Permit Details

Status:
Needs Resubmittal
Type:
Commercial Building
Apply Date:
08/29/2023
Applicant:
Bobby Hammond
Description:
The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.

Permit Reviews

Permit Number - TC-COM-0823-02097
Permit Status: Needs resubmittal
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Start Date Submittal Complete Date Status  
04/19/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.2 04/23/2024 APPROVED Review Details
07/28/2025 COMMERCIAL REVIEW - FULL v.3 07/30/2025 APPROVED Review Details
07/30/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 07/31/2025 REQUIRES RESUBMIT Review Details
06/24/2025 COMMERCIAL REVIEW - FULL v.2 07/02/2025 REQUIRES RESUBMIT Review Details
08/30/2023 COMMERCIAL REVIEW - FULL v.1 10/09/2023 REQUIRES RESUBMIT Review Details
05/16/2025 COMMERCIAL REVIEW - FULL v.1 06/18/2025 REQUIRES RESUBMIT Review Details
08/05/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.2 08/12/2025 APPROVED Review Details
10/29/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 11/03/2025 APPROVED Review Details
09/18/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 09/19/2024 APPROVED Review Details
02/15/2024 RESTAMP - COMMERCIAL v.1 02/16/2024 APPROVED Review Details
04/10/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 04/15/2024 REQUIRES RESUBMIT Review Details
11/05/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 11/06/2024 APPROVED Review Details
01/31/2024 COMMERCIAL REVIEW - FULL v.2 02/15/2024 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0823-02097
Permit Status: Needs resubmittal
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Total Outstanding Activity Conditions - 18
Date Name
04/23/2024 AIR BALANCING REPORT IS REQUIRED.
04/23/2024 SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED.
04/23/2024 COUNTY HEALTH INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED.
04/23/2024 State Approved Elevator Designs must be submitted prior to final.
04/23/2024 ELEVATOR INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED.
04/23/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
04/23/2024 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
04/23/2024 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
04/23/2024 Masonry Inspection Report submittal review is required.
04/23/2024 Post-Installed Anchor Inspection Report is required.
04/23/2024 SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED.
04/23/2024 SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED.
04/23/2024 STATE FIRE MARSHAL INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION
04/23/2024 SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED.
04/23/2024 SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED.
04/23/2024 SPECIAL INSPECTION FOR WELD REINF STEEL IS REQUIRED.
04/23/2024 SPECIAL INSPECTION FOR WELDING IS REQUIRED.
09/18/2024 Dust Control/Air Quality Permit

Conditions

Permit Number - TC-COM-0823-02097
Permit Status: Needs resubmittal
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Date Description Comments
04/23/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
04/23/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
04/23/2024 SPECIAL INSPECTION FOR SMOKE CONTROL SYSTEM IS REQUIRED.
04/23/2024 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.

Outstanding Inspections

Permit Status: Needs Resubmittal
Permit Number: TC-COM-0823-02097
Permite Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Total Outstanding Inspections - 26
Last Inspection Date Description Inspector Results Comments
06/20/2024 COT - HCEL - Grounding/Bonding N/A Partial Pass 6/20/24: partial for UFER at southeast corner of building.
11/13/2024 COT - HCBU - Preslab N/A Partial Pass 6/11/24: spread footings at Area B from GL L-H/1-5 passed ok to proceed. Stairway at Area B GL L-K/5-4 passed ok to proceed, elevator pit footing per plan ok to proceed
6/12/24: Spread footings for Area A complete ok to proceed.
6/20/24: Rebar inspection for East Side Exterior perimeter grade beam from Gridline E.2-L/5, J.1/1-5, J.1-E/1.1, stem wall at south east stairwell ok to pour, stem wall for elevator passed ok to proceed.
6/28/24: North half of Exterior Grade Beams. Gridline B-F/1-5
7/1/24: concrete wall reinforcement per plan at first level south east corner stairwell ok to proceed.
9/6/24: Reinforcement for slab on grade per plans for Area A and Area B ok to proceed.

