Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2005 | ELECTRIC - ABOVE CEILING | Approved | ||
| 12/14/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/1)LEVEL 1 LOBBY BETWEEN BLD G & H OK. 2)LEVEL P-1 ELEVATOR LOBBY OK 3)LEVEL P-1 BLD H 6 MEETING ROOMS OK. CONTRACTOR TO CLOSE OFF OPEN J-BOXES. ALL ABOVE OK TO COVER | |
| 12/10/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/07/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) G-P2 AREA GRID CEILING 2) MC CABLE NOT TO BE TIED TO EMT CONDUIT FOR SUPPORT 3) DO NOT USE GRID WIRES THAT ARE INTENDED FOR GRID SUPPORT TO SUPPORT MC, YOU MUST USE YOUR OWN GRID WIRES. TIE OFF AT BOTH ENDS 4) SUPPORT MC PER NEC. WITHIN 12" OF TERMINATION AND AT 6' INTERVALS. THE EXCEPTION TO SUPPORT IS MAX 6' LENGTHS USED AS FIXTURE WHIPS |
|
| 11/26/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* MAIN EXTERIOR SOFFIT & LOBBY AREA OK TO COVER CEILING. J-BOX N.EAST CORNER NEEDS TO BE MADE UP & COVER INSTALLED. MAIN LIGHT MC FEEDER IN 4.15" ALL TREADS DROPPED DOWN FOR SUPPORT. (MAIN LOBBY) | |
| 11/16/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/OK NORTH CORRIDOR AREAS NORTH & SOUTH OF BLD "G" P1 LEVEL, EXCEPT KITCHEN, COMPLETE EQUIP HOOK-UP. PLEASE LEAVE DETAILED MSG OF EXACT AREA & TYPE OF INSP NO MSG LEFT FOR THIS INSP | |
| 11/15/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/LOCKER ROOMS BLD D P1 | |
| 11/10/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) ABOVE CEILING IN CORRIDOR G TO F OK TO COVER | |
| 11/05/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/03/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) OK OFFICES SOUTH OF LOADING DOCK, BACK OF HOUSE OFFICES | |
| 10/20/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/OK ABOVE CEILING JR BALLROOM | |
| 10/15/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/1S)OK SERVICE CORRIDORS NORTH OF BOTH BALLROOMS 2)JR BALLROOM NEEDS MC FIXTURE. CABLES TO BE SUPPORTED WITHIN 12" OF TERMINATION AND AT 6' INTERVALS. ONLY LENGTHS LONGER THAN 6' |