Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T01CM00202
Permit Details
Apply Date:
01/16/2001
Applicant:
N/A
Description:
ADDITION:TERMINAL EXPANSION AND REMODEL
Architects:
- BEACH, RICHARD A
Contractors:
- SUNDT CORP
Permit Reviews
Permit Number - T01CM00202
Permit Status: C of o
Permit Description: ADDITION:TERMINAL EXPANSION AND REMODEL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/16/2001 | COMMERCIAL NEW | 06/07/2002 | COMPLETED |
| 01/16/2001 | SITE | 06/07/2002 | COMPLETED |
| 03/13/2003 | REVISION | 03/14/2003 | COMPLETED |
| 03/17/2005 | REVISION - WALK THRU | 03/25/2005 | COMPLETED |
| 04/07/2005 | REVISION | 05/20/2005 | COMPLETED |
| 04/24/2003 | 3RD PARTY REVIEW-REVISION/OTHER | 04/28/2003 | COMPLETED |
| 05/07/2003 | 3RD PARTY REVIEW-REVISION/OTHER | 05/21/2003 | COMPLETED |
| 05/17/2004 | 3RD PARTY REVIEW-REVISION/OTHER | 05/19/2004 | COMPLETED |
| 05/23/2003 | 3RD PARTY REVIEW-REVISION/OTHER | 06/12/2003 | COMPLETED |
| 06/08/2005 | REVISION | 06/27/2005 | COMPLETED |
| 07/11/2003 | REVISION | 07/28/2003 | COMPLETED |
| 08/06/2003 | 3RD PARTY REVIEW-REVISION/OTHER | 08/11/2003 | COMPLETED |
| 08/06/2003 | 3RD PARTY REVIEW-REVISION/OTHER | 08/25/2003 | COMPLETED |
| 09/08/2003 | 3RD PARTY REVIEW-REVISION/OTHER | 10/07/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01CM00202
Permit Status: C of o
Permit Description: ADDITION:TERMINAL EXPANSION AND REMODEL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/16/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T01CM00202
Permit Description: ADDITION:TERMINAL EXPANSION AND REMODEL
Total Completed Inspections - 38
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2002 | ELECTRIC - TEMPORARY POLE | JORTA | Approved | NO INSPECTION. ALREADY INSPECTED AND ENERIZED BY TUCSON ELECTRIC POWER. |
| 09/10/2002 | ELECTRIC - TEMPORARY SERVICE | JORTA | Approved | IVRS - Inspection 0000* |
| 12/17/2002 | ELECTRIC - UNDERGROUND | MCAPISTR | Approved | IVRS - Inspection 0000*1.) PVC FROM COLUMNS UNDERSLAB. 2.) PHONE PEDESTAL COM & PWR PVC. 3.) FLOOR BOX CENTER FRONT OF APART ADDN. |
| 12/24/2002 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | 1.) APPROVED AS NOTED ON PLAN OK TO COVER. |
| 12/24/2002 | BUILDING ABOVE CEILING | LHANLY | Approved | IVRS - Inspection 0000* 1.) CAFCO SPRAY ON FIREPROOFING APPLIED TO STRUCTURAL STEEL @ A-B/1-7 TO DEPTH OF 1 1/2". |
| 05/16/2003 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 09/22/2003 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 09/23/2003 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection 0000*/ 1) PLUMBING FINAL FOR TEMP. C OF O UPON COMPLETION OF POSTING OF BOND AND ISSUANCE OF CITY APPROVED DRAWING FOR WEST BAGGAGE LEVEL WOMENS REST ROOM WASTE AND VENT. THIS COVRERS BAGGAGE AND TICKETING LEVEL 1&2 , 101 - 22. 2) THIS ALSO COVERS MAINTENANCE SHOP AT CENTRAL PLANT. |
| 10/15/2003 | ELECTRIC - SERVICE RELOCATION | DSANTACR | Approved | IVRS - Inspection 0000*/ NOTES: WILL NEED TO GIVE CLEARANCE BEFORE ENERGIZING NEW SWITCH GEAR SECTIONS. PROVIDE LETTER OF TOURQUE, GROUND FAULT TEST. |
| 12/10/2003 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection 0000*/ 1) WEST MENS BAGGAGE RESTROOM 1212 WASTE AND VENT AIR TEST OK. WATER PIPING WATER TEST OK. UNISEX RESTROOM 1213 OK |
