Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM03151
Parcel: 11202003D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM03151
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2006 MARTIN BROWN FIRE REVIEW Approved
10/18/2006 ROBERT SHERRY WATER REVIEW Approved
10/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Second request. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2003.
2. The most of the condensate drain piping located in the second floor of the east wing is not shown, only the notes and leaders show up.
3. Second request. Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2003.
4. The transfer grille located on the wall between rooms 126 and 120 requires a fire damper. The duct is not fabricated of sheet metal and it is not continuous from an air-handling appliance and an air inlet or air outlet. Reference Section 607.5.2, exception 3, IMC 2003.
10/25/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please put the outdoor lighting code compliance calculations on the plans, as required by Section 8 of the Tucson Lighting Code. It appears that the following corrections are in order: 6 Fixtures S on Sheet E S01, not 5 (there is one on the SE corner of the property); 11 Fixtures P, not 8 (3 on Sheet E201, 8 on Sheet E202); and, a Fixture S1 (Sheet E201 Revision 1).
2. Reworked Service Load Calculations appear to total over 1300A, not 1189A, overloading the Service Entrance Switchgear and Service Entrance Conductors. Demand factor not accepted for Electric Ranges: there is no NEC Table 220.10, and Table 220.19 applies to household ranges, whereas these are grouped in a single kitchen. Plans Examiner counted 23 KVA of Kitchen Equipment, and another 23 KVA for the ranges, after applying the 65% demand factor for non-dwelling kitchen equipment. Demand factor not accepted for Dryers: NEC Table 220.18 applies to household dryers. Loads not in any other category were added to the mechanical with unity demand factor and appeared to total 203 KVA.
3. Reworked Panel 2D load calculations, which total 431A on Phase A and 425A on Phase B, overload the panel, feeder, and overcurrent protective device.
10/28/2006 LINHART PETERSEN POERS ASSOC. BUILDING-COMMERCIAL REVIEW Approved
10/31/2006 STEVE SHIELDS ZONING REVIEW Denied 10-31-06

Development Services Department
Zoning Review Section

Steve Shields
Lead Planner

Comments for T06CM03151:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.

4. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the building plan can be approved by Zoning. Two copies of the approved development plan, landscape and NPPO plans are to be submitted with the building plans packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the building plans packet processed together for site approval
10/31/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The wet-vented lavatory in Bath 220B exceeds the maximum trap arm length for a 1-1/2" trap arm. (Lavatories have a 1-1/4" tailpiece for which the maximum trap size is 1-1/2" per Section 1003.3, UPC 2003.)
2. Second request. Tucson Water will no longer allow water meters and backflow preventers to be manifolded to achieve additional capacity. Provide a revised site plan showing the correct water meter and reduced pressure backflow preventer assembly installation.
3. Provide shower control valves that comply with the requirements of Section 420.0, UPC 2003. (The division 15 specification section 15400, "Plumbing Fixtures and Equipment" is not in the project manual.) Note that a tempering valve located at a central water heater does not meet the requirements of Section 420.1, UPC 2003.
4. An approved appeal to the building official has not been included in drawing set. The use of Proset Systems' "Trap Guard" to provide trap seal protection in lieu of the accepted methods for trap seal protection will require an appeal to the Building Official. Reference Sections 301.2 and 1007.0, UPC 2003, as modified by the City of Tucson.
5. Provide upper terminal cleanouts on horizontal drainage pipes located in Bath 133 and Bath 232B. Reference Section 707.4, UPC 2003, as amended by the City of Tucson.
11/06/2006 GERRY KOZIOL WWM REVIEW Denied 1.Ronald McDonald House- Building #6 232FU @ SFR rate for Transient lodging & 125FU @ Commercial rate for common areas.
2. Needs wastewater 8th floor review of abandonment of portion of on-site public sewer M-142.
3. Needs wastewater 8th floor review of 20ft off-site private sewer easement for 6" private sewer for building #6.
4. Needs wastewater 8th floor review of manhole tap (740-6500) & manhole tap permit from 5th floor wastewater (740-6602)
5. Needs wastewater 8th floor credit evaluation if applicable
11/17/2006 JOSE ORTIZ ENGINEERING REVIEW Denied The building permit cannot be approved until the Development Plan (D06-0007) and Grading Plan (T06BU01321) have been approved. Upon approval of the Development Plan the Development Plan must be approved as a Site Plan with all required approval stamps for the Site Plan. Upon final Site Plan approval the Building Permit will be eligible for final approval.

If you have any questions, I can be reached at 791-5550 x1191 Jose.Ortiz@tucsonaz.gov
Jose E. Ortiz, PE
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1191 office
(520) 879-8010 fax
C:/ 0000 O. Street Address

Final Status

Task End Date Reviewer's Name Type of Review Description
12/05/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
12/05/2006 SUE REEVES REJECT SHELF Completed