Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00202
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/14/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING AT EAST WALKWAY LINK-SUBJECT TO VERIFICATION OF MEDIUM OR HEAVY DUCT GROUND SYSTEM. HAVE COPY FOR INSPECTOR NEXT INSPECTOR |
|
| 01/03/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK HARD CID FAR EAST ENTRY WAY LINK | |
| 12/20/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/OK WALLS & ABOVE CEILINGS OFFICES AT BAGGAGE WEST BACK OFFICES & FRONT OFFICES. | |
| 12/16/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ABOVE GRID 1ST FLOOR BETWEEN COL #102-THRU-109, B1-THRU-Y 2) OK POLE BASES AND UNDERGROUND FOR POLE LTS AT DROP OFF AREA/PICK UP AREA |
|
| 12/08/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1)OK HARD LIDS SOUTH WALL NITCHES LTG. LINK WALKWAY 2)OK CAN LTS/SPEAKERS WEST TICKET LEVEL 2ND FLOOR BY NEW ESCALATOR | |
| 11/03/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) OK WEST OUTSIDE CANOPY 2ND FLOOR 2) OK WALLS OFFICE AT WEST BAGGAGE COL'S #2 THRU #1 AND BETWEEN "X" AND "W" |
|
| 10/25/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/RECESSED ROUND FIXTURE INTERMEDIATE APPROVED. WEST BAGGAGE AREA FRONT INTRANCE COLUMN LINES 1 TO 106 AND W TO X | |
| 10/07/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :OK ABOVE GRID EAST BAGGAGE AREA - 1ST FLOOR | |
| 10/06/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOFFITS 1ST FLOOR BAGGAGE OFFICE WEST, COL- #104 THRU #108.8 . OK 2ND FLOOR CEILING COL #101 THRU # 103 HIGH CEILING BY ELEVATOR | |
| 10/04/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :OK WALLS 1ST FLOOR BETWEEN COLS 109 THRU 105 BAGGAGE AREA | |
| 09/24/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) OK HIGH SOFFIT LTG. TICKET WEST-SOUTH SOFFIT-2ND FLOOR 2) OK SOFFITS 1ST FLOOR BAGGAGE COL. #106 TO #102-HARD LIDS | |
| 09/20/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1) OK EAST BAGGAGE SOFFITS IN FRONT OF ELEV & EXCALATORS 1ST FLOOR. 2) OK 6 OFFICES WALLS & CEILINGS FROM COL.26 TO 20 1ST FLOOR. BAGGAGE EAST OK TEMP C OF O FOR OFFICES |
|
| 09/16/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) OK SOFFIT TICKET LEVEL WEST, NORTH UPPER LIGHTING, 2ND FLOOR 2) OK EAST OUTSIDE TICKET LEVEL CANOPY LIGHTING 3) OK TICKET LEVEL EAST CEILING BETWEEN COL. #22 AND #23 | |
| 09/10/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/OK HARD CEILINGS FROM COL #105 TO #109 WEST BAGGAGE FRONT ENTRY 1ST FLOOR | |
| 09/02/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :OK HARD LIDS 2ND FLOOR TICKET EAST HI-BAY CEILING & HI-BAY WALKWAY LINK |
|
| 08/27/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :OK SOFFITS AT 1ST FLOOR AT WINDOWS BAGGAGE LEVEL EAST | |
| 08/17/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*PARTIAL- OK LOWER SOLAT? SOUTH TICKET COUNTER EAST 2ND FLOOR | |
| 08/05/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) OK SOFFITS/HARD LIDS 1ST FLOOR FROM COLUMN LINE #26 TO #29 2) OK WALLS, HARD LID, ELEVATOR ROOM WEST | |
| 08/04/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 08/02/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :OK SOFFIT - HARD LID 1ST FLOOR FROM GRID LINE 29 TO 33.1 BAGGAGE LEVEL EAST OK 2ND FLOOR EAST TICKET LEVEL UPPER SOFFIT |
|
| 06/25/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) SUPPORT M/C CABLE WITHIN 12" OF BOXES. OK CANS IN CEILING WEST CIRCULATION #1211. OK 6 COLUMNS 104-109 AT COLUMNS. | |
| 05/11/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ OK WEDGE HARD LIDS, COLUMN ROUGH IN FAR EAST BAGGAGE AREA. | |
| 04/22/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) OK WALLS, EAST BAGGAGE ELECT RM/MECH RM 1ST FLOOR. 2) OK EAST BAGGAGE SOFFIT 1ST FLOOR. 3) OK EAST BAGGAGE OFFICES. 4) OK 2ND FLOOR TICKET AREA CEILINGS EAST AND WEST BY ESCALATORS. |
|
| 04/09/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK IN SLAB POWER, LTG, FA CONDUITS TICKET LEVER FAR WEST | |
| 03/23/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK CEILINGS WEST END TICKET LEVEL BY ESCALATORS. | |
| 03/22/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK ABOVE CEILING OVER ESCALATORS (EAST) | |
| 03/03/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK IN SLAB CONDUITS FOR LTG, FLOOR BOXES, 2ND FLOOR EAST SIDE. | |
| 02/27/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK SOFFIT AND WALLS OFFICE AREA EAST BAGGAGE 1ST HALF | |