| 12/29/2003 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | IVRS - Inspection 0000*/ 4B WEST - DUCT IN SOFFIT - OK TO COVER. |
| 12/31/2003 | STEM WALL/RETAINING WALL | LHANLY | Approved | IVRS - Inspection 0000* 1) C13 COLS LINE 23 OK, CC2 COLS LINE 27, CC2/30, 31/Z1. 2)4' DIAMETER COLS LINE 41 BEING POURED WITHOUT COT INSPECTION. (FAILURE TO GET COT APPROVAL COULD RESULT IN COSTLY DELAYS IN THE FUTURE.) |
| 12/31/2003 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | IVRS - Inspection 0000* FOOTING TUNNEL 7 & 8 NOT READY |
| 06/11/2004 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :*/ 1) 6 SETS ROOF DRAIN AND AREA DRAINS COLUMN LINE 26-31 IN EAST BAGGAGE AREA WATER TEST OK. MECH ENGINEER LETTER FOR 3" HORIZONTAL TO VERTICAL TRANSITION ON 4" HORIZONTAL PIPING OK PER RF1 578 DATED AND STAMPED 6/01/04. WATER PIPING 2" FROM 22.1 AND Y1 GOING EAST FROM VALVE TO TERMINATION PER PLAN. FOR EAST BAGGAGE PRESSURE TEST OK |
| 07/21/2004 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection :SOFFITS TICKET LEVER 2ND FLOOR, NORTH ENTRY |
| 08/24/2004 | EXT METAL CLIPS/EXT SHEATHING | LHANLY | Approved | IVRS - Inspection :* |
| 10/15/2004 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :*/SINK AREA-COPPER HEATING WATER, TO 7-4' THRU 47 VAV'S GO PSI |
| 11/16/2004 | STUCCO MESH | LHANLY | Approved | IVRS - Inspection :ALL BUT WEST END AT WEST BARREL |
| 11/16/2004 | REINFORCED MASONRY PRE-GROUT | LHANLY | Approved | IVRS - Inspection :* |
| 12/17/2004 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection :*/OK TO COVER GRID, LOWER LEVEL |
| 12/20/2004 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :*/OK WALLS & ABOVE CEILINGS OFFICES AT BAGGAGE WEST BACK OFFICES & FRONT OFFICES. |
| 12/22/2004 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* 1) OK T.C.O. FOR 1ST FLOOR WEST BAGGAGE AREA AND 2ND FLOOR WEST TICKET AREA |
| 12/22/2004 | BUILDING - FINAL | LHANLY | Approved | 1) OK FOR T.C.O. 2) ALL BAGGAGE 1-8 3) ALL TERMINAL 4) EXCLUDE LINK AREA |
| 12/22/2004 | ROOF NAILING | LHANLY | Approved | IVRS - Inspection :* |
| 12/22/2004 | BUILDING PRE-SLAB | LHANLY | Approved | IVRS - Inspection :* |
| 12/28/2004 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 12/28/2004 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 12/30/2004 | SHEET ROCK NAILING | LHANLY | Approved | IVRS - Inspection :* P LINK AREA OK TO TAPE |
| 12/30/2004 | FRAMING | LHANLY | Approved | IVRS - Inspection :* P LINK CEILING OK |
| 05/24/2005 | ELECTRIC - CONSTRUCTION POWER | DSANTACR | Approved | IVRS - Inspection :* |
| 05/27/2005 | FIRE - FINAL | LTHOMAS | Approved | |
| 05/27/2005 | FIRE - HYDRANTS | LTHOMAS | Approved | |
| 05/27/2005 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 06/06/2005 | RIGHT OF WAY - FINAL | MOTERO | Approved | CLEAR |
| 06/20/2005 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* TURNED IN ( 3) BOILER INSPECTION REPORTS (1) H20 CHLORINAZTION REPORT ( 10) BACKFLOW CERTIFICATIONS. |
| 06/22/2005 | ENGINEERING - FINAL | DROBERTS | Approved | OKAY FOR C OF O |
| 06/22/2005 | ENGINEERING - FINAL | LHANLY | Approved | IVRS - Inspection :* |
| 06/23/2005 | PLUMBING - SEWER HCS CONNECT | RRICH | Approved |