Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T05CM04248
Permit Details
Apply Date:
08/12/2005
Applicant:
N/A
Description:
NEW: HOSPICE FACILITY
Contractors:
- DIVERSIFIED DESIGN AND CONSTRUCT
Permit Reviews
Permit Number - T05CM04248
Permit Status: C of o
Permit Description: NEW: HOSPICE FACILITY
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/06/2006 | POST 3RD PARTY REVIEW | 01/27/2006 | COMPLETED |
01/12/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 01/18/2007 | COMPLETED |
01/18/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 01/19/2007 | COMPLETED |
01/27/2006 | SITE | 03/20/2006 | COMPLETED |
01/27/2006 | RESUBMITTAL | 03/20/2006 | COMPLETED |
02/12/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 02/14/2007 | COMPLETED |
04/30/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 05/01/2007 | COMPLETED |
05/02/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 05/02/2007 | COMPLETED |
05/31/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 06/07/2006 | COMPLETED |
06/07/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 06/08/2006 | COMPLETED |
08/12/2005 | PLANS OK TO SUBMIT - 3RD PARTY | 08/12/2005 | COMPLETED |
08/12/2005 | 3RD PARTY REVIEW-COMMERCIAL | 01/06/2006 | COMPLETED |
08/30/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 09/07/2006 | COMPLETED |
12/28/2006 | REVISION - - 1ST | 01/12/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM04248
Permit Status: C of o
Permit Description: NEW: HOSPICE FACILITY
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/12/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM04248
Permit Description: NEW: HOSPICE FACILITY
Total Completed Inspections - 52
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2006 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | Need plan/permit for fire service underground |
05/08/2006 | SITE - SEWER | RRICH | Approved | IVRS - Inspection :* VACUUM TEST OF NEW MANHOLE #1 OK |
09/05/2006 | ELECTRIC - UFER | RHOLLAND | Approved | IVRS - Inspection :* OK 3/0 TO REBAR AT SERVICE |
09/26/2006 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
09/27/2006 | BUILDING PRE-SLAB | JBURGE | Approved | IVRS - Inspection :* REMAINING SE CORNER OF SLAB; 3 @ COLUMN FOOTINGS @ N.7/4.4 TO 5.2 & L.7/5.9 TO 6.9 |
10/02/2006 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* 80 PSI TEST FROM METER STUB UP UNDERGROUIND TO BUILDING STUB UP 4" OK |
11/03/2006 | EXT METAL CLIPS/EXT SHEATHING | JBURGE | Approved | IVRS - Inspection :* JOIST CLIPS @ SW PORTION PORCH |
11/06/2006 | ROOF NAILING | JBURGE | Approved | IVRS - Inspection :* ALL CRICKETS; SW PORCH AREA OK TO DRY IN |
11/06/2006 | PLUMBING - YARD WTR LINE/TEST | RRICH | Approved | IVRS - Inspection :* |
11/08/2006 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* 1) THIS IS A MEDICAL GAS PRE-CON MEETING: PRESENT IS; BRIAN FROM CITY OF TUCSON, MARIO FROM DIVERSIFIED, DAVID WITH TUCSON MEDICAL CENTER, PAT & NATE FROM MECHANICAL SYSTEMS AND STEVE FROM CACTUS MEDICAL PLEASE HAVE PLUMBING MEDICAL GAS PRE-CON 03043, MED GAS TEST 03045 AND MED GAS FINAL 03089 ADDED TO PERMIT CARD. RECALL PRE-CON INSPECTION WHEN CALLING FOR 03045 ( TO BRING PAPERWORK UP TO SPEED). 03045 TEST INSPECTION IS TO BE USED AS A DAILY PROGRESS INSPECTION. HAVE DAILY LOG FORMS ON SITE AND COMPLETED DAILY. INSTALL SERVICE VALVES WHERE REQUIRED BY 2005 NFPA |
11/14/2006 | FRAMING | JBURGE | Approved | IVRS - Inspection :* WOOD LEDGERS AS PER DETAIL #223; WOOD BEAM CLIPS AS PER DETAIL #224 |
