Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address NEW:
3800 W STARR PASS BL
Apply Date:
06/06/2003
Applicant:
ADRIANNE WALKER
Description:
NEW:HOTEL PHASE VII
Contractors:
  • WEITZ COMPANY
  • WEITZ COMPANY L L C *C

Permit Reviews

Permit Number - T03CM02796
Permit Status: C of o
Permit Description: NEW:HOTEL PHASE VII
Start Date Submittal Complete Date Status  
04/13/2005 3RD PARTY REVIEW-REVISION/OTHER 04/15/2005 COMPLETED Review Details
06/06/2003 PLANS OK TO SUBMIT - 3RD PARTY 06/06/2003 COMPLETED Review Details
06/09/2003 3RD PARTY REVIEW-COMMERCIAL 07/03/2003 COMPLETED Review Details
07/06/2005 3RD PARTY REVIEW-REVISION/OTHER 08/05/2005 COMPLETED Review Details
07/14/2003 3RD PARTY REVIEW-REVISION/OTHER 08/06/2003 COMPLETED Review Details
07/21/2005 3RD PARTY REVIEW-REVISION/OTHER-2ND 08/05/2005 COMPLETED Review Details
07/25/2003 3RD PARTY REVIEW-REVISION/OTHER 07/31/2003 COMPLETED Review Details
08/08/2003 3RD PARTY REVIEW-REVISION/OTHER 08/26/2003 COMPLETED Review Details
08/25/2003 3RD PARTY REVIEW-REVISION/OTHER 09/08/2003 COMPLETED Review Details
09/03/2003 3RD PARTY REVIEW-REVISION/OTHER 09/16/2003 COMPLETED Review Details
09/09/2004 3RD PARTY REVIEW-REVISION/OTHER 09/21/2004 COMPLETED Review Details
09/30/2003 3RD PARTY REVIEW-COMMERCIAL 10/15/2003 COMPLETED Review Details
10/16/2003 3RD PARTY REVIEW-COMMERCIAL 12/24/2003 COMPLETED Review Details
12/13/2004 3RD PARTY REVIEW-REVISION/OTHER 01/10/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM02796
Permit Status: C of o
Permit Description: NEW:HOTEL PHASE VII
Total Outstanding Activity Conditions - 1
Date Name
06/06/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM02796
Permit Description: NEW:HOTEL PHASE VII
Total Completed Inspections - 37
Date Description Inspector Results Comments
06/23/2004 MECHANICAL - TEMP PWR FOR TEST CWILLIAM Approved
06/23/2004 PLUMBING - TEMP POWER FOR TEST TRINIVJR Approved
06/23/2004 BUILDING - TEMP POWER FOR TEST AMATHIES Approved
08/19/2004 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection :*/ 1) SOIL WATER TEST IS OK FOR GREASE INTERCEPTOR VENT AND OUTLET WASTE LINE TO P.O.C. 2) OK TO BACKFILL TRENCH 3) SOIL AIR PRESSURE TEST IS OK FOR BLDG G LEVEL 2, 3, 4 AND UP THEN ROOF ROOM # 4214, 4216, 5214, 5216, 6214, 6216 AS NOTED ON PLAN 4) 6" RWL WATER TEST IS OK FOR BLDG G LEVEL 1 AND 2 AS NOTED ON PLAN 5) MENS RESTROOM TRAP ARMS ARE OK FOR BLDG J BETWEEN JUNIOR AND GTLAND BALLROOMS 6) AIR PRESSURE TEST IS OK FOR HOT AND COLD WATER DISTRIBUTION FOR BLDG D AND E KNUCKLE ROOMS #4081, 4082, 4084, 5081, 5084, 6081, 6084, 7081, 7084, 8081, 8084
09/10/2004 ELECTRIC - TEMP POWER FOR TEST DSANTACR Approved IVRS - Inspection :*
09/13/2004 TEP CLEARANCE - AM JKOZUCH Approved ECO M3 ONLY
09/21/2004 BUILDING ABOVE CEILING TRINIVJR Approved 1)SOIL WATER TEST IS OK FOR BLDG. G1 RESTROOM 330 &333 AND SHAMPOO SINK AREA AS NOTED ON PLAN 2)SOIL WATER TEST IS OK FOR VENTS IN BLDG H AIR HANDLE AREA 3)OVERHEAD WATER DISTRIBUTION IS OK FOR MECH RM LEVEL 7 D-WEST RM M901 COMPLETE.4)WATER DISTRIBUTIO FOR LEVEL G P-1 RM 243, 245 IS OK AS NOTED ON PLAN 5)FLOOR SINK IN BLDG. G LEVEL 2 WATER TEST IS OK
10/13/2004 PLUMBING - YARD WTR LINE/TEST RRICH Approved IVRS - Inspection :*/LEVEL 2 BUILDING H, LEVEL 3 BUILDING H, LEVEL 4 BUILDING H, INCLUDING MAINS FROM G&H KNUCKLE ON LEVEL 4 TO 4" COLD AND 3" HOT TO BE CONTINUED DOWN AT EAST END 110 PSI AIR TEST OK. SHADE PAVILLION AREA, TEST ON AREA DRAINS WATER TEST OK LEVEL 4 BUILDING E CLOSET FLANGES OK
11/03/2004 PLUMBING - INTERMEDIATE TRINIVJR Approved IVRS - Inspection :*/1)HAD MEETINGS WITH PLBG. CONTRACTOR FOR TEMP C 0F O. REQUREMENTS
11/18/2004 FIRE - FINAL LTHOMAS Approved O.K for Temporary C of O, for Marriott staff only, in the following areas:
1. Wings A, B & C all floors through Level 4.
2. Corridors and Restrooms Parking Level 1, Area D.
3. Employee Locker Rooms and Cafeteria Wing G.(No food preparation requiring Type 1 Exhaust Hood.)
4. Staff offices Wing H.
5. Ballrooms Wings I and J.
6. Parking Level P-3.
7. Corridors Parking Level P-1 from parking to Wings A, B, & C.
Temporary C of O is granted with the understanding that the fire protection systems serving the approved areas will be in service at all times, and that no portion of the facility will be open to public occupancy until all areas are completed.
