SITE | 12/20/2006 | COMPLETED |
12/13/2007 | REVISION - - 6TH | 12/13/2007 | COMPLETED |
12/20/2006 | RESUBMITTAL | 12/20/2006 | COMPLETED |
12/20/2006 | RESUBMITTAL | 12/28/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM03151
Permit Status: C of o
Permit Description: NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/25/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM03151
Permit Description: NEW: TRANSIENT LODGING FOR FAMILIES OF CHILDREN RECEIVING CANCER TREATMENT
Total Completed Inspections - 45
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2007 | SEWER - PRE CONSTRUCTION MTG | BBENEDON | Approved | IVRS - Inspection :* PETER W/LLOYD 471-8414 PAUL DOHERTY RWS APPROVED PLAN 6" SDR REQUIRES TRACER WIRE 4" CLEANOUTS NOT TO EXCEED 100' TOTAL. INSTALL PER UPC. 1% FALL WILL REQUIRE VERIFICATION OF GRADE CALL FOR DAILY PROGRESS INSPECTION. CALL FOR INSP ON PRIVATE MANHOLE |
02/27/2007 | PLUMBING - PRE SLAB | BBENEDON | Approved | IVRS - Inspection :* |
02/27/2007 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
06/01/2007 | EXT METAL CLIPS/EXT SHEATHING | AQUIROZ | Approved | IVRS - Inspection :* ALL EXTERIOR WALL FRAMING OK |
06/28/2007 | STUCCO MESH | AQUIROZ | Approved | IVRS - Inspection :* |
08/17/2007 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :* |
08/23/2007 | ELECTRIC - CABLE DROP | CCLEMENS | Approved | IVRS - Inspection :* OVERHEAD TO PIPES 1. NEED BUSHING FOR PVC 352.46 2. #6 AND SMALLER GROUND TO BE GREEN ENTIRE LENGTH NEC 250.119 3. PROVIDE TORQUE LETTER -- NEC 110.3B 4. IDENTIFY DISCONNECTS -- NEC 110, INSTALL FUSES DO NOT ENERGIZE EQUIPMENT BEFORE SAFE TO DO SO LOCKOUT AS NEEDED |
08/23/2007 | ELECTRIC - SERVICE UPGRADE | CCLEMENS | Approved | IVRS - Inspection :* |
08/24/2007 | TEP CLEARANCE - AM | BFLORES | Approved | TEC PER C.CLEMENS |
08/30/2007 | PLUMBING - SEWER HCS CONNECT | BBENEDON | Approved | IVRS - Inspection :* TEST OK CONNECTION OK VERIFICATION OF GRADE FROM SCHERRER ENGINEER |
09/04/2007 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
09/04/2007 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
10/01/2007 | MECHANICAL - ABOVE CEILING | MRAMBER | Approved | IVRS - Inspection :* |
10/01/2007 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection :* |
10/01/2007 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* |
10/01/2007 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
10/01/2007 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :* |
10/01/2007 | STEM WALL/RETAINING WALL | AQUIROZ | Approved | IVRS - Inspection :* |
10/29/2007 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection :* 3" PVC YARDWATER INSTALLED PER PLAN OK TO COVER |
11/14/2007 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
11/27/2007 | FIRE - ALARM FINAL | LTHOMAS | Approved | |
11/28/2007 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
11/28/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
11/28/2007 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
11/28/2007 | FIRE - FINAL | LTHOMAS | Approved | |
11/29/2007 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
11/29/2007 | SIGN - FINAL | JSONKIN | Approved | IVRS - Inspection :* |
11/30/2007 | MECHANICAL - PROGRESS | MRAMBER | Approved | |
11/30/2007 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* |
11/30/2007 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* PROVIDE POWER TO SMOKE DAMPERS |
12/07/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* NOTE: CONTRACTOR TO DEMO (REMOVE) TEMPORARY WIRING TO CONSTRUCTION TRAILER AND ENERGIZE HOT WATER TANK |
12/07/2007 | ELECTRIC - OUTDOOR LIGHTING | CCLEMENS | Approved | IVRS - Inspection :* |
12/07/2007 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* |
12/07/2007 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* |
12/07/2007 | ELECTRIC - UNDERGROUND | CCLEMENS | Approved | IVRS - Inspection :* |
12/10/2007 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* - NEED IRR. ASSEM. AND CERT. - NEED BAC T REPORT - NO HOSE THREADS W/OUT VAC BREAKERS - INSTALL AERATORS AT LAUNDRY - HALL SINK IS MISSING CLIPS, IS LEAKING AND HANDLES ARE BACKWARDS - CLAMP ALL DW HOSES 2" BELOW SINK W/PIPE CLAMPS - ADJUST WATER TEMP. INSULATE AT WH - INSTALL STRAINER IN FLOOR SINKS - HAND HELD SHOWER HEADS. - KIT. SINK CO AND PIPE - TRAP PRIMER? CO COVERS |
12/10/2007 | PLUMBING - PROGRESS | BBENEDON | Approved | IVRS - Inspection :* |
12/10/2007 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* |
12/10/2007 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* |
12/19/2007 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* OK C OF O |
12/19/2007 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection :* |
12/20/2007 | PERMIT FINALED | ACONNOR | Approved | |
12/20/2007 | NPPO - FINAL | ACONNOR | Approved | |
12/20/2007 | LANDSCAPE - FINAL | ACONNOR | Approved | |
12/20/2007 | ENGINEERING - FINAL | MRUSSO | Approved |