Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM03151
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
02/21/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WEST SECTION BELOW SLAB PLUMBING INSTALLED PER REDLINES ON APPROVED PLAN W/TEST OK TO COVER SUBJECT TO PLAN REVISION |
|
02/20/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* NEED WATER TEST AND REDLINES ON PLAN FOR CHANGE |
|
02/06/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) OK TO COVER FROM "B.2" TO "E" SANITARY SEWER SCH 40 PVC 2) TOILET ROOM 129 & 133 TO TWO WAY 3) CLEANOUT OK TO COVER WATER TEST ONE RISER TO TEN FEET |
|
02/01/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* KITCHEN WASTE STUBBED TO OUTSIDE BLDG. OK WATER TEST ONE RISER TO TEN FEET OK |
|
01/31/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR NOT IN TRAILER UNABLE TO DETECT ANY CHANGE FROM LAST INSPECTION |
|
01/26/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. AT F.S 1 - REQUIRE 2X PIPE DIAMETER BETWEEN TRAP WEIR AND POINT OF VENT. 2. WATER SERVICE STUBBED INTO BLDG. OK 3. PVC DWV BETWEEN GRIDLINES "E" AND "H" OK TO COVER WATER TEST ONE RISER TO TEN FEET. 4. INTERCEPTOR NOT SET AT THIS TIME. |