Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM03151

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/28/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/25/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
INSTALL FLEX DUCTS EXACTLY AS PER DETAIL ON PLANS
BOTH ENDS
09/05/2007 MECHANICAL - ABOVE CEILING Partial Approval - OK TO SHEETROCK HONEYMOON SUITE.
- RELOCATE SMASHED FLEX DUCT WEST CORRIDOR FIRE DAMPER.
- FIRE DAMPER ACCESS DOORS OK
- DO NOT ALLOW FLEX DUCTS TO LAY ON CONDUIT
- FOLLOW ALL DETAILS ON PLANS.
08/17/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
GREASE DUCT ACCESS DOORS OK
OK TO SHEETROCK REMAINING RESTROOMS 2ND FLOOR
07/30/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO SHEETROCK BATHROOM LIDS 2ND FLOOR EAST CORRIDOR SOUTH SIDE
FIRE CAULK AROUND FIRE DAMPER ANGLE IRON
07/18/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE SCREWS IN ALL JOINTS OF EXHAUST DUCTS AND SCREW THE DUCT TO THE OUTLET ON THE FAN.
PROVIDE FRAMED OPENINGS FOR FIRE DAMPERS.
07/13/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- PROVIDE SCREWS IN EXHAUST DUCT JOINTS.
- PROVIDE SECONDARY DRAINS OR OVERFLOW SENSORS.
- INSTALL ACCESS CLEANOUT PER INSTALL INSTRUCTIONS.
- PROVIDE MIN. 26 GA. DUCT WHEN PASSING THROUGH A FIRE RATED ASSEMBLY.
- OK TO SHEETROCK ROOM 129.
07/11/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ACCESS @ 3:45 PM