Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM03151

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
OVERHEAD TO PIPES
1. NEED BUSHING FOR PVC 352.46
2. #6 AND SMALLER GROUND TO BE GREEN ENTIRE LENGTH
NEC 250.119
3. PROVIDE TORQUE LETTER -- NEC 110.3B
4. IDENTIFY DISCONNECTS -- NEC 110, INSTALL FUSES
DO NOT ENERGIZE EQUIPMENT BEFORE SAFE TO DO SO
LOCKOUT AS NEEDED