12/02/2004 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
12/14/2004 ELECTRIC - ABOVE CEILING RMAJUTA Approved IVRS - Inspection :*/1)LEVEL 1 LOBBY BETWEEN BLD G & H OK. 2)LEVEL P-1 ELEVATOR LOBBY OK 3)LEVEL P-1 BLD H 6 MEETING ROOMS OK. CONTRACTOR TO CLOSE OFF OPEN J-BOXES. ALL ABOVE OK TO COVER
12/14/2004 FIRE - ALARM FINAL LTHOMAS Approved
12/20/2004 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*/KITCHEN W/TYPE I HOODS MUST BE COMPLETELY FINISHED AND FIRE CONTROL SYSTEM APPROVED BY T.F.D. PRIOR TO TURNING OVER FOR OPERATION. ALL KITCHEN AREAS. RM. CHILD ACTIVITY CONNOT ELIMINATE ACCESS PANELS TO REACH SMOKE FIRE DAMPER ACTIVATORS
12/20/2004 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
12/27/2004 PLUMBING - GAS PRESSURE TEST TRINIVJR Approved IVRS - Inspection :*/1)GAS PRESSURE TEST IS OK 2)THIS INSPECTIN IS FOR GAS LINES FOR PATIO HTRS ONLY.
12/28/2004 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*/CASUAL KITCHEN OK. OK TO USE WHEN RELEASED BY TFD
12/29/2004 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :*
1) CASUAL KITCHEN P-1C OK TO OCCUPY
2) FLOOR EP-1
3) ELECTRIC ROOM LEVEL 2 WING D AND E
4) MISSING FIXTURES IN HALLWAY LEVEL P-1 #2)
5) STAR BUCKS COFFEE SHOP INCLUDING PANEL AND FEEDER OK TO OCCUPY
6) ROOMS LEVEL 1-E OK
7) ROOMS LEVEL 2-E OK
8) ROOMS LEVEL 3-E OK
9) ROOMS LEVEL 3-D OK
10) ROOMS LEVEL L 4 E OK
11) ROOMS LEVEL 4-D OK
12) ROOMS LEVEL 5-D OK
13) ROOMS LEVEL 5-E OK
14) ROOMS LEVEL 6-D OK
15) BLDG P-1 I-NOT COMPLETE
16) BLDG P-1 H-NOT COMPLETE
17) ALL DBL SUITE FLOORS 5 AND 6, ADDED ON FANS NOT FINISHED
12/30/2004 BUILDING - PROGRESS LHANLY Approved IVRS - Inspection :* PROGRESS ON SHAFT WALLS IN STAIR H OK
12/30/2004 BUILDING - FINAL LHANLY Approved IVRS - Inspection :* TO COMPLETE A-E FOR PUBLIC C OF O
1) FINISH PAVILLION STAIRS, RAMPS, HANDRAILS. 2) FINISH ENTRY FLAT WORK AND LIGHTING 3) COMPLETE ADA REQUIREMENTS A) LAVATORIES@ 34 1/2" OR LESS HAVE BEEN APPROVED PER THE DIMENSIONAL TOLERANCE PROVISION IN THE ADAAE GUIDELINES B) OTHER DISCREPANCIES MUST BE ADDRESSED BY REPAIR OR APPEAL THROUGH BUILDING OFFICIAL. THIS INCLUDES AREA AT REFUGE REQUIREMENTS.
12/30/2004 FRAMING LHANLY Approved IVRS - Inspection :*
12/31/2004 PLUMBING - FINAL TRINIVJR Approved IVRS - Inspection :* 1) WOMENS RESTROOM FOR POOL BAR IS OK 2) LOBBY BAR FINAL IS OK 3) NOTE: MENS POOL BAR RESTROOM THERE IS ONE WATER CLOSET THAT DOES NOT MEET MIN SIDE WALL CLEARANCE
01/24/2005 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
01/24/2005 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
01/24/2005 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
05/24/2005 OUTDOOR LIGHTING FINAL RMAJUTA Approved
06/30/2005 FIRE - KITCHEN EXH HOOD FINAL LTHOMAS Approved
06/30/2005 FIRE SPKLR - FINAL LTHOMAS Approved
06/30/2005 RIGHT OF WAY - FINAL LLOPEZ Approved
07/05/2005 ENGINEERING - FINAL DROBERTS Approved C OF O APPROVED
08/01/2005 SIGN - FINAL DCAPPLE Approved
08/05/2005 PERMIT FINALED JMORALES Approved
08/05/2005 ELECTRIC - PROGRESS RMAJUTA Approved
08/05/2005 ELECTRIC - CONSTRUCTION POWER RMAJUTA Approved
08/05/2005 PLUMBING - SEWER HCS CONNECT TRINIVJR Approved
08/05/2005 PLUMBING - ROOF DRAINS TRINIVJR Approved
08/05/2005 PLUMBING - ABOVE CEILING TRINIVJR Approved