Permit: T03CM02796

Parcel: 11628001E

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
09/10/2004 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
07/07/2004 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
07/01/2004 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
06/28/2004 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*/ BOND WIRE IN X-FORMER NOT CHANGED OUT YET. OK ROOMS AND CORRIDOR LEVEL 3 'E' WING, VERIFY HOME RUN # OF CONDUCTORS IN HOME RUN J-BOX.
06/25/2004 ELECTRIC - TEMP POWER FOR TEST Partial Approval M-4 OK FOR TEMP POWER.
06/24/2004 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*/ OK M-4 LEVELS P-2, P-1, L1, L2, L3, L4, L5. LEVELS P-2 P-1. LEVEL L-1 - 1/0 GROUND TO COPPER ON 112.5TRANS LOOSE NEWT ON BUS DUCT SW. THIS INSP APPROVES ALL LEVELS FOR ABC ON SWITCH GEAR M-4 TO BE ENERGIZED FOR TESTING.
06/23/2004 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*/ OK TO CLEAR POWER M1 - SES4, AND M2 - SES3, SUBJECT TO BOND./ RISER D LEVELS P1, L1, L2, L3, L4, L5, L6 OK