Permit: T03CM05561

Parcel: 11415008V


Addresses:

8080 S HOUGHTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM05561

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
APPROVED ON REINSPECT
06/14/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* OK FOR TEMP C OF O . COOLING TOWER IS BLOWING WATER OUT OF THE FLOOR DRAIN & ONTO CONCRETE SURFACE. EVERYTHING INSIDE BLDG. IS OK. OK FO TEMP C OF O TO OCCUPY & OPEN FOR BUSINESS.
06/13/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
06/03/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* AH-2 RECONNECT DUCT TO AIR HANDLER. IDENTIFY ALL EQUIPMENT. IS THERE A PRESSURE RELIEF ON REFRIGERATION COMPRESSORS? CONNECT VENTILATION LOUVERS IN COMPRESSOR ROOM. CONDENSATE CANNOT DRIP ONTO A HARD SURFACE. PAINT EXPOSED PVC W/LATEX PAINT.