Permit Number: T01CM00202
Parcel: 140420740

Address:
7250 S TUCSON BL

Review Status: Completed

Review Details: REVISION

Permit Number - T01CM00202
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Please provide a specification, listed by an approved testing agency, for the protection of penetrations to horizontal assemblies. Ref. IBC 711.4.


PLUMBING COMMENTS
General
1. Please specify the slope of the horizontal drainage piping. Ref. UPC 708.

2. Note 2, providing contact information for material specification, does not appear to apply. Please clarify.




ELECTRICAL COMMENTS
Sheet 3E4.1
1. The service information shown in the ejector schedule on Sheet 3P4.4 does not agree with the load summary notes. Please coordinate and clarify.
07/28/2003 EROSE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2003 ELAINE ROSE OUT TO CUSTOMER Completed