Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/30/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE POWER TO SMOKE DAMPERS
11/30/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/28/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
ROOFTOP OK
11/20/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
AC-1-1 = CONDENSATE PIPING NOT COMPLETED ON ROOF
AC-2-2 = CONDENSATE PIPING NOT COMPLETE ON ROOF
AC-2-1 = CONDENSATE PIPING NOT COMPLETE ON ROOF
AC-1-1 = FIRE DAMPERS OK

GEF-1 & 2: PROVIDE HINGE KITS ON EXHAUST FANS PER PLANS

- PROVIDE UL LISTING ON COMMERICAL KITCHEN HOOD GREASE FILTERS
- 4-FIRE/SMOKE DAMPERS, 1-DUCT SMOKE DETECTOR TO BE TESTED
11/19/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*