Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T06CM03151

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2007 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
08/06/2007 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
TEST ON 1ST FLOOR WASTE OFFSET OK.
WRAP W/FOAM
ABOVE CEILING WATER INSTALLED PER CODE
HANGERS ON CW NOT PER PLAN SPECS
LARGE PIPING NOT BRAZED
COVER AT OWN RISK
07/18/2007 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/16/2007 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*