Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03151
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NOTE: CONTRACTOR TO DEMO (REMOVE) TEMPORARY WIRING TO CONSTRUCTION TRAILER AND ENERGIZE HOT WATER TANK |
|
12/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. CHECK ALL PANEL DIRECTORIES TO MAKE SURE THEY GO TO WHAT DIRECTORY SAYS ITS GOING TO - NEC 408.4 2. MULTIPLE CKT'S TO RECEPTACLES TO HAVE 2 POLE BREAKER - NEC 210.7B 3. MAKE SURE ALL PREVIOUS CORRECTIONS HAVE BEEN COMPLETED. |
|
12/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |
|
11/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT GROUNDS TO BE INCREASED WHERE PHASE CONDUCTORS ARE INCREASED - NEC 250.122B 2. IN LIGHTING J-BOX BY CONTACTORS - SELF TAP SCREWS NOT ALLOWED FOR GROUND BAR, CHECK WIRE NUT FILL 3. CHECK EXTERIOR E-LIGHTING/SOME NOT WORKING |
|
11/29/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION PETER 471-8414 1. HOOD INTERLOCK WIRING NOT PER PLAN 2. NEED #2 CU GROUND TO IDF MAIN GROUND BUSS PER PLAN 3. ALL PANEL DIRECTORYS TO BE INSTALLED, MAKE SURE THEY ARE CORRECT 4. TEMPORARY WIRING TO BE DE-ENERGIZED AND REMOVED 5. CHECK DISH/DISP LOADS |
|
11/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PARTIAL INSPECTION FIRST FLOOR 2) CHECK FOR EMERGENCY LIGHT OPERATION AND AIM 3) PANEL DIRECTORIES TO BE CORRECT 4) W.H. DISCONNECT TO HAVE PROPER FRONT WORKING CLEARANCE NEC 110.26 |
|
11/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION INSPECTION FOR 2ND LEVEL 1. PANEL DIRECTORYS TO BE CORRECT 2. ROOMS NOT NUMBERED PER PLAN? 3. PIGTAILS FOR WASHER/DRYER COMBOS IMPROPERLY WIRED - REMOVE NEUTRAL JUMPER FOR RTU FEEDERS - 1. WIRE NUTS OVERFILLED 2. GROUND J-BOXES 3. STRAP EMT WITHIN 36" OF ENCLOSURE 4. TAP CONDUCTORS TO RTU'S TO BE NO MORE THAN 25' |
|
11/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSPECTION FOR ROOF TOP: FLEX TO BE STRAPPED WITHIN 12" OF ENCLOSURES 2) DISCONNECT NOT GROUNDED A/C 2-2 3) IDENTIFY DATA PLATES 4) CONDUCTOR SIZES TO ROOF TOP EQUIPMENT NOT PER PLAN 5) PROVIDE LETTER FOR ANY CHANGES TO RTU'S SIZES |