Permit: T05CM04248

Parcel: 110121020


Addresses:

2715 N WYATT DR


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM04248

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
ALL CLOSET FLANGES OK TO COVER
02/08/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 1" SOFT CU TO FOUNTAIN OK RP NOT YET INSTALLED
2) CLOSET FLANGES WEST HALF OK-DO NOT COVER ANYMORE WITHOUT INSPECTION
12/29/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RM 51 1/2 COPPER TO DW-RED LINE
12/21/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 39, 40, 49 DWV AND WATER OK
12/19/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 34, 35, 38 AND 45 DWV AND WATER OK TO INSULATE AT RM 39.
DETAILS 5-P2 AND 4-P3
1/2 HW DOWN TO L.S, WM AND BSA APPEARS TO BE UNDERSIZED INSTALL 3/4 DOWN TO FIRST FIXTURE. ALSO, ICE MACHINE AND COFFEE BREWER EACH REQUIRE BACKFLOW PROTECTION.
12/15/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. DWV AT RM 45, 51 AND 53 OK
2. ROOF DRAINS RMS 44 AND 43 OK
3. PLANS APPROVED IN ERROR; WATER PIPING SUPPLY FOR ICE MAKER AND COFFEE MAKING EQUIPMENT IS IN VIOLATION OF UPC SECTIONS 603.3.4 AND 603
ALSO, CITY POLICY IS TO ALLOW ONLY ONE DEVICE PER EACH PIECE OF EQUIPMENT THAT MAY CAUSE CONTAMINATION TO THE WATER SUPPLY. EACH DEVICE SHALL BE ACCESSIBLE.
12/14/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PIPING INSULATION RMS 23-33 OK
2. MED GAS OXYGEN UNDER 150 PSI TEST MOST LABELING COMPLETE. LABELS AND ISOLATION FROM METAL NEEDED AT RM 47

PROVIDE LOG BOOK AT NEXT INSPECTION
12/12/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 23, 31, 32, 33 AND 30 OK TO COVER
RM 27 DWV OK -- WATER NOT INSTALLED
RMS 26, 25 AND 24 - CORRECT LEAKS ON DWV - RETEST
RMS 26, 25 AND 24 WATER PIPING OK
12/01/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 55-63 OK TO COVER WALLS ONLY
BRACE VENT AT NS RM 61
MED GAS PROGRESS - NATE WORKING ON OXYGEN LINE RM 63
NF NITROGEN W/ALARMED REGULATORS IN USE.
11/30/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TEST ON RDS IN RMS 61 AND 59 OK
WATER PIPING IN WALLS RMS 66-76 OK FOR INSULATION
DWV HAS LEAK - RETEST ALL DWV IN 66-76
11/27/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. RMS 7-17 ROOF DRAINS AND DOMESTIC PIPING OK
2. OK TO INSULATE HOT WATER
3. MED GAS PROGRESS OK, REGULATOR AND LOG BOOK CHECKED.
4. PIPING OK - LABELS NEEDED BEFORE COVERING WESTSIDE PIPING.
11/22/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RD ROOM 10-OK, KIT ROOM 13 OK, WATER IN WALLS THIS AREA OK, IN TOILET ROOMS MAKE 3" CLEANOUTS ACCESSIBLE
11/21/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TYPE L WATER PIPING W/100 PSI TEST IN WALLS ONLY
ROOMS 15, 16, 8, 9 AND NURSE STATIONS.
DWV NOT READY.
MED GAS LOG BOOK WAS CHECKED AND IS UP TO DATE
11/15/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
VAC UNDER TEST
1/2 OZ PIPING MOSTLY COMPLETE IN SW POD
HANGER MISSING ON 1/2" TUBING.
11/06/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST WASTE & VENT RESTROOMS 67, 68, 74, 75, 89, 90 WITH SINK IN MEETING ROOM 81 THRU ROOF OK.
1. SHALL PROVIDE CORRECT DRAIN ARM FOR ROOM 70
WATER PIPING IN WALL & OVERHEAD SAME ROOMS ABOVE
100 PSI AIR TEST OK