Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
Permit Number - T05CM04248
Inspection Description - PLUMBING - MEDICAL GAS/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2007 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
03/12/2007 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* VAC PIPING COMPLETE IN BUILDING, STUBBED INTO MECH RM. 60 PSI TEST AND LABELS OK |
|
03/02/2007 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* VACUUM PIPING W/60 PSI TEST EVERYTHING WEST OF HALL 60 OK - LABELS INSTALLED |
|
02/23/2007 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1 INSTALLER AND 1 HOLDER ON VAC SYSTEM |
|
02/20/2007 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* NATE INSTALLING 1 1/2 VACUUM MAIN AND BRANCH CONNECTIONS FOR VACUUM PLAN REVISION OF 1/12/07 WHICH DOES NOT YET HAVE CITY APPROVAL. CHECKED LOG BOOK. WORK IN PROGRESS HALL 72 AND 4. |
|
12/14/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
12/11/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* ONE INSTALLER AND ONE HELPER INSTALLING 02 IN EAST WING. |
|
12/08/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* PROGRESS OK, NATE INSTALLING VAC PIPNG, EAST WING NOTE: OVERHEAD HORIZONTAL PIPING SUPPORTS SHALL NOT EXCEED 6'. I WANT TO SEE LABELS INSTALLED IN WALLS PRIOR TO CONCEALMENT. |
|
12/01/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
11/29/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* OUTLET BOXES TIED IN LOW PSI TEST IN PROGRESS |
|
11/27/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
11/16/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* MED. GAS PIPING LOOKS GOOD, JUST NEED LABELS BEFORE COVERING WALLS. |
|
11/15/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* |