Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM04248
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* ALL CLOSET FLANGES OK TO COVER |
|
02/08/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 1" SOFT CU TO FOUNTAIN OK RP NOT YET INSTALLED 2) CLOSET FLANGES WEST HALF OK-DO NOT COVER ANYMORE WITHOUT INSPECTION |
|
12/29/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RM 51 1/2 COPPER TO DW-RED LINE |
|
12/21/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RMS 39, 40, 49 DWV AND WATER OK |
|
12/19/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RMS 34, 35, 38 AND 45 DWV AND WATER OK TO INSULATE AT RM 39. DETAILS 5-P2 AND 4-P3 1/2 HW DOWN TO L.S, WM AND BSA APPEARS TO BE UNDERSIZED INSTALL 3/4 DOWN TO FIRST FIXTURE. ALSO, ICE MACHINE AND COFFEE BREWER EACH REQUIRE BACKFLOW PROTECTION. |
|
12/15/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. DWV AT RM 45, 51 AND 53 OK 2. ROOF DRAINS RMS 44 AND 43 OK 3. PLANS APPROVED IN ERROR; WATER PIPING SUPPLY FOR ICE MAKER AND COFFEE MAKING EQUIPMENT IS IN VIOLATION OF UPC SECTIONS 603.3.4 AND 603 ALSO, CITY POLICY IS TO ALLOW ONLY ONE DEVICE PER EACH PIECE OF EQUIPMENT THAT MAY CAUSE CONTAMINATION TO THE WATER SUPPLY. EACH DEVICE SHALL BE ACCESSIBLE. |
|
12/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PIPING INSULATION RMS 23-33 OK 2. MED GAS OXYGEN UNDER 150 PSI TEST MOST LABELING COMPLETE. LABELS AND ISOLATION FROM METAL NEEDED AT RM 47 PROVIDE LOG BOOK AT NEXT INSPECTION |
|
12/12/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RMS 23, 31, 32, 33 AND 30 OK TO COVER RM 27 DWV OK -- WATER NOT INSTALLED RMS 26, 25 AND 24 - CORRECT LEAKS ON DWV - RETEST RMS 26, 25 AND 24 WATER PIPING OK |
|
12/01/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RMS 55-63 OK TO COVER WALLS ONLY BRACE VENT AT NS RM 61 MED GAS PROGRESS - NATE WORKING ON OXYGEN LINE RM 63 NF NITROGEN W/ALARMED REGULATORS IN USE. |
|
11/30/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TEST ON RDS IN RMS 61 AND 59 OK WATER PIPING IN WALLS RMS 66-76 OK FOR INSULATION DWV HAS LEAK - RETEST ALL DWV IN 66-76 |
|
11/27/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RMS 7-17 ROOF DRAINS AND DOMESTIC PIPING OK 2. OK TO INSULATE HOT WATER 3. MED GAS PROGRESS OK, REGULATOR AND LOG BOOK CHECKED. 4. PIPING OK - LABELS NEEDED BEFORE COVERING WESTSIDE PIPING. |
|
11/22/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RD ROOM 10-OK, KIT ROOM 13 OK, WATER IN WALLS THIS AREA OK, IN TOILET ROOMS MAKE 3" CLEANOUTS ACCESSIBLE |
|
11/21/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TYPE L WATER PIPING W/100 PSI TEST IN WALLS ONLY ROOMS 15, 16, 8, 9 AND NURSE STATIONS. DWV NOT READY. MED GAS LOG BOOK WAS CHECKED AND IS UP TO DATE |
|
11/15/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* VAC UNDER TEST 1/2 OZ PIPING MOSTLY COMPLETE IN SW POD HANGER MISSING ON 1/2" TUBING. |
|
11/06/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT RESTROOMS 67, 68, 74, 75, 89, 90 WITH SINK IN MEETING ROOM 81 THRU ROOF OK. 1. SHALL PROVIDE CORRECT DRAIN ARM FOR ROOM 70 WATER PIPING IN WALL & OVERHEAD SAME ROOMS ABOVE 100 PSI AIR TEST OK |