Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM03151
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* OVERHEAD TO PIPES 1. NEED BUSHING FOR PVC 352.46 2. #6 AND SMALLER GROUND TO BE GREEN ENTIRE LENGTH NEC 250.119 3. PROVIDE TORQUE LETTER -- NEC 110.3B 4. IDENTIFY DISCONNECTS -- NEC 110, INSTALL FUSES DO NOT ENERGIZE EQUIPMENT BEFORE SAFE TO DO SO LOCKOUT AS NEEDED |