Permit: T03CM02796

Parcel: 11628001E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/05/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/18/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* HOOD NOT PROPER LENGTH FOR COOKING LINE. 1) DEEP FAT FRYER STRAINER. IS A GREASE FLARE UP FIRE POSSIBLE?
01/24/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* STAIRWAY 18 OK. 2HR CHASE CARRING OVER TO EXH. FAN LOCATION
01/21/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
01/20/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* 1) POOL SPA HTR.ROOM PROGRESSING. TRANSFER AIR DUCTS DUCTED OR ELIMINATED. COMBUSTION AIR OPENINGS 2) AHU-6 COMPLETE CONDEN.DRAIN. 3) CHILLED WATER ICE MACH. INSULATION ON CH LINES?? G & H LEVELS 2 & 3 HOTEL RM'S MINUS STAIRWELL. OK MECH
01/06/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*1) SPA POOK HT. RM. WHERE IS UPPER & LOWER COMB. VENT OPENINGS ??? LOWE 12" & UPPER 12" OF SPACE. 2) TRANSFER AIR GRILLS THRU POOL HTR. SPACE NOT ISOLATED FROM STORAGE AREA. CONSULT ENGINEER FOR DIRECTION
12/20/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/KITCHEN W/TYPE I HOODS MUST BE COMPLETELY FINISHED AND FIRE CONTROL SYSTEM APPROVED BY T.F.D. PRIOR TO TURNING OVER FOR OPERATION. ALL KITCHEN AREAS. RM. CHILD ACTIVITY CONNOT ELIMINATE ACCESS PANELS TO REACH SMOKE FIRE DAMPER ACTIVATORS
08/13/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*