Permit: T03CM05561

Parcel: 11415008V


Addresses:

8080 S HOUGHTON RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/18/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/26/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* 60 PSI 3" WELDED GAS PIPING FROM METER TO ALL APPLIANCES THAT ARE VALVED OFF PER PLAN( APPROVED PARTIAL) 10 PSI TEST REQUIRED FOR HANGING DUCT HEATER & UTENSIL WASHER.
02/15/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* PARTIAL APPROVAL 2" GAS FROM 10' FROM FINISH FLOOR CENTER NORTH TO 1 1/2 TO OVEN AND 3/4" TO UTENSIL WASHER 60 PSI AIR TEST OK. 1) NEED REVISED GAS ISOMETRIC FOR DELETION OF WATER HEATER GAS PIPING