Permit: T01CM00202

Parcel: 140420740


Addresses:

7250 S TUCSON BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM00202

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/14/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ABOVE CEILING AT EAST WALKWAY LINK-SUBJECT TO VERIFICATION OF MEDIUM OR HEAVY DUCT GROUND SYSTEM. HAVE COPY FOR INSPECTOR NEXT INSPECTOR
01/03/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK HARD CID FAR EAST ENTRY WAY LINK
12/20/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/OK WALLS & ABOVE CEILINGS OFFICES AT BAGGAGE WEST BACK OFFICES & FRONT OFFICES.
12/16/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ABOVE GRID 1ST FLOOR BETWEEN COL #102-THRU-109, B1-THRU-Y
2) OK POLE BASES AND UNDERGROUND FOR POLE LTS AT DROP OFF AREA/PICK UP AREA
12/08/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/1)OK HARD LIDS SOUTH WALL NITCHES LTG. LINK WALKWAY 2)OK CAN LTS/SPEAKERS WEST TICKET LEVEL 2ND FLOOR BY NEW ESCALATOR
11/03/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK WEST OUTSIDE CANOPY 2ND FLOOR
2) OK WALLS OFFICE AT WEST BAGGAGE COL'S #2 THRU #1 AND BETWEEN "X" AND "W"
10/25/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/RECESSED ROUND FIXTURE INTERMEDIATE APPROVED. WEST BAGGAGE AREA FRONT INTRANCE COLUMN LINES 1 TO 106 AND W TO X
10/07/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK ABOVE GRID EAST BAGGAGE AREA - 1ST FLOOR
10/06/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK SOFFITS 1ST FLOOR BAGGAGE OFFICE WEST, COL- #104 THRU #108.8 . OK 2ND FLOOR CEILING COL #101 THRU # 103 HIGH CEILING BY ELEVATOR
10/04/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK WALLS 1ST FLOOR BETWEEN COLS 109 THRU 105 BAGGAGE AREA
09/24/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK HIGH SOFFIT LTG. TICKET WEST-SOUTH SOFFIT-2ND FLOOR 2) OK SOFFITS 1ST FLOOR BAGGAGE COL. #106 TO #102-HARD LIDS
09/20/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/1) OK EAST BAGGAGE SOFFITS IN FRONT OF ELEV & EXCALATORS 1ST FLOOR. 2) OK 6 OFFICES WALLS & CEILINGS FROM COL.26 TO 20 1ST FLOOR. BAGGAGE EAST
OK TEMP C OF O FOR OFFICES
09/16/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK SOFFIT TICKET LEVEL WEST, NORTH UPPER LIGHTING, 2ND FLOOR 2) OK EAST OUTSIDE TICKET LEVEL CANOPY LIGHTING 3) OK TICKET LEVEL EAST CEILING BETWEEN COL. #22 AND #23
09/10/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/OK HARD CEILINGS FROM COL #105 TO #109 WEST BAGGAGE FRONT ENTRY 1ST FLOOR
09/02/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK HARD LIDS 2ND FLOOR TICKET EAST
HI-BAY CEILING & HI-BAY WALKWAY LINK
08/27/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK SOFFITS AT 1ST FLOOR AT WINDOWS BAGGAGE LEVEL EAST
08/17/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*PARTIAL- OK LOWER SOLAT? SOUTH TICKET COUNTER EAST 2ND FLOOR
08/05/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK SOFFITS/HARD LIDS 1ST FLOOR FROM COLUMN LINE #26 TO #29 2) OK WALLS, HARD LID, ELEVATOR ROOM WEST
08/04/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
08/02/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK SOFFIT - HARD LID 1ST FLOOR FROM GRID LINE 29 TO 33.1 BAGGAGE LEVEL EAST
OK 2ND FLOOR EAST TICKET LEVEL UPPER SOFFIT
06/25/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) SUPPORT M/C CABLE WITHIN 12" OF BOXES. OK CANS IN CEILING WEST CIRCULATION #1211. OK 6 COLUMNS 104-109 AT COLUMNS.
05/11/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ OK WEDGE HARD LIDS, COLUMN ROUGH IN FAR EAST BAGGAGE AREA.
04/22/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) OK WALLS, EAST BAGGAGE ELECT RM/MECH RM 1ST FLOOR. 2) OK EAST BAGGAGE SOFFIT 1ST FLOOR. 3) OK EAST BAGGAGE OFFICES. 4) OK 2ND FLOOR TICKET AREA CEILINGS EAST AND WEST BY ESCALATORS.
04/09/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK IN SLAB POWER, LTG, FA CONDUITS TICKET LEVER FAR WEST
03/23/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK CEILINGS WEST END TICKET LEVEL BY ESCALATORS.
03/22/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK ABOVE CEILING OVER ESCALATORS (EAST)
03/03/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK IN SLAB CONDUITS FOR LTG, FLOOR BOXES, 2ND FLOOR EAST SIDE.
02/27/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK SOFFIT AND WALLS OFFICE AREA EAST BAGGAGE 1ST HALF
