Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T01CM00202
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. The design professional's seal is not legible for the west side temporary stair design. Please submit at least one wet sealed drawing set for each of the two stair designs.

2. Provide an exit plan specifying the occupant load to be serviced by the temporary exiting. Include the calculations demonstrating adequate widths. Refs. IBC 106.1.2, 1003.2.2, 1003.2.3.

3. Dimension the provisions for areas of refuge. Ref. 1003.2.13.5.

4. Provide construction details of the stairs and openings for the stair access. Refs. IBC 1003.3.3.1 through 1003.3.3.3.12.1

5. Detail handrail construction. Ref. IBC 1003.3.3.11.

6. Provide the number of treads and risers for each of the stairs. Ref. IBC 1003.3.3.3.3.

7. Dimension guard height for compliance with IBC 1003.2.12.

STRUCTURAL COMMENTS
General
1. Provide the design calculations for the stairs.

2. Indicate the method of connection to the existing structure and at foundation conditions by providing details and design calculations for each condition.

ELECTRICAL COMMENTS
General
1. Provide an exit signage plan for directing occupants to the proposed temporary exits. Ref. IBC 1003.2.10.

2. Provide the power plan and emergency back up for exit illumination. Ref. IBC 1003.2.11.2.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2003 ELAINE ROSE OUT TO CUSTOMER Completed