Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM03151
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/02/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES 2ND LEVEL LOBBY AREA ENTRY TRACK LIGHT YET TO BE INSTALLED |
|
11/01/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. STILL NEED TO GO OVER HOODS PROTECTION SYSTEM INTERLOCK OK CEILING TILES ROOM 136 AREA |
|
10/26/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL CORRECT SIZE FUSES FOR AIR HANDLERS (PER DATA PLATE) 2. SECURE FIXTURES TO GRID 3. CHECK J-BOX FILL IN CONTACTOR J-BOX 1. SELF TAP SCREWS NOT ALLOWED FOR GROUNDING CONNECTIONS 2. NEED CORRECT SIZE GROUND TO ENCLOSURE 3. EMT TO BE SECURED WITHIN 36" OF CONTACTOR ENCLOSURE PARTIAL INSPECTION ONLY ELECTRICIAN NOT ON SITE |
|
10/09/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. DATA PLATES NEED TO BE IDENTIFIED ON ALL MECHANICAL EQUIPMENT THROUGHOUT JOB - NEC 440 2. HAVE OVERFILLED J-BOXES - NEC 314.16 3. LOW VOLTAGE WIRING TO BE COMPLETED AND RAN IN A NEAT AND WORKMANLIKE MANNER, PROPERLY SUPPORTED 4. PROVIDE LETTER FROM ENGINEER CONCERNING CODE COMPLIANCE FOR FC UNITS (7.6 AMPS) 4 ON 20 AMP. CKT? OK CEILING TILE AS DISCUSSED |
|
09/25/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK 2ND FLOOR CORRIDOR EAST #241 2. OK 1ST FLOOR WEST OF MAIN LOBBY 3. ENSURE ALL EXITS GET THE WIRES #12 GAUGE 4. ENSURE TEMP POWER GETS REMOVED FROM 2ND FLOOR CORRIDOR 5. RECEIVED LETTER OF TORQUE FOR SWITCHGEAR |
|
07/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* KITCHEN & DINING HALL |
|
07/25/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* MISC. HARD LIDS ON SECOND LEVEL AS DISCUSSED (PARTIAL BATHS AND HALL) |