Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T03CM05561
Permit Details
Apply Date:
12/01/2003
Applicant:
METRO PERMIT EXPRESS, INC
Description:
NEW:GROCERY STORE
Contractors:
- TL ROOF AND ASSOCIATES
Permit Reviews
Permit Number - T03CM05561
Permit Status: C of o
Permit Description: NEW:GROCERY STORE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/12/2005 | 3RD PARTY REVIEW-REVISION/OTHER-2ND | 01/21/2005 | COMPLETED |
| 01/14/2004 | 3RD PARTY REVIEW-COMMERCIAL | 08/06/2004 | COMPLETED |
| 01/21/2005 | POST 3RD PARTY REVIEW | 01/31/2005 | COMPLETED |
| 01/31/2005 | RESUBMITTAL | 02/14/2005 | COMPLETED |
| 03/24/2005 | 3RD PARTY REVIEW-REVISION/OTHER | 03/24/2005 | COMPLETED |
| 03/24/2005 | POST 3RD PARTY REVIEW | 08/23/2005 | COMPLETED |
| 08/06/2004 | RESUBMITTAL | 10/05/2004 | COMPLETED |
| 11/24/2004 | 3RD PARTY REVIEW-REVISION/OTHER | 01/31/2005 | COMPLETED |
| 12/01/2003 | PLANS OK TO SUBMIT - 3RD PARTY | 12/08/2003 | COMPLETED |
| 12/09/2003 | 3RD PARTY REVIEW-COMMERCIAL | 01/09/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03CM05561
Permit Status: C of o
Permit Description: NEW:GROCERY STORE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/01/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T03CM05561
Permit Description: NEW:GROCERY STORE
Total Completed Inspections - 55
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2004 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection :* |
| 12/08/2004 | BUILDING - TEMP POWER FOR TEST | LHANLY | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU NEED A BLDG FIRST |
| 12/08/2004 | PLUMBING - SEWER HCS CONNECT | RRICH | Approved | IVRS - Inspection :* |
| 12/13/2004 | ELECTRIC - CONSTRUCTION POWER | RSUBA | Approved | IVRS - Inspection :* 1) OK TO CLEAR ELECTRIC CONSTRUCTION POWER |
| 12/14/2004 | TEP CLEARANCE - AM | RMAJUTA | Approved | POWER POLE |
| 12/16/2004 | STEM WALL/RETAINING WALL | LHANLY | Approved | IVRS - Inspection :* 1) LINE F 205-5 |
| 12/28/2004 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | IVRS - Inspection :* 1) SPREAD FOOTINGS AROUND FREEZER (AREA G-F) |
| 12/29/2004 | ELECTRIC - UNDERGROUND | RSUBA | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRICIANS WENT HOME DUE TO RAIN |
| 12/29/2004 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection :*/COMBINATION WASTE & VENT ON NORTH WEST SECTION UNDERGROUND WATER TEST OR PER HIGHLIGHTED & INITIALED PLAN ON SITE. 1) WILL REQUIRE CITY APPROVED REVISED PLAN OF ALL RED LINES AND ADDITIONAL FIXTURES |
| 12/29/2004 | REINFORCED MASONRY PRE-GROUT | LHANLY | Approved | IVRS - Inspection :* |
| 12/29/2004 | BUILDING PRE-SLAB | LHANLY | Approved | IVRS - Inspection :* |
| 03/31/2005 | STUCCO MESH | LHANLY | Approved | IVRS - Inspection :* |
| 04/13/2005 | SHEET ROCK NAILING | LHANLY | Approved | IVRS - Inspection :* |
| 04/13/2005 | FRAMING | LHANLY | Approved | IVRS - Inspection :* |
| 04/13/2005 | EXT METAL CLIPS/EXT SHEATHING | LHANLY | Approved | IVRS - Inspection :* |
| 04/19/2005 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* INSPECTED CONDENSATE DRAINS ON FOOD CASES. STILL NEED TO SEE WALK IN COOLER DRAINS |
| 04/27/2005 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* |
| 05/11/2005 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :* |
| 05/11/2005 | ROOF NAILING | LHANLY | Approved | IVRS - Inspection :* |
| 05/13/2005 | ELECTRIC - TEMPORARY SERVICE | RMAJUTA | Approved | ELECTRICAL CONTRACTOR RESPONSIBLE TO KEEP ENERGIZED PARTS SAFE, AND LOCK OUT UN-INSPECTED WORK CALLED IN FIR 5/13/05 1) UFER APPROVED PER ROBERT SUBA. 2) SES OK TO ENERGIZE. 3) HDPB OL TO ENERGIZE. 4. TRANSFORMER TM OK TO ENERGIZE 5) PNL BOARD LDPA OK TO ENERGIZE. 6) PNLS CPA, CPB, CLA, CPC OK TO ENERGIZE. ELECTRICAL CONTRACTOR TO LOCK OUT ALL UNINSPECTED WORK AND GET OK PRIOR TO ENERGIZING ANY OTHER WORK. 7) SES CHANGE ON CONDUCTORS TO COPPER OK BY ENGINEER LETTER. 8) WATER -GAS-SPINKLER-STEEL-UFER APPROVED. |
| 05/13/2005 | ELECTRIC - CABLE DROP | RMAJUTA | Approved | IVRS - Inspection :* |
