Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/25/2005 |
MECHANICAL - INTERMEDIATE |
|
Approved |
|
| 10/15/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/SINK AREA-COPPER HEATING WATER, TO 7-4' THRU 47 VAV'S GO PSI |
| 08/06/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) WEAT BAGGAGE-HEAT COILS WATER PRESS 100 PSI |
| 08/05/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ FOR 4035 INTERMEDIATE EIGHT (8) OK TO WRAP |
| 06/21/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* |
| 05/11/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :$/ 1) 4" CW MAINS TO AHV 104. 3/4" CW TO FC 1 - 60 PSI. OUTSIDE AIR (OSA) AT A/H 104 - ACCESS??? 2) HTG WTR EAST BAGGAGE AREA - 60 PSI. |
| 08/28/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ HEATING WATER, CENTRAL PLANT - 100 PSI - EQUALIZED DOWN TO 40 PSI - 5 MIN. |
| 07/02/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) LOWER WATER, CHILLER #5 SUPPLY/RETURN LOOP-110 PSI 2) CHILLED RELIEF VALVES-RECEIVERS PIPED VTR 3) REFRIG. DETECTOR SYSTEM PROGRESSING |
| 06/04/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/29/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PULL RETAINING ANGLES, 1 SIDE, ALL FIRE/SMOKE DAMPERS. WILL CHECK OPENINGS 2) BE PREPARED TO EXPOSE IN ? DUCT 3) HAVE SET OF PLANS FOR WALK THRU 4) UPPER LEVEL-SUSPENDED AIR HANDLERS ACCESS ??? |
| 03/20/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*BAGGAGE AREA WEST SIDE 112 PSI. EAST SIDE 115 PSI. MENS REST RM. DOMESTIC WATER 100 PSI. OVERHEAD & CWR LINES. |