10/17/2024 reinforcement for 2nd floor approved. Okay for concrete placement.
11/13/24: reinforcement for 3rd floor deck approved ok for concrete placement
12/02/2024 COT - HCPL - Sewer N/A Partial Pass 6/18/24: partial for sewer from manhole on north west corner of project to 1st clean out. Ok to proceed. Air pressure test will be completed once run is complete.
6/26/24: partial for sewer from 1st clean out to future tie in at grease interceptor.
6/27/24: Air test at 5PSI for sewer pipe from manhole on northwest corner of project to future tie in at grease interceptor. Ok to backfill progress areas. Shading required
12/2/24: partial pass for Inspection of grease interceptor & SS piping to and from interceptor.
02/06/2025 COT - HCME - Venting N/A Partial Pass Level #1, Area B in wall vent lines.
03/14/2025 COT - HCPL - Yard Water Line N/A Partial Pass 3/14/25: Inspect (2) 3" domestic water lines from city tap to building. Pressure test passed. Ok to proceed with backfill.
04/01/2025 COT - HCBU - Stem Wall/Retaining Wall N/A Partial Pass
04/04/2025 COT - HCPL - Plumbing Roof Drains N/A Canceled 4/4/2025 canceled per contractor.
04/17/2025 COT - HCEL - Electrical Underground N/A Partial Pass 7/10/24: partial electrical underground for (4) 4" conduit for low voltage from midpoint of building to northwest elevator shaft , branch circuits conduits per plan mid span of building GL I-F.2/3. Ok to backfill progress areas.
7/22/24: electrical underground at emergency elec room and main elec room on south east corner partial pass. Stub-outs,
7/23/24: ok to backfill and compact electrical underground at emergency elec room per plans, pending UFER (will leave exposed).
8/6/24: Canceled by Mike
8/7/24: (8)4" conduit from building to future transformer for secondaries.
4/17/25: electrical underground for emergency generator per plan ok to backfill.
04/24/2025 COT - HCBU - Building Progress N/A Partial Pass Level #2 exterior sheathing. Ok to water proof and water surface areas.
12/27/2024 COT - HCBU - Interior Shear Bracing N/A Re-inspection required 12/27/2024 : Rebar Inspection for Concrete Roof Access Walls not ready.
06/30/2025 COT - HCME - Mechanical Progress N/A Partial Pass 12/16/24: return air hard duct in rooms 1AM008,1AM009,1AM010,1AM011,1AM012,1AM013,1AM014, 1AM003,1RH003,1DI018. Ok to proceed with insulation in progress areas.
1/8/25: 2nd floor 48"x20" hard duct from rooms 2RH003,2RH005,2RH007,2RH009,2RH011,2RH013,2RH015,2RH017,2RH019,2RH021,2RH023,2RH025,2RH027,2RH029, 2RH035, 2RH037,2RH039,2RH041,2RH043,2RH045,2RH047. First floor perimeter return air hard duct passed ok to insulate.
04/09/2025 COT - HCEL - Electrical Progress N/A Partial Pass Level #2, East side patient rooms; in wall electric. OK to insulate and cover walls.
12/27/2024 COT - HCBU - Firewall/Fire Barrier/Firestop N/A Re-inspection required Call in when all of 1st Floor Above Ceiling @ Priority Walls caulking is in place. 12/27/2024
04/24/2025 COT - HCME - Mechanical Intermediate N/A Partial Pass Hood grease duct system; Level 1 - Level 3 (smoke tested), stainless steel duct system for dish washer, Levels 1 - 3. Ok to double wrap grease duct system from level #1 to level #3.
04/04/2025 COT - HCEL - Electrical Intermediate N/A Partial Pass Electrical in wall. 2nd floor room numbers 31, 29, 27, 25, 23, 21, 19, 17, 15, 13. Okay to proceed progress areas. 4/4/2025
08/01/2025 COT - HCPL - Medical Gas/Final N/A Partial Pass 8-1-25: medical gas on 3rd floor verified under test -pending labelling .Okay to continue with construction at progress areas.
04/04/2025 COT - HCPL - Plumbing Intermediate N/A Partial Pass 2nd floor patient rooms #26, #28, #30, #32, #34. Domestic water stubbed out to main corridor and DWV on test. #36 ,#38, #40 only DWV, okay to proceed progress areas. 4/4/2025
07/29/2025 COT - HCPL - Plumbing Above Ceiling N/A Partial Pass 7-29-25: 3rd floor Area B above ceiling DWV along west end verified per plans and under test. Okay to continue with construction at progress areas.
12/27/2024 COT - HCBU - Framing N/A Partial Pass partial pass. 1st floor interior framing approved. Pending elevators areas, store front framing and exterior framing at all of west end. Okay to proceed progress areas. 12/27/2024
08/06/2025 COT - HCEL - Electrical Above Ceiling N/A Partial Pass Level #3, East side of floor; room units and restrooms, mechanical, plumbing, electric and framing. Ok to cover walls in progress areas.
11/03/2025 COT - HCME - Mechanical Above Ceiling N/A Partial Pass Level #3, center portion of corridor, mechanical above ceiling. Ok to.drop.ceiling,tiles in,progress areas.
COT - HCME - Mechanical Final N/A Scheduled
12/04/2025 COT - HCBU - Building Final N/A Partial Pass 12/3/25: Level 1 TCO approved for the 1st floor only. The building must not be occupied at any time under this TCO. A Level 1 TCO authorizes stocking and furniture placement only.
Approval from Fire, Engineering, and Right-of-Way is required before submitting a Level 1 TCO request. Without their approval, the TCO will not be issued.

