Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T05CM04248
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2007 | MECHANICAL - ABOVE CEILING | Approved | ||
02/22/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SECURE STEEL PLATES AROUND FIRE DAMPERS TO THE STRUCTURE. WILL CHECK ON FINAL. PROVIDE ACCESS DOORS. OK FOR CEILING TILES. |
|
02/06/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILING N.W. AND S.E. PATIENT PODS TO ARCH BEYOND COM ROOM 2) NEED TO SEE SPLIT SYSTEM IN COM. ROOM |
|
01/24/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES S.W PATIENT POD |
|
01/23/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* INSULATE RETURN DUCT @ S.W PATIENT POD ADMIN & ENTRY OK FOR CEILING TILES. |
|
12/05/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/30/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NORTHWEST POD RESTROOM SOUTHEAST POD RESTROOM ROOM 5, 6 OK |
|
11/22/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY EXHAUST IN ADMIN-RESTROOMS AND S.W. POD RESTROOMS 2) OK TO SHEETROCK |