Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM04248

Parcel: 110121020


Addresses:

2715 N WYATT DR


Inspection Status: Approved

Inspection History: PLUMBING - MEDICAL GAS/TEST

Permit Number - T05CM04248

Inspection Description - PLUMBING - MEDICAL GAS/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2007 PLUMBING - MEDICAL GAS/TEST Approved IVRS - Inspection :*
03/12/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
VAC PIPING COMPLETE IN BUILDING, STUBBED INTO MECH RM.
60 PSI TEST AND LABELS OK
03/02/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
VACUUM PIPING W/60 PSI TEST
EVERYTHING WEST OF HALL 60 OK - LABELS INSTALLED
02/23/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1 INSTALLER AND 1 HOLDER ON VAC SYSTEM
02/20/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
NATE INSTALLING 1 1/2 VACUUM MAIN AND BRANCH CONNECTIONS FOR VACUUM PLAN REVISION OF 1/12/07 WHICH DOES NOT YET HAVE CITY APPROVAL. CHECKED LOG BOOK. WORK IN PROGRESS HALL 72 AND 4.
12/14/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
12/11/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
ONE INSTALLER AND ONE HELPER INSTALLING 02 IN EAST WING.
12/08/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
PROGRESS OK, NATE INSTALLING VAC PIPNG, EAST WING

NOTE: OVERHEAD HORIZONTAL PIPING SUPPORTS SHALL NOT EXCEED 6'. I WANT TO SEE LABELS INSTALLED IN WALLS PRIOR TO CONCEALMENT.
12/01/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
11/29/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
OUTLET BOXES TIED IN LOW PSI TEST IN PROGRESS
11/27/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
11/16/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MED. GAS PIPING LOOKS GOOD, JUST NEED LABELS BEFORE COVERING WALLS.
11/15/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*