Permit: TC-COM-0823-02097
Permit Details
Status:
Needs Resubmittal
Type:
Commercial Building
Address:
820 E TUCSON MARKETPLACE BL
Address NEW:
820 E TUCSON MARKETPLACE BL
Apply Date:
08/29/2023
Applicant:
Bobby Hammond
Description:
The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Permit Reviews
Permit Number - TC-COM-0823-02097
Permit Status: Needs resubmittal
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/19/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 04/23/2024 | APPROVED |
| 07/28/2025 | COMMERCIAL REVIEW - FULL v.3 | 07/30/2025 | APPROVED |
| 07/30/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 07/31/2025 | REQUIRES RESUBMIT |
| 06/24/2025 | COMMERCIAL REVIEW - FULL v.2 | 07/02/2025 | REQUIRES RESUBMIT |
| 08/30/2023 | COMMERCIAL REVIEW - FULL v.1 | 10/09/2023 | REQUIRES RESUBMIT |
| 05/16/2025 | COMMERCIAL REVIEW - FULL v.1 | 06/18/2025 | REQUIRES RESUBMIT |
| 08/05/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 08/12/2025 | APPROVED |
| 10/29/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 11/03/2025 | APPROVED |
| 09/18/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 09/19/2024 | APPROVED |
| 02/15/2024 | RESTAMP - COMMERCIAL v.1 | 02/16/2024 | APPROVED |
| 04/10/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 04/15/2024 | REQUIRES RESUBMIT |
| 11/05/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 11/06/2024 | APPROVED |
| 01/31/2024 | COMMERCIAL REVIEW - FULL v.2 | 02/15/2024 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0823-02097
Permit Status: Needs resubmittal
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Total Outstanding Activity Conditions - 18
| Date | Name |
|---|---|
| 04/23/2024 | AIR BALANCING REPORT IS REQUIRED. |
| 04/23/2024 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. |
| 04/23/2024 | COUNTY HEALTH INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED. |
| 04/23/2024 | State Approved Elevator Designs must be submitted prior to final. |
| 04/23/2024 | ELEVATOR INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED. |
| 04/23/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
| 04/23/2024 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. |
| 04/23/2024 | SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED. |
| 04/23/2024 | Masonry Inspection Report submittal review is required. |
| 04/23/2024 | Post-Installed Anchor Inspection Report is required. |
| 04/23/2024 | SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED. |
| 04/23/2024 | SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED. |
| 04/23/2024 | STATE FIRE MARSHAL INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION |
| 04/23/2024 | SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED. |
| 04/23/2024 | SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED. |
| 04/23/2024 | SPECIAL INSPECTION FOR WELD REINF STEEL IS REQUIRED. |
| 04/23/2024 | SPECIAL INSPECTION FOR WELDING IS REQUIRED. |
| 09/18/2024 | Dust Control/Air Quality Permit |
Conditions
Permit Number - TC-COM-0823-02097
Permit Status: Needs resubmittal
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
| Date | Description | Comments |
|---|---|---|
| 04/23/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 04/23/2024 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
| 04/23/2024 | SPECIAL INSPECTION FOR SMOKE CONTROL SYSTEM IS REQUIRED. | |
| 04/23/2024 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. |
Outstanding Inspections
Permit Status: Needs Resubmittal
Permit Number: TC-COM-0823-02097
Permite Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Total Outstanding Inspections - 26
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2024 | COT - HCEL - Grounding/Bonding | N/A | Partial Pass | 6/20/24: partial for UFER at southeast corner of building. |
