Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM05561
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2005 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* PROVIDE ACCESS TO FILTERS ON FAN COILS. NEED TO SEE CONDENSATE DRAIN IN PHARMACY WILL CHECK ON FINAL. OK FOR TEMP C OF O | |
| 05/18/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/11/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK CEILING TILES IN KITCHEN & UPSTAIRS OFFICES. PROVIDE SECONDARY DRAIN PANS OR FAN COILS IN PHARMACY. DO NOT MOUNT ELECT EQUIPMENT ON SERVICE ACCESS PANELS. PROVIDE ELEC TO INLINE DUCT HEATER. BE SURE THERE IS ADEQUATE ACCESS TO SERVICE FAN COILS. | |
| 04/07/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* INSPECTED SUPPLY & EXHAUST IN RESTROOMS OK TO COVER. PROVIDE SECONDARY DRAIN PANS UNDER AHCC 3 04 | |
| 04/04/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* INSPECTED TYPE II HOOD & DUCT, SUSPENDED ROUGH DUCT IN KITCHEN. OK TO INSULATE. DISCUSSED CLEARANCES AROUND DUCT FURNACE |