Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM04248
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
02/22/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK GROUNDING AT SERVICE, WATER, GAS, BLD, STEEL SPRINKLER, X-FORMERS ALL OK! SERVICE TERMINATIONS OK MAIN BOND JUMPER OK 2. OK ABOVE CEILING EXCEPT ROOM #20 NOT FINISHED |
|
02/07/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FIXTURES, CONDUIT AND BOXES TO COLUMN K 2) FINISH VDV CABELING |
|
02/06/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS |
|
02/02/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) MANUFACTURES CLIPS TO BE EFFECTIVE 2) SUPPORTS TO BE PER 300.11 3) FIXTURE TO BE PER 410.16 4) MISSING COVER PLATES 5) FINISH VDV CABELING |
|
01/26/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. USE APPROVED HARDWARE WITH LIGHTS 2. FINISH SUPPORTING VDV CABELING OK FIXTURES, BOXES & CONDUIT COLUMN F WEST |
|
01/24/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SECURELY ATTACH FIXTURE TO GRID 410.16 |
|
01/23/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/22/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/17/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK WALLS ROOM 5-17 OK HARD LIDS ROOM 89 & 90 1. PROTECT M/C CABLE IN CHANNEL OR MOVE 2. SUPPORT M/C CABLE WITHIN 12" OF BOXES & CANS |