| 11/13/2024 | COT - HCBU - Preslab | N/A | Partial Pass | 6/11/24: spread footings at Area B from GL L-H/1-5 passed ok to proceed. Stairway at Area B GL L-K/5-4 passed ok to proceed, elevator pit footing per plan ok to proceed 6/12/24: Spread footings for Area A complete ok to proceed. 6/20/24: Rebar inspection for East Side Exterior perimeter grade beam from Gridline E.2-L/5, J.1/1-5, J.1-E/1.1, stem wall at south east stairwell ok to pour, stem wall for elevator passed ok to proceed. 6/28/24: North half of Exterior Grade Beams. Gridline B-F/1-5 7/1/24: concrete wall reinforcement per plan at first level south east corner stairwell ok to proceed. 9/6/24: Reinforcement for slab on grade per plans for Area A and Area B ok to proceed. 10/17/2024 reinforcement for 2nd floor approved. Okay for concrete placement. 11/13/24: reinforcement for 3rd floor deck approved ok for concrete placement |
| 12/02/2024 | COT - HCPL - Sewer | N/A | Partial Pass | 6/18/24: partial for sewer from manhole on north west corner of project to 1st clean out. Ok to proceed. Air pressure test will be completed once run is complete. 6/26/24: partial for sewer from 1st clean out to future tie in at grease interceptor. 6/27/24: Air test at 5PSI for sewer pipe from manhole on northwest corner of project to future tie in at grease interceptor. Ok to backfill progress areas. Shading required 12/2/24: partial pass for Inspection of grease interceptor & SS piping to and from interceptor. |
| 02/06/2025 | COT - HCME - Venting | N/A | Partial Pass | Level #1, Area B in wall vent lines. |
| 03/14/2025 | COT - HCPL - Yard Water Line | N/A | Partial Pass | 3/14/25: Inspect (2) 3" domestic water lines from city tap to building. Pressure test passed. Ok to proceed with backfill. |
| 04/01/2025 | COT - HCBU - Stem Wall/Retaining Wall | N/A | Partial Pass | |
| 04/04/2025 | COT - HCPL - Plumbing Roof Drains | N/A | Canceled | 4/4/2025 canceled per contractor. |
| 04/17/2025 | COT - HCEL - Electrical Underground | N/A | Partial Pass | 7/10/24: partial electrical underground for (4) 4" conduit for low voltage from midpoint of building to northwest elevator shaft , branch circuits conduits per plan mid span of building GL I-F.2/3. Ok to backfill progress areas. 7/22/24: electrical underground at emergency elec room and main elec room on south east corner partial pass. Stub-outs, 7/23/24: ok to backfill and compact electrical underground at emergency elec room per plans, pending UFER (will leave exposed). 8/6/24: Canceled by Mike 8/7/24: (8)4" conduit from building to future transformer for secondaries. 4/17/25: electrical underground for emergency generator per plan ok to backfill. |
| 04/24/2025 | COT - HCBU - Building Progress | N/A | Partial Pass | Level #2 exterior sheathing. Ok to water proof and water surface areas. |
| 12/27/2024 | COT - HCBU - Interior Shear Bracing | N/A | Re-inspection required | 12/27/2024 : Rebar Inspection for Concrete Roof Access Walls not ready. |
| 06/30/2025 | COT - HCME - Mechanical Progress | N/A | Partial Pass | 12/16/24: return air hard duct in rooms 1AM008,1AM009,1AM010,1AM011,1AM012,1AM013,1AM014, 1AM003,1RH003,1DI018. Ok to proceed with insulation in progress areas. 1/8/25: 2nd floor 48"x20" hard duct from rooms 2RH003,2RH005,2RH007,2RH009,2RH011,2RH013,2RH015,2RH017,2RH019,2RH021,2RH023,2RH025,2RH027,2RH029, 2RH035, 2RH037,2RH039,2RH041,2RH043,2RH045,2RH047. First floor perimeter return air hard duct passed ok to insulate. |
| 04/09/2025 | COT - HCEL - Electrical Progress | N/A | Partial Pass | Level #2, East side patient rooms; in wall electric. OK to insulate and cover walls. |
| 12/27/2024 | COT - HCBU - Firewall/Fire Barrier/Firestop | N/A | Re-inspection required | Call in when all of 1st Floor Above Ceiling @ Priority Walls caulking is in place. 12/27/2024 |
| 04/24/2025 | COT - HCME - Mechanical Intermediate | N/A | Partial Pass | Hood grease duct system; Level 1 - Level 3 (smoke tested), stainless steel duct system for dish washer, Levels 1 - 3. Ok to double wrap grease duct system from level #1 to level #3. |
| 04/04/2025 | COT - HCEL - Electrical Intermediate | N/A | Partial Pass | Electrical in wall. 2nd floor room numbers 31, 29, 27, 25, 23, 21, 19, 17, 15, 13. Okay to proceed progress areas. 4/4/2025 |
| 08/01/2025 | COT - HCPL - Medical Gas/Final | N/A | Partial Pass | 8-1-25: medical gas on 3rd floor verified under test -pending labelling .Okay to continue with construction at progress areas. |
