Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM04248
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* REVISION TO GO BACK THROUGH WILDAN FOR STAMP |
|
04/16/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. USE CORRECT SIZE SPLICE CONNECTOR PER LISTING 2. SPLICES IN PULL BOX TO BE FOR WET LOCATION 3. FINISH SUPPORTING JUNCTION BOX FOR COMPRESSOR/VAC PUMP 4. TIGHTEN SEAL TITE FITTINGS |
|
04/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROPERLY GROUND POLE BASES 2) BOND BUSHING AT OVER 250 V 250.77 3) MAINTAIN WORKING CLEARANCES A/C DISCONNECT 4) TIGHTEN LOOSE FITTINGS 5) DISCONNECT NOT ON UNITS 440.14 6) USE TERMINAL ENDS ON STRANDED CONDUCTOR 7) PROPERLY GROUND BOX EXHAUST FAN 8) SUPPORT BOXES FOR PHOTO CELLS 9) WAITING ON EQUIPMENT |
|
04/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK INTERIOR FOR DEVICES & LIGHTING 1. PLEASE PROVIDE A LETTER CERTIFYING EM & EXIT LIGHTING IS WORKING PROPERLY. RECEIVED PAPERWORK FOR GFI, GENERATOR TEST, TORQUE OF EQUIPMENT. |
|
04/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
04/02/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. TIGHTEN LOOSE OFFICE FURNITURE CONNECTIONS. 2. LABEL BREAKER TO INTENDANT USAGE 404.8 NO ABBREVIATIONS 3. BOXES MORE THAN 1/4" FROM SURFACE TO BOX NEED AN APPROVED EXTENDER RING 314.20 |
|
03/29/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MARIO TO RESCHEDULE |