Inspection Status: Not Ready

Inspection History: COT - HCEL - Electrical Final 

Permit Number - TC-COM-0823-02097

Inspection Description - COT - HCEL - Electrical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
12/05/2025 COT - HCEL - Electrical Final  Not Ready
12/12/2025 COT - HCEL - Electrical Final  Partial Pass 12-12-25: emergency electrical room, mechanical room-secure control wires on unit GWH-1EQLA-1, fire riser room, exterior receptacles front side of building verified weather resistant gfci, vacuum- pump room, med gas, main electrical room, panels in kitchen, electrical rm.1eg005, electrical room 2nd floor. Schedules in all panels, receptacles, junction boxes and all panels properly labeled, properly bonded.
12/15/2025 COT - HCEL - Electrical Final  Partial Pass 12/15/25
1st and 2nd floor:
1. Kitchen outlet adjacent to ice machine 1NLK-10 needs a bigger wall plate.
2. Garbage disposal wiring incomplete.
3. 2nd floor staff lounge 2RH058, 3 receptacles next to sink within 6ft needs to be GFCI protected.