Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address NEW:
8080 S HOUGHTON RD
Apply Date:
12/01/2003
Applicant:
METRO PERMIT EXPRESS, INC
Description:
NEW:GROCERY STORE
Contractors:
  • TL ROOF AND ASSOCIATES

Permit Reviews

Permit Number - T03CM05561
Permit Status: C of o
Permit Description: NEW:GROCERY STORE
Start Date Submittal Complete Date Status  
01/12/2005 3RD PARTY REVIEW-REVISION/OTHER-2ND 01/21/2005 COMPLETED Review Details
01/14/2004 3RD PARTY REVIEW-COMMERCIAL 08/06/2004 COMPLETED Review Details
01/21/2005 POST 3RD PARTY REVIEW 01/31/2005 COMPLETED Review Details
01/31/2005 RESUBMITTAL 02/14/2005 COMPLETED Review Details
03/24/2005 3RD PARTY REVIEW-REVISION/OTHER 03/24/2005 COMPLETED Review Details
03/24/2005 POST 3RD PARTY REVIEW 08/23/2005 COMPLETED Review Details
08/06/2004 RESUBMITTAL 10/05/2004 COMPLETED Review Details
11/24/2004 3RD PARTY REVIEW-REVISION/OTHER 01/31/2005 COMPLETED Review Details
12/01/2003 PLANS OK TO SUBMIT - 3RD PARTY 12/08/2003 COMPLETED Review Details
12/09/2003 3RD PARTY REVIEW-COMMERCIAL 01/09/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM05561
Permit Status: C of o
Permit Description: NEW:GROCERY STORE
Total Outstanding Activity Conditions - 1
Date Name
12/01/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM05561
Permit Description: NEW:GROCERY STORE
Total Completed Inspections - 55
Date Description Inspector Results Comments
11/15/2004 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*
12/08/2004 BUILDING - TEMP POWER FOR TEST LHANLY Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU NEED A BLDG FIRST
12/08/2004 PLUMBING - SEWER HCS CONNECT RRICH Approved IVRS - Inspection :*
12/13/2004 ELECTRIC - CONSTRUCTION POWER RSUBA Approved IVRS - Inspection :*
1) OK TO CLEAR ELECTRIC CONSTRUCTION POWER
12/14/2004 TEP CLEARANCE - AM RMAJUTA Approved POWER POLE
12/16/2004 STEM WALL/RETAINING WALL LHANLY Approved IVRS - Inspection :*
1) LINE F 205-5
12/28/2004 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*
1) SPREAD FOOTINGS AROUND FREEZER (AREA G-F)
12/29/2004 ELECTRIC - UNDERGROUND RSUBA Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRICIANS WENT HOME DUE TO RAIN
12/29/2004 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*/COMBINATION WASTE & VENT ON NORTH WEST SECTION UNDERGROUND WATER TEST OR PER HIGHLIGHTED & INITIALED PLAN ON SITE. 1) WILL REQUIRE CITY APPROVED REVISED PLAN OF ALL RED LINES AND ADDITIONAL FIXTURES
12/29/2004 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection :*
12/29/2004 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
03/31/2005 STUCCO MESH LHANLY Approved IVRS - Inspection :*
04/13/2005 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection :*
04/13/2005 FRAMING LHANLY Approved IVRS - Inspection :*
04/13/2005 EXT METAL CLIPS/EXT SHEATHING LHANLY Approved IVRS - Inspection :*
04/19/2005 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :* INSPECTED CONDENSATE DRAINS ON FOOD CASES. STILL NEED TO SEE WALK IN COOLER DRAINS
04/27/2005 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
05/11/2005 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
05/11/2005 ROOF NAILING LHANLY Approved IVRS - Inspection :*
05/13/2005 ELECTRIC - TEMPORARY SERVICE RMAJUTA Approved ELECTRICAL CONTRACTOR RESPONSIBLE TO KEEP ENERGIZED PARTS SAFE, AND LOCK OUT UN-INSPECTED WORK CALLED IN FIR 5/13/05 1) UFER APPROVED PER ROBERT SUBA. 2) SES OK TO ENERGIZE. 3) HDPB OL TO ENERGIZE. 4. TRANSFORMER TM OK TO ENERGIZE 5) PNL BOARD LDPA OK TO ENERGIZE. 6) PNLS CPA, CPB, CLA, CPC OK TO ENERGIZE. ELECTRICAL CONTRACTOR TO LOCK OUT ALL UNINSPECTED WORK AND GET OK PRIOR TO ENERGIZING ANY OTHER WORK. 7) SES CHANGE ON CONDUCTORS TO COPPER OK BY ENGINEER LETTER. 8) WATER -GAS-SPINKLER-STEEL-UFER APPROVED.
05/13/2005 ELECTRIC - CABLE DROP RMAJUTA Approved IVRS - Inspection :*
05/13/2005 ELECTRIC - UFER RMAJUTA Approved IVRS - Inspection :*
