Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T01CM00202
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 05/27/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE CALL IN ALL INSPECTIONS FOR THURSDAY 6/2/05, HAVE PLUMBER ON SITE. PROVIDE CITY APPROVED REVISED PLAN OF BOILER AREA GAS PIPING PER 6/18/05 INSPECTION |
|
| 08/12/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :FROM MANHOLE AT Y2 + 38.1 6" UPSTREAM TO 1-3", 2-4" STUBS UP FOR RAIN DRAINS AND 4" FROM AREA DRAIN IN NEW STAIRWAY AT RAC WATER TEST OK | |
| 07/08/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 1) 6" RWL UNDERGROUND FROM MANHOLE AT COLUMN 38.1 TO 3-4" RISERS ENDS AT 6" EDN OF LINE CLEANOUT AND 4" RISER AT 34.1 WATER TEST OK. THIS PIPING ENDS HERE 3" RWL SHOWN IS DELETED PER RFI AT COLUMN 34 | |
| 06/11/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 1) FLOOR SINK AND VENT WATER TEST ROOM 101-OK. FLOOR SINK TO SUMP PUMP TANK WATER TEST ROOM 101-OK | |
| 04/23/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 2" FLOOR SINK IN FIRE RISER ROOM STUBBED 6' NORTH OK ON WTR TEST. | |
| 03/10/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 6" GRAVITY DRAIN FROM FORCE MAIN EAST CONCOURSE INTO NEW MANHOLE VACUUM TEST APPROVED. | |
| 03/09/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*/ VACUUM TEST ON NEW MANHOLE FOR 6" EAST FORCE MAIN DISCHARGE DENIED, | |
| 03/08/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ WTR TEST TIE INTO 6" EXISTING 6" WEST FORCED MAIN TO 8' ABOVE FINISHED GRADE OK. WTR TEST 6" EAST FORCED MAIN TIE INTO NEW MANHOLE 10' ABOVE FINISHED GRADE OK. NEW MANHOLE TO BE VACUUM TESTED. | |
| 02/27/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) 18" STORM DRAINS IN LIND AREA IS OK 2) AIR PRESSURE TEST IS OK 3) OK TO BACKFILL TRENCH | |
| 01/22/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 4" RAIN DRAIN EXTENDED TO 108 TY, 4" RAIN DRAIN EXTENDED TO 105 TY, 4" RAIN DRAIN EXTENDED TO YT109. WTR TEST APPROVED. | |
| 01/21/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) 10" RAIN DRAIN 12' EAST OF CENTER LINE X RUNS WEST TO B1 + 109, 6" TAP BETWEEN X + Y WITH 3-4" STUB UPS AT Y + 106, Y + 105, Y + 104, 4" TAP BETWEEN X + Y RUNS WEST STUB UPS AT Y + 108, Y+ 109 WATER TEST (APPROVED) | |
| 01/15/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 4" RAIN DRAIN UNDERGROUND FROM CENTER LINE 104 AND Y TO CENTER LINE 1 PLUS Y 6" CONNECTION. | |
| 12/18/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 12" STORM DRAIN ORIGIN AT R-15, 10' OUTSIDE BLDG FROM C/C 26 TO C/C 31 WTR TEST UNDERGROUND APP. | |
| 11/12/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) ROUGH SOIL TO ? HEIGHT WATER TEST OK FOR MENS REST ROOM AND UNISEX RESTROOM COLUMN LINES 102, 103 AND C, B. OK TO COVER | |
| 08/11/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN IS OK. 3) THIS INSPECTION IS FOR BAGGAGE AREA WEST WOMENS RESTROOM. 4) OK FOR BACKFILL. 5) NOTE: WILL REQUIRE A REVISED AND APPROVED DRAWING ON WASTE AND VENT SYSTEM PRIOR TO FINAL INSPECTION. PLEASE RED LINE AS BUILTS. | |
| 08/07/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*/ 1) LAVATORYS INSTALLED IN SETS ARE 2 FIXTURE UNITS EACH. YOU CAN ONLY DISCHARGE 8 F.U. ON A TWO INCH HORIZONTAL DRAIN. SEE SECTION: TABLE 7-3, 94 UPC. | |
| 04/18/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*PLEASE HAVE APPROVED PLANS ON SITE @ A LOCATION WHERE I CAN HAVE ACCESS TO THEM. | |
| 04/01/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*1.) 3" N/H TO MOP SINK AT COLUMNS 2.5 & B OK WATER TEST OK OK TO COVER. | |
| 03/10/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*F.S. @ 19.5 OK. | |
| 03/07/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*1.) 2" WASTE FOR FLOOR SINK @ COLUMN LINE 5-6/B-C. 2.) F.S. @ COLUMN 19.5 REQUIRES VENT 'Y' TO BE ROTATED UP 45 MIN. 3.) LAV, WC & MOP SINK FLOOR DRAIN & VENT OK 20-21.5 LINE B-2. |
|
| 03/04/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*GATES WERE LOCKED ON SITE. | |
| 02/25/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK. 3.) THIS INSPECTION IF FOR BAGGAGE LEVEL EAST RESTROOMS ONLY. 4.) WILL REQUIRE A REVISED & APPROVED PLAN. |
|
| 02/21/2003 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*1.) MUST PROVIDE WATER TEST ON WASTE & VENT SYSTEM. | |
| 12/24/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | 1.) APPROVED AS NOTED ON PLAN OK TO COVER. | |
| 12/22/2002 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FOR INSPECTION. | |
| 12/12/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | 1.) 6" DIP UNDERGROUND WATER SERVICE W/COPPER LOOP ABOVE GRADE INCLUDING VALVE OK. TIE-IN TO C900 OK OK TO COVER PRESSURE TEST OK 2.) 3P2.12 RWL 6" & 4" UNDERGROUND OK AS NOTED ON PLAN WATER TEST OK OK TO COVER. |
|
| 12/10/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*3P2.12 & 3 P2.13. 1.) 6" & 8" N/H RWL UNDERGROUND, AS HIGHLIGHTED ON ABOVE PAGES OK WATER TEST OK 2.) OK TO COVER. |
|
| 12/08/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*3P2.13 RAIN WATER LEADER AS HIGHLIGHTED ON PLAN OK OK TO COVER. | |
| 12/04/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*3P2. 14 RWL 4" 6" & 8" 1.) N/H RWL UNDERGROUND, AS HIGHLIGHTED ON PLAN OK WATER TEST OK 2.) OK TO COVER. |
|
| 12/02/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000* 1.) 6" U.G. SEWER FROM MANHOLE @ C-5 up to C-101. 6" CAST IRON NO HUB. FCO @ 3" UB C-1.2 RELOCATED TO ABOVE 4" TIE @ C 2.2; THIS WAS APPROVED. 2.) 2" NO HUB APPROX 12' FROM 4" C.O. TO EXISTING ON COLUMN LINE 107 C1 TO SEWER MAIN APPROVED. AFTER HOURS INSPECTION. |