Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
08/17/2007 MECHANICAL - HOODS Approved IVRS - Inspection :*
08/10/2007 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/09/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCTS
OK TO FINISH FIRE WRAP
BUILD ACCESS DOORS PER INSTRUCTIONS
FIRE DAMPER CAULKING OK
PROVIDE APPROVED ACCESS DOORS
08/08/2007 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
GREASE DUCT CONNECTION TO HOOD LEAKING.
REPAIR & RECALL FOR INSPECTION
ACCESS DOOR NOT PER INSTALL INSTRUCTIONS
PROVIDE APPROVED ACCESS DOORS FOR FIRE DAMPERS
05/21/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1. EX. HOOD DUCT, PROGRESSING.
PORTION WRAPPED WITH 3 FIRE WRAP - 2 HR
AS NOTED MIN. 1 HR. ON SHT. M 101 KEYNOTE #1
VERTICAL DUCT DOWN TO 1ST FLOOR W/HORIZONTAL RUNS TO FRONT OF EACH HOOD.
2. FC1-6 DISCUSSED ACCESS TO FC
05/15/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1. EX. HOOD BLK. IRON - OK TO WRAP TOP 3/4 FT
2. CONSULT ENG./ARCH. FOR DIRECTION
ACCESS FOR F.D FIRST FLOOR