Permit: T05CM04248

Parcel: 110121020


Addresses:

2715 N WYATT DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04248

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
REVISION TO GO BACK THROUGH WILDAN FOR STAMP
04/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. USE CORRECT SIZE SPLICE CONNECTOR PER LISTING
2. SPLICES IN PULL BOX TO BE FOR WET LOCATION
3. FINISH SUPPORTING JUNCTION BOX FOR COMPRESSOR/VAC PUMP
4. TIGHTEN SEAL TITE FITTINGS
04/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PROPERLY GROUND POLE BASES
2) BOND BUSHING AT OVER 250 V 250.77
3) MAINTAIN WORKING CLEARANCES A/C DISCONNECT
4) TIGHTEN LOOSE FITTINGS
5) DISCONNECT NOT ON UNITS 440.14
6) USE TERMINAL ENDS ON STRANDED CONDUCTOR
7) PROPERLY GROUND BOX EXHAUST FAN
8) SUPPORT BOXES FOR PHOTO CELLS
9) WAITING ON EQUIPMENT
04/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK INTERIOR FOR DEVICES & LIGHTING
1. PLEASE PROVIDE A LETTER CERTIFYING EM & EXIT LIGHTING IS WORKING PROPERLY.

RECEIVED PAPERWORK FOR GFI, GENERATOR TEST, TORQUE OF EQUIPMENT.
04/04/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE OFFICE FURNITURE CONNECTIONS.
2. LABEL BREAKER TO INTENDANT USAGE 404.8
NO ABBREVIATIONS
3. BOXES MORE THAN 1/4" FROM SURFACE TO BOX NEED AN APPROVED EXTENDER RING 314.20
03/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
MARIO TO RESCHEDULE