Permit: T05CM04248

Parcel: 110121020


Addresses:

2715 N WYATT DR


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM04248

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
09/22/2006 PLUMBING - ROUGH, SOIL Partial Approval - CORRECT SLOPE ON NS WASTE AT TOILET RM 8 LOCATION
OK TO POUR AFTER CORRECTING.
- ALL AREAS EXCEPT SOUTHEAST CORNER OF BUILDING.
- I RECOMMEND WATER TESTING ALL BUILDING DRAIN PIPING AGAIN BECAUSE OF SHOWER FORM STAKES PROXIMITY TO SINK PIPING.
09/19/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
UNDERGROUND PIPING OK TO COVER
RECALL UNDERGROUND INSPECTION FOR PRE-SLAB
09/18/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
SOIL PIPING ALONG M.3, TRS 62, 63, 55, 56 OK TO COVER
09/15/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH PIPING RMS 34-36 AND MAIN LINE THROUGH END OF LINE C.O OK TO COVER.
PIPE WRAPS IN FOOTING OK
4" CW W/BRAZED JOINT 98 PSI TEST
PROTECT FROM CONCRETE
09/14/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
RMS 27, 24, 25, 31 AND 32 OK TO COVER
09/12/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- TOILET RM 8, 9, 15 AND 1
- CORRECT SLOPE AT NS WASTE AND SH TRAP ARM IN TR8
- OK TO COVER AFTER CORRECTING.
09/08/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PRE-SLAB SEC. A-F PIPE WRAPS OK
FDS W/PRIMERS INSTALLED
SHOWER DRAINS INSTALLED
09/05/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
SEC A-C OK TO COVER
NEED TO SEE FDS AND PIPE WRAPS BEFORE CONCRETE.
09/01/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ABS DWV COL LINES C-F OK TO COVER
CALL FOR PRE-SLAB PRIOR TO CONCRETE.
08/31/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
RESTROOM AREAS DRAIN TO BE UPSIZED AT LAV BECAUSE PLAN IS APPROVED IN ERROR TO 3"
ALL PIPING TO BE SHADED CORRECTLY.
DELTA 3 REVISION DATED 8/15/06 SERVING AS REDLINE ON SITE. PLEASE RED LINE UP SIZE ON YOUR PLAN.