Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM03151

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
- NEED IRR. ASSEM. AND CERT.
- NEED BAC T REPORT
- NO HOSE THREADS W/OUT VAC BREAKERS - INSTALL AERATORS AT LAUNDRY
- HALL SINK IS MISSING CLIPS, IS LEAKING AND HANDLES ARE BACKWARDS
- CLAMP ALL DW HOSES 2" BELOW SINK W/PIPE CLAMPS
- ADJUST WATER TEMP. INSULATE AT WH
- INSTALL STRAINER IN FLOOR SINKS
- HAND HELD SHOWER HEADS.
- KIT. SINK CO AND PIPE
- TRAP PRIMER? CO COVERS
09/25/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES OK TO COVER
KEEP OPEN DRAIN PIPES PLUGGED
USE OF WATERLESS URINAL OK PER CASE #070904
ONLY REMAINING ITEM IS THE CONFLICT OF PIPING SPECIFICATIONS.
09/05/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 128, 129 AND 133 TEST OK,
REMOVE SHARP METAL TOUCHING VENT
08/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
UPSTAIRS SHOWER PAN TESTS OK
RUN TEST W/HOSE
ADA SHOWERS
SECURE MECHANICAL CLOSET FLANGES
07/27/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 213-218 DWV TEST OK
PIPE INSULATION OK
RM 220 DWV AND WATER W/INSULATION OK
OK TO COVER WALLS
DO NOT COVER CEILING UNTIL HANGERS,
VALVE HANDLE EXTENSION AND BRAZING SPECIFICATIONS HAVE BEEN MET
07/25/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 201-204 OK TO COVER AFTER INSULATING
RMS 213-218 OK TO INSULATE COPPER
DWV NOT UNDER TEST
RM 239 INSULATION OK - EXPOSE CW HAMMER ARRESTOR
07/18/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- LETTER RECEIVED ALLOWING SWIVEL LOOP HANGERS FROM KELLY WRIGHT
- BREEZEWAY PIPING OK TO COVER
- PIPE INSULATION RMS 205-211 OK
- PIPE INSULATION TEST ON SHWRS AND CLOSET FLANGES OK IN RMS 221-227
- WATER PIPING IN 239, 236 AND 237 OK TO INSULATE
07/16/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV TEST ON ROOMS 201-211
USE CLEVIS HANGERS PER SPEC 2-8A
DOMESTIC WATER PIPING RMS 201-211 OK TO INSULATE
07/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV RMS 239, 236, 237 OK
SHWR DIVERTORS RMS 224-228 OK TO INSULATE
DOMESTIC WATER PIPING IN BREEZEWAY;
OK TO INSULATE AFTER PROVIDING CLEARANCE FOR PIPE INSULATION -- NOTE: SPEC #3.9F SPECS
OVERSIZED HANGERS TO ALLOW FOR CONTINUOUS INSULATION. ALSO, SEE SPECIFICATION #'S 2-2B, 2-8C AND
SEE SPEC 2-7A #2 REQUIRING BRAZED JOINTS ON 2 1/2" AND LARGER COPPER PIPING.
07/05/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/28/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 230, 231, 232, 233, 234 DWV AND COPPER OK EXCEPT FOR SHOWERS AND PIPE INSULATION
06/25/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 132, 138, 139, 140
227, 228, 225, 226, 224, 223, 222 AND 221 OK
EXCEPT FOR SHOWER STALLS & CLOSET FLANGES
PIPE INSULATION FIRST FLOOR N.E END OK
TEST FLOOR LEVEL OFFSET
06/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. #105, #106 & EWC AT #109
PVC & N/H TO 2ND FLOOR OK
2. TOILET ROOMS #112 AND BREAKROOM SINK IN #111
OK TO OVERHEAD - OK TO COVER THIS AREA
3. OK TO INSULATE OVERHEAD COPPER 1ST FLOOR