| 05/13/2005 | ELECTRIC - UFER | RMAJUTA | Approved | IVRS - Inspection :* |
| 05/13/2005 | TEP CLEARANCE - PM | JKOZUCH | Approved | ECO |
| 05/18/2005 | PLUMBING - GAS PRESS TEST FNL | RRICH | Approved | IVRS - Inspection :*20 PSI AIR TST ON ENTIRE SYSTEM UP TO APPLIANCE SHUT OFF VALVES OK |
| 05/18/2005 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* |
| 05/18/2005 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 05/18/2005 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 05/18/2005 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 05/18/2005 | BUILDING ABOVE CEILING | LHANLY | Approved | IVRS - Inspection :* |
| 05/19/2005 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* PROVIDE ACCESS TO FILTERS ON FAN COILS. NEED TO SEE CONDENSATE DRAIN IN PHARMACY WILL CHECK ON FINAL. OK FOR TEMP C OF O |
| 05/19/2005 | PLUMBING - ROOF DRAINS | RRICH | Approved | |
| 05/19/2005 | PLUMBING - YARD WTR LINE/TEST | RRICH | Approved | |
| 05/23/2005 | ELECTRIC - ABOVE CEILING | RMAJUTA | Approved | IVRS - Inspection :* 1) DELI, BAKERY, PHARMACY CEILINGS OK TO COVER |
| 05/23/2005 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* 1) ? #1 DISCONNECT MOVED-OK 2) DLA OK, DLA1, DLA2 OK 3) P1-OK, P-2 OK, AH 3, 4 AND 5 OK 4) LA OK CK FUSES 5) LA CONTACTOR GRD. 6) EH CK FUSES, EH OK 7) EH CONTACTOR OK 8) TRANS TEM OK 9) OK ITEMS ABOVE OK TO POWER CK |
| 05/24/2005 | PLUMBING - PROGRESS | TRINIVJR | Approved | IVRS - Inspection :* 1) WOMENS AND MENS RESTROOM IS WORKING 2) OK FOR TEMP C OF O |
| 06/03/2005 | ELECTRIC - PROGRESS | RMAJUTA | Approved | IVRS - Inspection :* FOR TEMP C OF O CALL IN UNDER 2090. 1. EMERGENCY GENERATOR TEST RESULTS & INSPECTION OF EQUIPMENT AND INSPECTION OF GENERATOR RUNNING ALL EMERGENCY LIGHTING. 2. ALL ELECTRICAL SWITCH GEAR AND PANELS TO HAVE ALL LABELING & ID REQUIREMENTS PLUS PANEL SCHEDULES. 3. ALL PANELS TO BE CLOSED & COVERS PUT ON. 4. ALL LOW VOLTAGE CABLING 2ND FLOOR BY PHARMACY TO BE SUPPORTED OFF T-BAR CEILING. 5. INSPECT SOFFIT AREAS-MAKE SURE ALL J-BOXES MADE UP. 6. FINISH J-BOXES ABOVE SEAFOOF FREEZERS. 7. FINISH WIRING BAND SAWS MEAT SECTION. 8. CLOSE UP ALL OPEN J-BOXES. 9. ROOF DONE? |
| 06/10/2005 | FIRE - FINAL | JEGAN | Approved | |
| 06/10/2005 | FIRE SPKLR - FINAL | LLAKEY | Approved | |
| 06/10/2005 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | |
| 06/13/2005 | HEALTH DEPT - FINAL 724-7908 | RPEYTON | Approved | |
| 06/14/2005 | BUILDING - PROGRESS | LHANLY | Approved | IVRS - Inspection :* |
| 06/16/2005 | OUTDOOR LIGHTING FINAL | RMAJUTA | Approved | |
| 06/29/2005 | SIGN - FINAL | RDEAR | Approved | shop & elec ok |
| 09/16/2005 | MECHANICAL - FINAL | LHANLY | Approved | IVRS - Inspection :* APPROVED ON REINSPECT |
| 09/16/2005 | PLUMBING - FINAL | LHANLY | Approved | IVRS - Inspection :* |
| 09/16/2005 | PLUMBING - FINAL | LHANLY | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 09/16/2005 | MECHANICAL - PROGRESS | LHANLY | Approved | IVRS - Inspection :* |
| 09/16/2005 | MECHANICAL - HOOD SYSTEMS | LHANLY | Approved | IVRS - Inspection :* |
| 09/16/2005 | MECHANICAL - HOODS | LHANLY | Approved | IVRS - Inspection :* |
| 09/19/2005 | RIGHT OF WAY - FINAL | NKALAHAR | Approved | ( No "complete" until PIA approved) |
| 09/19/2005 | ELECTRIC - FINAL | RSUBA | Approved | IVRS - Inspection :* |
| 09/19/2005 | LANDSCAPE - FINAL | ACONNOR | Approved | Ok for Temp. C of O Monitoring Report required for approval. |
| 09/19/2005 | NPPO - FINAL | ACONNOR | Approved | Ok for Temp. C of O Monitoring Report required for approval. |
| 09/19/2005 | U VALUE FOR WINDOW | LHANLY | Approved | IVRS - Inspection :* |
| 09/20/2005 | ENGINEERING - FINAL | DROBERTS | Approved | MET WITH THE OWNER, MANAGEMENT FIRM, AND THE CONTRACTOR TO DISCUSS THE REMAINING WORK ON THIS SITE. THEY WILL TRY TO COMPLETE THE WORK FOR THIS AREA WITHIN THE NEXT TWO WEEKS, A RE-INSPECTION FOR THE SITE WILL BE SCHEDULED ONCE ALL OF THE WORK IS COMPLETE. I ADVISED THE CREW THAT I WILL TRY TO VISIT THE SITE DURING THAT TIME FRAME TO SEE HOW THE WORK IS PROGRESSING. |