Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03151

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
NOTE: CONTRACTOR TO DEMO (REMOVE) TEMPORARY WIRING TO CONSTRUCTION TRAILER AND ENERGIZE HOT WATER TANK
12/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. CHECK ALL PANEL DIRECTORIES TO MAKE SURE THEY GO TO WHAT DIRECTORY SAYS ITS GOING TO - NEC 408.4
2. MULTIPLE CKT'S TO RECEPTACLES TO HAVE 2 POLE BREAKER - NEC 210.7B
3. MAKE SURE ALL PREVIOUS CORRECTIONS HAVE BEEN COMPLETED.
12/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
11/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT GROUNDS TO BE INCREASED WHERE PHASE CONDUCTORS ARE INCREASED - NEC 250.122B
2. IN LIGHTING J-BOX BY CONTACTORS - SELF TAP SCREWS NOT ALLOWED FOR GROUND BAR, CHECK WIRE NUT FILL
3. CHECK EXTERIOR E-LIGHTING/SOME NOT WORKING
11/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
PETER 471-8414

1. HOOD INTERLOCK WIRING NOT PER PLAN
2. NEED #2 CU GROUND TO IDF MAIN GROUND BUSS PER PLAN
3. ALL PANEL DIRECTORYS TO BE INSTALLED, MAKE SURE THEY ARE CORRECT
4. TEMPORARY WIRING TO BE DE-ENERGIZED AND REMOVED
5. CHECK DISH/DISP LOADS
11/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PARTIAL INSPECTION FIRST FLOOR
2) CHECK FOR EMERGENCY LIGHT OPERATION AND AIM
3) PANEL DIRECTORIES TO BE CORRECT
4) W.H. DISCONNECT TO HAVE PROPER FRONT WORKING CLEARANCE NEC 110.26
11/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
INSPECTION FOR 2ND LEVEL

1. PANEL DIRECTORYS TO BE CORRECT
2. ROOMS NOT NUMBERED PER PLAN?
3. PIGTAILS FOR WASHER/DRYER COMBOS IMPROPERLY WIRED - REMOVE NEUTRAL JUMPER

FOR RTU FEEDERS -
1. WIRE NUTS OVERFILLED
2. GROUND J-BOXES
3. STRAP EMT WITHIN 36" OF ENCLOSURE
4. TAP CONDUCTORS TO RTU'S TO BE NO MORE THAN 25'
11/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSPECTION FOR ROOF TOP: FLEX TO BE STRAPPED WITHIN 12" OF ENCLOSURES
2) DISCONNECT NOT GROUNDED A/C 2-2
3) IDENTIFY DATA PLATES
4) CONDUCTOR SIZES TO ROOF TOP EQUIPMENT NOT PER PLAN
5) PROVIDE LETTER FOR ANY CHANGES TO RTU'S SIZES