Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T05CM04248
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2007 | ELECTRIC - CONSTRUCTION POWER | Approved | ||
04/17/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* | |
03/08/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* | |
03/07/2007 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE REVISE PLANS FOR EC1A & EL4A & ET1 OK LINE SIDE BONDING OK GENERATOR GROUNDING, TERMINATIONS OK PREVIOUS ITEMS FROM 3/5/07 OK EQUIPMENT WITH GREEN STICKERS RECEIVED LETTER FOR TORQUE |
|
03/05/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* | |
03/02/2007 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* 1. BONDING ON LINE SIDE CONDUCTORS TO BE AS PER 250.102 2. VERIFY MISSING 200 AMP MAIN - SES 3. DO NOT STACK LUGS 4. WHERE IS GROUNDING ELECTRODE & CONDUCTOR AT GENERATOR. 5. MOUNT NEUTRAL BLOCK TO POST DESIGNATED FOR SUCH 6. CHECK CONDUCTOR TERMINATIONS AT GENERATOR MAIN 7. PLEASE PROVIDE A LETTER FOR TORQUE OF EQUIPMENT ON COMPANY LETTERHEAD. |
|
03/01/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* RECEIVED GFI TEST RESULTS -- OK TO ENERGIZE CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT |
|
02/23/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* 1) CONTR. NOT TO ENERGIZE EQUIP. BEYOND THE SERVICE PRIOR TO APPROVAL OF GFI TESTING BY INSPECTOR. CONTR. WILL CONTACT G.E. CONCERNING GFI MAIN-BREAKER TEST. INSTALLATION INSTRUCTIONS NOT CLEAR |
|
02/22/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* | |
02/20/2007 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* |