Permit: T06CM03151

Parcel: 11202003D

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/07/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
08/13/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
08/10/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) ACCESS DOORS NOT BUILT PER INSTALL INSTRUCTIONS
2) DO NOT CUT FIRE WRAP AROUND UNISTRUT. WRPA UNISTRUT IF NEEDED
30 INSTALL DOORS EXACTLY AS PER INSTALL INSTRUCTIONS. NEXT TIME A REINSPECTION FEE WILL BE CHARGED
07/12/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK EXTERIOR SITE LIGHTING COVER AS NEEDED
STAY AT 18" DEPTH, 24" DEPTH IN VEHICLE TRAFFIC AREAS
03/02/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/01/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BRACE BACK OF TEMP SER, MAKE STURDIER
2. SEAL HOLE BOTTOM OF PANEL

RECALL
02/23/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK REMAINDER OF INTERIOR UNDER SLAB
OK SECONDARY RACEWAYS COVER
02/15/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
B2/LOBBY/LIVING AREA UNDER SLAB
02/14/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELLED
02/09/2007 ELECTRIC - UNDERGROUND Partial Approval OK UFER
OK TO COVER ELECTRICAL RACEWAYS UNDER SLAB FROM EAST EXTERIOR WALL TO B.2 (ELEVATOR)
02/06/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK TN/PHONE MAIN RACEWAYS
2) OK UNDERGROUND RACEWAY TO WEST PANELS
02/01/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
01/31/2007 ELECTRIC - UNDERGROUND Partial Approval OK PVC UNDER EAST STAIRWELL
01/30/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO COVER UNDER SLAB RACEWAYS FOR FEEDERS 2D, 1C, ELE, SHUNT TRIP
01/29/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO COVER RACEWAYS COLUMN B2-E & PHONE/TV STUB
01/16/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
UFER POURED BEFORE INSPECTION
SUPER FOR JOB STATES THAT JIM BURGE LOOKED AT IT.
01/12/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR