Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: SEWER - PRE CONSTRUCTION MTG

Date Description Inspector Results Comments
02/16/2007 SEWER - PRE CONSTRUCTION MTG Approved IVRS - Inspection :*
PETER W/LLOYD 471-8414

PAUL DOHERTY
RWS APPROVED PLAN
6" SDR REQUIRES TRACER WIRE
4" CLEANOUTS NOT TO EXCEED 100' TOTAL. INSTALL PER UPC.
1% FALL WILL REQUIRE VERIFICATION OF GRADE
CALL FOR DAILY PROGRESS INSPECTION.
CALL FOR INSP ON PRIVATE MANHOLE