Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05CM04248
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2007 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
02/28/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL PIPE SUPPORTS WITHIN 18" OF BRANCH CONNECTIONS AND EQUIPMENT. USE CORRECT SIZE PIPE CLAMPS NOT EMT CLAMPS. LEAVE 15 PSI TEST ON AND RECALL FOR INSPECTION. |
|
02/16/2007 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* WELDED GAS MAIN FROM METER TO 2" MAIN W/65 PSI TEST OK |
|
02/12/2007 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 60 PSI TEST ON 4" UNDERGROUND FROM REDLINE METER LOCATION UP AT BUILDING THRU 4X3X2 1/2 TEE CAPPED ON ROOF AND AT 3' OF 2 1/2" BRANCH. |
|
10/02/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 80 PSI TEST FROM METER STUB UP UNDERGROUIND TO BUILDING STUB UP 4" OK |