05/13/2005 TEP CLEARANCE - PM JKOZUCH Approved ECO
05/18/2005 PLUMBING - GAS PRESS TEST FNL RRICH Approved IVRS - Inspection :*20 PSI AIR TST ON ENTIRE SYSTEM UP TO APPLIANCE SHUT OFF VALVES OK
05/18/2005 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :*
05/18/2005 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
05/18/2005 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
05/18/2005 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
05/18/2005 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection :*
05/19/2005 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :* PROVIDE ACCESS TO FILTERS ON FAN COILS. NEED TO SEE CONDENSATE DRAIN IN PHARMACY WILL CHECK ON FINAL. OK FOR TEMP C OF O
05/19/2005 PLUMBING - ROOF DRAINS RRICH Approved
05/19/2005 PLUMBING - YARD WTR LINE/TEST RRICH Approved
05/23/2005 ELECTRIC - ABOVE CEILING RMAJUTA Approved IVRS - Inspection :*
1) DELI, BAKERY, PHARMACY CEILINGS OK TO COVER
05/23/2005 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
1) ? #1 DISCONNECT MOVED-OK
2) DLA OK, DLA1, DLA2 OK
3) P1-OK, P-2 OK, AH 3, 4 AND 5 OK
4) LA OK CK FUSES
5) LA CONTACTOR GRD.
6) EH CK FUSES, EH OK
7) EH CONTACTOR OK
8) TRANS TEM OK
9) OK ITEMS ABOVE OK TO POWER CK
05/24/2005 PLUMBING - PROGRESS TRINIVJR Approved IVRS - Inspection :*
1) WOMENS AND MENS RESTROOM IS WORKING
2) OK FOR TEMP C OF O
06/03/2005 ELECTRIC - PROGRESS RMAJUTA Approved IVRS - Inspection :* FOR TEMP C OF O CALL IN UNDER 2090. 1. EMERGENCY GENERATOR TEST RESULTS & INSPECTION OF EQUIPMENT AND INSPECTION OF GENERATOR RUNNING ALL EMERGENCY LIGHTING. 2. ALL ELECTRICAL SWITCH GEAR AND PANELS TO HAVE ALL LABELING & ID REQUIREMENTS PLUS PANEL SCHEDULES. 3. ALL PANELS TO BE CLOSED & COVERS PUT ON. 4. ALL LOW VOLTAGE CABLING 2ND FLOOR BY PHARMACY TO BE SUPPORTED OFF T-BAR CEILING. 5. INSPECT SOFFIT AREAS-MAKE SURE ALL J-BOXES MADE UP. 6. FINISH J-BOXES ABOVE SEAFOOF FREEZERS. 7. FINISH WIRING BAND SAWS MEAT SECTION. 8. CLOSE UP ALL OPEN J-BOXES. 9. ROOF DONE?
06/10/2005 FIRE - FINAL JEGAN Approved
06/10/2005 FIRE SPKLR - FINAL LLAKEY Approved
06/10/2005 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
06/13/2005 HEALTH DEPT - FINAL 724-7908 RPEYTON Approved
06/14/2005 BUILDING - PROGRESS LHANLY Approved IVRS - Inspection :*
06/16/2005 OUTDOOR LIGHTING FINAL RMAJUTA Approved
06/29/2005 SIGN - FINAL RDEAR Approved shop & elec ok
09/16/2005 MECHANICAL - FINAL LHANLY Approved IVRS - Inspection :*
APPROVED ON REINSPECT
09/16/2005 PLUMBING - FINAL LHANLY Approved IVRS - Inspection :*
09/16/2005 PLUMBING - FINAL LHANLY Approved IVRS - Inspection :
See detailed listing on site.| 999*
09/16/2005 MECHANICAL - PROGRESS LHANLY Approved IVRS - Inspection :*
09/16/2005 MECHANICAL - HOOD SYSTEMS LHANLY Approved IVRS - Inspection :*
09/16/2005 MECHANICAL - HOODS LHANLY Approved IVRS - Inspection :*
09/19/2005 RIGHT OF WAY - FINAL NKALAHAR Approved ( No "complete" until PIA approved)
09/19/2005 ELECTRIC - FINAL RSUBA Approved IVRS - Inspection :*
09/19/2005 LANDSCAPE - FINAL ACONNOR Approved Ok for Temp. C of O

Monitoring Report required for approval.
09/19/2005 NPPO - FINAL ACONNOR Approved Ok for Temp. C of O

Monitoring Report required for approval.
09/19/2005 U VALUE FOR WINDOW LHANLY Approved IVRS - Inspection :*
09/20/2005 ENGINEERING - FINAL DROBERTS Approved MET WITH THE OWNER, MANAGEMENT FIRM, AND THE CONTRACTOR TO DISCUSS THE REMAINING WORK ON THIS SITE. THEY WILL TRY TO COMPLETE THE WORK FOR THIS AREA WITHIN THE NEXT TWO WEEKS, A RE-INSPECTION FOR THE SITE WILL BE SCHEDULED ONCE ALL OF THE WORK IS COMPLETE. I ADVISED THE CREW THAT I WILL TRY TO VISIT THE SITE DURING THAT TIME FRAME TO SEE HOW THE WORK IS PROGRESSING.

Documents

File Name Document Type  
C OF O_06-07-2007.TIF CERT OF OCC VIEW
None CERT OF OCC VIEW
BONDRELEASE.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW