Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* APPROVED ON REINSPECT |
|
| 06/14/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK FOR TEMP C OF O . COOLING TOWER IS BLOWING WATER OUT OF THE FLOOR DRAIN & ONTO CONCRETE SURFACE. EVERYTHING INSIDE BLDG. IS OK. OK FO TEMP C OF O TO OCCUPY & OPEN FOR BUSINESS. | |
| 06/13/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/03/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AH-2 RECONNECT DUCT TO AIR HANDLER. IDENTIFY ALL EQUIPMENT. IS THERE A PRESSURE RELIEF ON REFRIGERATION COMPRESSORS? CONNECT VENTILATION LOUVERS IN COMPRESSOR ROOM. CONDENSATE CANNOT DRIP ONTO A HARD SURFACE. PAINT EXPOSED PVC W/LATEX PAINT. |