| 04/04/2025 | COT - HCPL - Plumbing Intermediate | N/A | Partial Pass | 2nd floor patient rooms #26, #28, #30, #32, #34. Domestic water stubbed out to main corridor and DWV on test. #36 ,#38, #40 only DWV, okay to proceed progress areas. 4/4/2025 |
| 07/29/2025 | COT - HCPL - Plumbing Above Ceiling | N/A | Partial Pass | 7-29-25: 3rd floor Area B above ceiling DWV along west end verified per plans and under test. Okay to continue with construction at progress areas. |
| 12/27/2024 | COT - HCBU - Framing | N/A | Partial Pass | partial pass. 1st floor interior framing approved. Pending elevators areas, store front framing and exterior framing at all of west end. Okay to proceed progress areas. 12/27/2024 |
| 08/06/2025 | COT - HCEL - Electrical Above Ceiling | N/A | Partial Pass | Level #3, East side of floor; room units and restrooms, mechanical, plumbing, electric and framing. Ok to cover walls in progress areas. |
| 11/03/2025 | COT - HCME - Mechanical Above Ceiling | N/A | Partial Pass | Level #3, center portion of corridor, mechanical above ceiling. Ok to.drop.ceiling,tiles in,progress areas. |
| COT - HCME - Mechanical Final | N/A | Scheduled | ||
| 12/04/2025 | COT - HCBU - Building Final | N/A | Partial Pass | 12/3/25: Level 1 TCO approved for the 1st floor only. The building must not be occupied at any time under this TCO. A Level 1 TCO authorizes stocking and furniture placement only. Approval from Fire, Engineering, and Right-of-Way is required before submitting a Level 1 TCO request. Without their approval, the TCO will not be issued. 12/3/25: general walk through of the first floor (not ready for building final inspection) |
| COT - HCPL - Gas Final | N/A | Scheduled | ||
| COT - HCPL - Plumbing Final | N/A | Scheduled | ||
| COT - HCEL - Electrical Final | N/A | Scheduled |
Completed Inspections
Permit Status: Needs Resubmittal
Permit Number: TC-COM-0823-02097
Permit Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2024 | COT - HCPL - Plumbing Progress | Passed | 7/24/24: plumbing underground Area A per plans ok to backfill. partial pass on underground plumbing at Area B north of elevator shaft. 8/9/24: plumbing underground Area B (grease) per plans ok to proceed. Elevator sump pump on test. Area B sanitary waste per plan and under pressure. X2 4” vents for grease interceptor on test. Okay to backfill progress areas. Shading required. 8/23/2024 8/27/24: (2) 3" for domestic water under pressure at 100psi, 8" storm drain under pressure ok to proceed 8/29/24: tie in at sewer passed ok to proceed. |
|
| 02/26/2025 | COT - HCPL - Medical Gas/Test | Passed | Med gas lines under pressure test. | |
| 03/18/2025 | BULD - Electrical Clearance | Passed | PASS 3-18-25, MSA main electric room on 1st. Floor is okay to be energized. ECO clearance issued to TEP. |
|
| 06/26/2025 | COT - HCEL - Outdoor Lighting | Passed | ||
| 09/23/2025 | COT - BULD - SWG Clearance | Passed | 9-23-25: gas pressure test for remaining areas of site to include, mechanical room, kitchen and rooftop verified under test. Okay for SWG to install meter-clearance issued. | |
| 09/23/2025 | COT - HCPL - Gas Pressure Test | Passed | 9-23-25: gas pressure test for remaining areas of site to include, mechanical room, kitchen and rooftop verified under test. Okay for SWG to install meter. |
Scheduled Inspections
Scheduled Inspections - TC-COM-0823-02097
Status: Needs Resubmittal
Description: The Project proposes a New 3-Story stand alone & independently licensed 48 bed, inpatient physical rehabilitation hospital, Level 1 is a administrative and support spaces. Level 2 & 3 are the patient floors. Each floor contains a therapy suite and 24 bed nursing units.
| Scheduled Date | Description | Entered By | Entered Date |
|---|---|---|---|
| 12/05/2025 | COT - HCPL - Gas Final | Scheduled | |
| 12/05/2025 | COT - HCPL - Plumbing Final | Scheduled | |
| 12/05/2025 | COT - HCEL - Electrical Final | Scheduled | |
| 12/05/2025 | COT - HCME - Mechanical Final | Scheduled |