Permit: T03CM05561

Parcel: 11415008V


Addresses:

8080 S HOUGHTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM05561

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2005 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :* PROVIDE ACCESS TO FILTERS ON FAN COILS. NEED TO SEE CONDENSATE DRAIN IN PHARMACY WILL CHECK ON FINAL. OK FOR TEMP C OF O
05/18/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/11/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*OK CEILING TILES IN KITCHEN & UPSTAIRS OFFICES. PROVIDE SECONDARY DRAIN PANS OR FAN COILS IN PHARMACY. DO NOT MOUNT ELECT EQUIPMENT ON SERVICE ACCESS PANELS. PROVIDE ELEC TO INLINE DUCT HEATER. BE SURE THERE IS ADEQUATE ACCESS TO SERVICE FAN COILS.
04/07/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* INSPECTED SUPPLY & EXHAUST IN RESTROOMS OK TO COVER. PROVIDE SECONDARY DRAIN PANS UNDER AHCC 3 04