12/3/25: general walk through of the first floor (not ready for building final inspection)
COT - HCPL - Gas Final N/A Scheduled
COT - HCPL - Plumbing Final N/A Scheduled
COT - HCEL - Electrical Final N/A Scheduled

Completed Inspections

Permit Status: Needs Resubmittal
Permit Number: TC-COM-0823-02097
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Total Completed Inspections - 6
Date Description Inspector Results Comments
08/29/2024 COT - HCPL - Plumbing Progress Passed 7/24/24: plumbing underground Area A per plans ok to backfill. partial pass on underground plumbing at Area B north of elevator shaft.
8/9/24: plumbing underground Area B (grease) per plans ok to proceed.

Elevator sump pump on test. Area B sanitary waste per plan and under pressure. X2 4” vents for grease interceptor on test. Okay to backfill progress areas. Shading required. 8/23/2024
8/27/24: (2) 3" for domestic water under pressure at 100psi, 8" storm drain under pressure ok to proceed
8/29/24: tie in at sewer passed ok to proceed.
02/26/2025 COT - HCPL - Medical Gas/Test Passed Med gas lines under pressure test.
03/18/2025 BULD - Electrical Clearance Passed PASS

3-18-25, MSA main electric room on 1st. Floor is okay to be energized. ECO clearance issued to TEP.
06/26/2025 COT - HCEL - Outdoor Lighting Passed
09/23/2025 COT - BULD - SWG Clearance Passed 9-23-25: gas pressure test for remaining areas of site to include, mechanical room, kitchen and rooftop verified under test. Okay for SWG to install meter-clearance issued.
09/23/2025 COT - HCPL - Gas Pressure Test Passed 9-23-25: gas pressure test for remaining areas of site to include, mechanical room, kitchen and rooftop verified under test. Okay for SWG to install meter.

Scheduled Inspections

Scheduled Inspections - TC-COM-0823-02097
Status: Needs Resubmittal
Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Scheduled Date Description Entered By Entered Date
12/05/2025 COT - HCPL - Gas Final Scheduled
12/05/2025 COT - HCPL - Plumbing Final Scheduled
12/05/2025 COT - HCEL - Electrical Final Scheduled
12/05/2025 COT - HCME - Mechanical Final Scheduled
For information about today’s scheduled inspections please refer to the PDSD Daily Inspections Dashboards (Desktop) PDSD Daily Inspections Dashboards (Mobile) .

Documents

File Name Document Type  
0336-9305_SEALED CALCS_NOPBIS REHAB_V1.PDF DOCUMENTS VIEW
TUCSON REHAB CARPORT CANOPY___V2.PDF DOCUMENTS VIEW
2025-05-06_TUCSON_PR07 COMBINED_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
051200.002-00 - PD - STRUCTURAL STEEL STAIR CALCULATIONS PRODUCT DATA_RESPONSE_FIO_V1.PDF DOCUMENTS VIEW
055113.001-02 - SD - METAL STAIRS SHOP DRAWINGS_(RESPONSE)-EAN_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
TUCSON REHAB SPECIAL INSPECTIONS CERTIFICATE-2024-04-19_V1.PDF DOCUMENTS VIEW
WILLDAN_APPROVED_COMCHECK_V1.PDF DOCUMENTS VIEW
WILLDAN_APPROVED_IFC PROJMANVOL1OF2_V1.PDF DOCUMENTS VIEW
WILLDAN_APPROVED_IFC PROJMANVOL2OF2_V1.PDF DOCUMENTS VIEW
WILLDAN_APPROVED_PROJECT MANUAL_V1.PDF DOCUMENTS VIEW
WILLDAN_APPROVED_STRUCT CALCS_V1.PDF DOCUMENTS VIEW
CONS-2024-01-18_TUCSON_ADDENDUM 4_COMPOSITE SET_V2.PDF DOCUMENTS VIEW
CONS-2024-01-18_TUCSON_ADDENDUM 4_COMPOSITE SET_V2.PDF DOCUMENTS VIEW
CONS-2024-01-18_TUCSON_ADDENDUM 4_COMPOSITE SET_V2.PDF DOCUMENTS VIEW