Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM03151

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/02/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES 2ND LEVEL LOBBY AREA
ENTRY TRACK LIGHT YET TO BE INSTALLED
11/01/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. STILL NEED TO GO OVER HOODS PROTECTION SYSTEM INTERLOCK OK CEILING TILES ROOM 136 AREA
10/26/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL CORRECT SIZE FUSES FOR AIR HANDLERS (PER DATA PLATE)
2. SECURE FIXTURES TO GRID
3. CHECK J-BOX FILL

IN CONTACTOR J-BOX
1. SELF TAP SCREWS NOT ALLOWED FOR GROUNDING CONNECTIONS
2. NEED CORRECT SIZE GROUND TO ENCLOSURE
3. EMT TO BE SECURED WITHIN 36" OF CONTACTOR ENCLOSURE

PARTIAL INSPECTION ONLY ELECTRICIAN NOT ON SITE
10/09/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. DATA PLATES NEED TO BE IDENTIFIED ON ALL MECHANICAL EQUIPMENT THROUGHOUT JOB - NEC 440
2. HAVE OVERFILLED J-BOXES - NEC 314.16
3. LOW VOLTAGE WIRING TO BE COMPLETED AND RAN IN A NEAT AND WORKMANLIKE MANNER, PROPERLY SUPPORTED
4. PROVIDE LETTER FROM ENGINEER CONCERNING CODE COMPLIANCE FOR FC UNITS (7.6 AMPS) 4 ON 20 AMP. CKT?

OK CEILING TILE AS DISCUSSED
09/25/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK 2ND FLOOR CORRIDOR EAST #241
2. OK 1ST FLOOR WEST OF MAIN LOBBY
3. ENSURE ALL EXITS GET THE WIRES #12 GAUGE
4. ENSURE TEMP POWER GETS REMOVED FROM 2ND FLOOR CORRIDOR
5. RECEIVED LETTER OF TORQUE FOR SWITCHGEAR
07/27/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
KITCHEN & DINING HALL
07/25/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
MISC. HARD LIDS ON SECOND LEVEL AS DISCUSSED
(PARTIAL BATHS AND HALL)