Permit: T05CM04248

Parcel: 110121020


Addresses:

2715 N WYATT DR


Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T05CM04248

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2007 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
02/06/2007 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ABV CEILING WEST OF AND INCLUDING HALL 60 OK
01/26/2007 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
OVERHEAD WEST OF AND INCLUDING HALL 72 OK
YARD WATER PIPING JUST STARTING
PROVIDE SITE UTILITY PLAN, REDLINE ANY CHANGES,
PROVIDE MATERIAL SPECS.
INSTALL TRACER WIRE
LEAVE EXPOSED ALL JOINTS FOR TEST
DO NOT TEST W/AIR
01/25/2007 PLUMBING - ABOVE CEILING Cancelled CANCELLED BY MARCO
01/25/2007 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/23/2007 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL UNISTRUT CLAMPS ON UNISTRUT SUPPORTS
INSTALL HANGERS ON PIPING 1 1/4" AND SMALLER AT 6'
INTERVALS MAX
11/08/2006 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) THIS IS A MEDICAL GAS PRE-CON MEETING: PRESENT IS; BRIAN FROM CITY OF TUCSON, MARIO FROM DIVERSIFIED, DAVID WITH TUCSON MEDICAL CENTER, PAT & NATE FROM MECHANICAL SYSTEMS AND STEVE FROM CACTUS MEDICAL
PLEASE HAVE PLUMBING MEDICAL GAS PRE-CON 03043, MED GAS TEST 03045 AND MED GAS FINAL 03089 ADDED TO PERMIT CARD. RECALL PRE-CON INSPECTION WHEN CALLING FOR 03045 ( TO BRING PAPERWORK UP TO SPEED). 03045 TEST INSPECTION IS TO BE USED AS A DAILY PROGRESS INSPECTION. HAVE DAILY LOG FORMS ON SITE AND COMPLETED DAILY. INSTALL SERVICE VALVES WHERE REQUIRED BY 2005 NFPA