01/28/2004 ELECTRIC - INTERMEDIATE Partial Approval AFTER HOURS INSPECTION: 1) OK GFCI TEST FOR SERVICE MODIFICATIONS AT WEST ELECTRICAL ROOM, OKE TO RE-ENERGIZE. PAID WITH CHECK #2128 $108.00
01/22/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK UNDERSLAB POWER AND COMM EAST BAGGAGE AREA, OK C OF O RESTROOMS WEST BAGGAGE AREA.
01/09/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK TO RE-ENERGIZE TRANSFORMER #55. CALLED TEP MAP ROOM AT 2:17AM. RECEIVED CHECK #215 FOR $104.00 AND $4.00 CASH FOR AFTER HOURS INSPECTION
01/05/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK WALLS IDF CLOSET WEST OFFICE, STORAGE.
12/11/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) OK TERMINATIONS AT 1500 KVA GEN AT CENTRAL PLANT, BUSS TIE BETWEEN SES & GEN. 2) OK GEN INSTALL 1000 KVA AT WEST ELECTRICAL ROOM. BUSS LINKS TO GEN. WILL TIE IN AT FUTURE OUTAGE. 3) PROVIDE GFI & GEN TEST APPROVAL DOCUMENT FROM TESTING AGENCY AT CENTRAL PLANT AND WEST ELECTRICAL EQUIP. VAULT.
12/10/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS AND HARD LIDS WEST MENS BATHROOMS, BAGGAGE, 1ST FLOOR
10/13/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK TEMP C OF O 2ND FLOOR CENTRAL TICKET AREA
09/26/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK TEMP C OF O CENTRAL BAGGAGE AREA 1ST FLOOR
09/25/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) FLEX CONDUIT STUB UP'S AT FLOOR IN CENTRAL BAGGAGE MUST TERMINATED OR ISOLATED FROM PUBLIC PRIOR TO TEMP C OF O
09/17/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK GRID CEILINGS GRID 19 TO 22 1ST FLOOR, 2ND FLOOR EAST AND WEST CEILINGS OK
09/15/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK GRID CEILING BAGGAGE 1ST FLOOR CENTER AREA TO GRID .19.
09/12/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK ABOVE CEILINGS BAGGAGE AREA WEST 1/2
09/05/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK HARD LIDS CENTER SECTION 2ND FLOOR. OK CEILINGS CENTER ESCALATOR TO WEST RESTROOMS.
08/28/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK OUTSIDE CANOPYS EAST AND WEST 2ND FLOOR.
08/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) VERIFY VOLTAGE RATING OF CONTRA WIRING THAT IS TERMINATED IN 120VAC BOXES WITH SWITCHES, MUST BE RATED FOR THE HIGHER VOLTAGE. 2) OK FIRST FLOOR WEST WOMENS RESTROOMS.
08/08/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK CENTER AREA TICKET, AND LOW SOFFIT AREA WEST END COLUMN 1-7
07/31/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) ok soffit lighting columns #7-thru-#1 2nd floor ticket area
07/29/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) 2ND FLOOR TICKET AREA SOFFIT LIGHTS EAST AREA 7-22 COLUMNS
07/16/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK HARD HD COLUMN #18 TO #22 2) OK WALLS, HARD LID INFORMATION CENTER GROUND INFORMATION
07/11/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK HARD LID FROM COLUMN # 18 UP TO #1.
07/09/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) OK 2ND FLOOR SOFFITS BY ESCALATORS. 2) OK EAST RESTROOMS FIRST FLOOR AT COLUMNS #23 & #24 COMPLETE OK FOR TEMP C/O
06/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK SOFFIT CENTER AREA WEST BAGGAGE
06/11/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK HARD LIDS CENTER EAST BAGGAGE AREA SOFFITS
05/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK HARD CEILING 2ND FLOOR CENTER SECTION OK 2 COLUMNS #6 & 7.
04/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK ROUGH IN 5 COLUMNS FRONT BAGGAGE CENTER AREAS.
2.) OK MECH. ROOM UNASSIGNED OFFICES, EAST AND WEST OF CENTER ESCHAUTERS BAGGAGE ROUGH IN, WALLS, HARD LIDS.
03/31/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS AND HARD LIDS FAR EAST MIDDLE BATHROOMS, BAGGAGE LEVEL.
03/12/2003 ELECTRIC - INTERMEDIATE Partial Approval OK SOFFIT LIGHTING ABOVE TICKET COUNTER S, 3 AREAS SECOND FLOOR.
2.) OK FEEDER CONDUITS FROM ELECTRIC ROOMS THRU BAGGAGE DROP OFF, PICK AREA 2 LOCATIONS.
01/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK CENTER SECTION 2ND FLOOR UNDER SLAB (TERMINAL)
01/23/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK IN SLAB CONDUIT BOXES 2ND FLOOR TERMINAL WEST 1/3 CENTER AREA.
01/16/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK IN SLAB PVC AND FLOOR BOXES EAST 1/3 2ND FLOOR TERMINAL CENTER SECTION.