Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM03151
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
08/13/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
08/10/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) ACCESS DOORS NOT BUILT PER INSTALL INSTRUCTIONS 2) DO NOT CUT FIRE WRAP AROUND UNISTRUT. WRPA UNISTRUT IF NEEDED 30 INSTALL DOORS EXACTLY AS PER INSTALL INSTRUCTIONS. NEXT TIME A REINSPECTION FEE WILL BE CHARGED |
|
07/12/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK EXTERIOR SITE LIGHTING COVER AS NEEDED STAY AT 18" DEPTH, 24" DEPTH IN VEHICLE TRAFFIC AREAS |
|
03/02/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
03/01/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BRACE BACK OF TEMP SER, MAKE STURDIER 2. SEAL HOLE BOTTOM OF PANEL RECALL |
|
02/23/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK REMAINDER OF INTERIOR UNDER SLAB OK SECONDARY RACEWAYS COVER |
|
02/15/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* B2/LOBBY/LIVING AREA UNDER SLAB |
|
02/14/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
02/09/2007 | ELECTRIC - UNDERGROUND | Partial Approval | OK UFER OK TO COVER ELECTRICAL RACEWAYS UNDER SLAB FROM EAST EXTERIOR WALL TO B.2 (ELEVATOR) |
|
02/06/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK TN/PHONE MAIN RACEWAYS 2) OK UNDERGROUND RACEWAY TO WEST PANELS |
|
02/01/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
01/31/2007 | ELECTRIC - UNDERGROUND | Partial Approval | OK PVC UNDER EAST STAIRWELL | |
01/30/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER UNDER SLAB RACEWAYS FOR FEEDERS 2D, 1C, ELE, SHUNT TRIP |
|
01/29/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER RACEWAYS COLUMN B2-E & PHONE/TV STUB |
|
01/16/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* UFER POURED BEFORE INSPECTION SUPER FOR JOB STATES THAT JIM BURGE LOOKED AT IT. |
|
01/12/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |