Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 05/11/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. NO UFER VERIFICATION. 2. VERIFY CHANGED PLAN ON CONDUCTOR & FAULT CURRENT. 3. LETTER ON TORQUE. 4. GROUNDING ON TRANSFORMER-SUPPORT CONDUITS W. IN 3' | |
| 05/10/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |