Inspection History: PLUMBING - FINAL

Permit Number - T05CM04248

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2007 PLUMBING - FINAL Approved
05/03/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. COMPLETE ICE MAKER INSTALL
2. VAC PUMP DRAIN IS OK TO COVER
3. MAKE CLEANOUTS WATER AND GAS TIGHT
4. CLEANOUT PLUGS SHALL BE LISTED TO RECEIVE SCREW IF USED FOR THAT PURPOSE.
5. INSTALL BACKFLOW PROTECTION AS REQUIRED BY PLAN
6. AT COFFEE EQUIPT IN RMS 52 AND 81 OR PROVIDE LETTER OF DELETION
7. PROVIDE TRAP SEAL PROTECTION FOR FD AT RM 81 OR PLUG.
8. BACKFLOW CERTS REQUIRED ON EXTERNAL ASSEMBLIES AROUND BUILDING.
9. RECEIVED CERTS ON INTERNAL ASSEMBLIES FOR ICE MAKERS AND IRRIGATION AND DOMESTIC SUPPLY ASSEMBLIES
10. RECEIVED LETTERS FROM MECH ENGINEER STATING NO NEED FOR TAPE PRIMER AT VAC PUMP.
05/01/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. WATER LEAK RM 168
2. CORRECT IMPROPERLY VENTED P TRAP AT VAC PUMP
3. PROVIDE METHOD OF MAINTAIN A TRAP SEAL AT VAC PUMP
4. INSTALL UNION ON 1" RPA
5. SUPPORT ALL RPA'S
6. PROVIDE BACKFLOW CERTS
7. HARD PIPE UPSTREAM OF ALL BACKFLOW ASSEMBLIES
8. INSTALL ICE MAKERS
9. PROVIDE CORRECT DRAINAGE FOR INDIRECT WASTE FROM ICE MAKERS. 1" AG REQUIRED.

MED GAS COMPLETE
EXP TANK OK
BED PANS OK
03/30/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
ADMINISTRATIVE AREA PLUMBING OK
03/28/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
AT BED PAN WASHERS, NO VALVES ARE ALLOWED DOWNSTREAM OF ATMOSPHERIC VACUUM BREAKERS
PER CHAPTER 6 UPC
NEED PLAN REVISION FOR VAC PUMP DRAIN