| 01/28/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | AFTER HOURS INSPECTION: 1) OK GFCI TEST FOR SERVICE MODIFICATIONS AT WEST ELECTRICAL ROOM, OKE TO RE-ENERGIZE. PAID WITH CHECK #2128 $108.00 | |
| 01/22/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK UNDERSLAB POWER AND COMM EAST BAGGAGE AREA, OK C OF O RESTROOMS WEST BAGGAGE AREA. | |
| 01/09/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO RE-ENERGIZE TRANSFORMER #55. CALLED TEP MAP ROOM AT 2:17AM. RECEIVED CHECK #215 FOR $104.00 AND $4.00 CASH FOR AFTER HOURS INSPECTION | |
| 01/05/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK WALLS IDF CLOSET WEST OFFICE, STORAGE. | |
| 12/11/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) OK TERMINATIONS AT 1500 KVA GEN AT CENTRAL PLANT, BUSS TIE BETWEEN SES & GEN. 2) OK GEN INSTALL 1000 KVA AT WEST ELECTRICAL ROOM. BUSS LINKS TO GEN. WILL TIE IN AT FUTURE OUTAGE. 3) PROVIDE GFI & GEN TEST APPROVAL DOCUMENT FROM TESTING AGENCY AT CENTRAL PLANT AND WEST ELECTRICAL EQUIP. VAULT. | |
| 12/10/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS AND HARD LIDS WEST MENS BATHROOMS, BAGGAGE, 1ST FLOOR | |
| 10/13/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TEMP C OF O 2ND FLOOR CENTRAL TICKET AREA | |
| 09/26/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TEMP C OF O CENTRAL BAGGAGE AREA 1ST FLOOR | |
| 09/25/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) FLEX CONDUIT STUB UP'S AT FLOOR IN CENTRAL BAGGAGE MUST TERMINATED OR ISOLATED FROM PUBLIC PRIOR TO TEMP C OF O | |
| 09/17/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK GRID CEILINGS GRID 19 TO 22 1ST FLOOR, 2ND FLOOR EAST AND WEST CEILINGS OK | |
| 09/15/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK GRID CEILING BAGGAGE 1ST FLOOR CENTER AREA TO GRID .19. | |
| 09/12/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK ABOVE CEILINGS BAGGAGE AREA WEST 1/2 | |
| 09/05/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK HARD LIDS CENTER SECTION 2ND FLOOR. OK CEILINGS CENTER ESCALATOR TO WEST RESTROOMS. | |
| 08/28/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK OUTSIDE CANOPYS EAST AND WEST 2ND FLOOR. | |
| 08/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) VERIFY VOLTAGE RATING OF CONTRA WIRING THAT IS TERMINATED IN 120VAC BOXES WITH SWITCHES, MUST BE RATED FOR THE HIGHER VOLTAGE. 2) OK FIRST FLOOR WEST WOMENS RESTROOMS. | |
| 08/08/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK CENTER AREA TICKET, AND LOW SOFFIT AREA WEST END COLUMN 1-7 | |
| 07/31/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ok soffit lighting columns #7-thru-#1 2nd floor ticket area | |
| 07/29/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) 2ND FLOOR TICKET AREA SOFFIT LIGHTS EAST AREA 7-22 COLUMNS | |
| 07/16/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK HARD HD COLUMN #18 TO #22 2) OK WALLS, HARD LID INFORMATION CENTER GROUND INFORMATION | |
| 07/11/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK HARD LID FROM COLUMN # 18 UP TO #1. | |
| 07/09/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) OK 2ND FLOOR SOFFITS BY ESCALATORS. 2) OK EAST RESTROOMS FIRST FLOOR AT COLUMNS #23 & #24 COMPLETE OK FOR TEMP C/O | |
| 06/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK SOFFIT CENTER AREA WEST BAGGAGE | |
| 06/11/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK HARD LIDS CENTER EAST BAGGAGE AREA SOFFITS | |
| 05/14/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK HARD CEILING 2ND FLOOR CENTER SECTION OK 2 COLUMNS #6 & 7. | |
| 04/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK ROUGH IN 5 COLUMNS FRONT BAGGAGE CENTER AREAS. 2.) OK MECH. ROOM UNASSIGNED OFFICES, EAST AND WEST OF CENTER ESCHAUTERS BAGGAGE ROUGH IN, WALLS, HARD LIDS. |
|
| 03/31/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALLS AND HARD LIDS FAR EAST MIDDLE BATHROOMS, BAGGAGE LEVEL. | |
| 03/12/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | OK SOFFIT LIGHTING ABOVE TICKET COUNTER S, 3 AREAS SECOND FLOOR. 2.) OK FEEDER CONDUITS FROM ELECTRIC ROOMS THRU BAGGAGE DROP OFF, PICK AREA 2 LOCATIONS. |
|
| 01/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK CENTER SECTION 2ND FLOOR UNDER SLAB (TERMINAL) | |
| 01/23/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK IN SLAB CONDUIT BOXES 2ND FLOOR TERMINAL WEST 1/3 CENTER AREA. | |
| 01/16/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK IN SLAB PVC AND FLOOR BOXES EAST 1/3 2ND FLOOR TERMINAL CENTER SECTION. |