Permit: T01CM00202

Parcel: 140420740


Addresses:

7250 S TUCSON BL


Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T01CM00202

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2004 ROOF NAILING Approved IVRS - Inspection :*
08/24/2004 ROOF NAILING Partial Approval IVRS - Inspection :*
07/13/2004 ROOF NAILING Partial Approval IVRS - Inspection :*
06/16/2004 ROOF NAILING Partial Approval IVRS - Inspection :*/ 1) FLAT ROOF EAST END OF EAST BARRED. REPAIR 4 EACH PUDDLE WELDS AT SEAM OF NORTH SHEET. OK TO COVER
05/25/2004 ROOF NAILING Partial Approval IVRS - Inspection :*
05/12/2004 ROOF NAILING Partial Approval IVRS - Inspection :* AREA E SOUTH OF BARREL EACH PARAPETS & FLAT ROUTS OK TO COVER
04/21/2004 ROOF NAILING Partial Approval IVRS - Inspection 0000* 6 REMAINING COLS OK. PLEASE TIE CHAIRS
12/11/2003 ROOF NAILING Partial Approval IVRS - Inspection 0000*
04/10/2003 ROOF NAILING Partial Approval IVRS - Inspection 0000*BARREL ARCH DECKING YZ/1-7.
03/26/2003 ROOF NAILING Partial Approval IVRS - Inspection 0000*
03/17/2003 ROOF NAILING Partial Approval 1.) BARREL ARCH DECKING AREA D HAS BEEN COVERED. REVIEW OF SPECIAL INSPECTION REPORTS INDICATES THAT DIFFERENT AREA WAS DONE.
2.) A MEETING ON SITE WITH TERRACON WELDING INSPECTOR G. DENUZIO WILL BE HELD ON 3-21 OR 3-24 TO 20 OVER WHAT HE HAS ACTUALLY BEEN INSPECTED.
03/13/2003 ROOF NAILING Denied IVRS - Inspection 0999*
do not cover work without approval of building offical. I have not inspection nor have i seen special inspection reports for high roof that is now being covered.
03/05/2003 ROOF NAILING Partial Approval IVRS - Inspection 0000*PRELIMINARY WALK THRU DONE.
1.) RFI 256 ADDRESSED MOVING SC2 LINE Z BETWEEN 7 & 16 3/8" TOTAL.
2.) RFI 260 ALLOWS 2 1/4" BASE PLATE INSTEAD OF 2 1/2" FOR BOX BEAMS.
3.) NEED INFORMATION ON REPAIR FOR BEAMS FABRICATED TOO SHORT VARIOUS LOCATIONS ALONG LINES Y AND Z.