11/14/2006 | PLUMBING - MD GAS/PRECONST MTG | BBENEDON | Approved | IVRS - Inspection :* |
11/21/2006 | REINFORCED MASONRY PRE-GROUT | JBURGE | Approved | IVRS - Inspection :* EAST HALF OF N. SCREEN WALL - OK TO GROUT & CAP |
11/22/2006 | BUILDING - PROGRESS | JBURGE | Approved | IVRS - Inspection :* CONTRACTOR CANCELLED |
11/22/2006 | ELECTRIC - PROGRESS | RHOLLAND | Approved | IVRS - Inspection :* 1) OK HARD LIDS ROOM #67, 68, 74 & 75 2) OK WALLS AND LIDS 52-65 |
11/22/2006 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* |
12/05/2006 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
12/05/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* SUPPLY & EXHAUST IN N.E POD RESTROOMS OK TO SHEETROCK. OK SHEETROCK EAST PUBLIC RESTROOMS CONDENSATE IN WALL OK TO COVER |
12/14/2006 | PLUMBING - MEDICAL GAS/TEST | BBENEDON | Approved | IVRS - Inspection :* |
12/15/2006 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* |
12/15/2006 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* |
12/20/2006 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* NE PATIENT POD - OK TO TAPE |
12/21/2006 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* OK 6 POLE BASE NORTH 1. REMOVE BOND CLAMP TO REBAR AND GEC TO BE STRAIGHT AS POSSIBLE. |
12/21/2006 | EXCAVATION/LAYOUT REBAR & ZON | JBURGE | Approved | IVRS - Inspection :* 8 @ 6' LIGHT POLE CAISSONS; NW SPILL WAY - OK TO POUR |
12/21/2006 | ELECTRIC - OUTDOOR LIGHTING | RHOLLAND | Approved | IVRS - Inspection :* |
12/29/2006 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* 1) RM 51 1/2 COPPER TO DW-RED LINE |
12/29/2006 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* OK 3 POLE BASES AND CONDUIT POLE TO POLE SOUTH |
02/26/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED PER D. SANTACRUZ |
03/30/2007 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
04/02/2007 | FIRE - FINAL | LTHOMAS | Approved | |
04/02/2007 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
04/02/2007 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
04/02/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
04/02/2007 | FIRE - ALARM FINAL | LTHOMAS | Approved | |
04/04/2007 | PLUMBING - GAS PRESS TEST FNL | BBENEDON | Approved | IVRS - Inspection :* |
04/04/2007 | SIGN - FINAL | JYBARRA | Approved | |
04/16/2007 | ELECTRIC - CABLE DROP | RHOLLAND | Approved | IVRS - Inspection :* |
04/17/2007 | OUTDOOR LIGHTING FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
04/18/2007 | ELECTRIC - CONSTRUCTION POWER | RHOLLAND | Approved | |
04/26/2007 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
04/30/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE AIR BALANCE OK OK FOR FINAL |
04/30/2007 | U VALUE FOR WINDOW | JBURGE | Approved | IVRS - Inspection :* |
04/30/2007 | STUCCO MESH | JBURGE | Approved | IVRS - Inspection :* |
04/30/2007 | BUILDING ABOVE CEILING | JBURGE | Approved | IVRS - Inspection :* |
04/30/2007 | STEM WALL/RETAINING WALL | JBURGE | Approved | IVRS - Inspection :* |
05/01/2007 | MECHANICAL - UNDERGROUND | JMILITEL | Approved | |
05/01/2007 | PLUMBING - MEDICAL GAS/FINAL | BBENEDON | Approved | IVRS - Inspection :* |
05/03/2007 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* |
05/04/2007 | PLUMBING - FINAL | BBENEDON | Approved | |
05/04/2007 | NPPO - FINAL | ACONNOR | Approved | |
05/04/2007 | LANDSCAPE - FINAL | ACONNOR | Approved | |
05/04/2007 | ENGINEERING - FINAL | JBRUCKME | Approved |