Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address NEW:
707 W MIRACLE MILE 07
Apply Date:
09/23/2009
Applicant:
N/A
Description:
SUPPORT SERVICE BLDG FOR WOMEN'S HOUSING FACILITY
Contractors:
  • SAXTON DESIGN BUILD LLC

Permit Reviews

Permit Number - T09CM02572
Permit Status: C of o
Permit Description: SUPPORT SERVICE BLDG FOR WOMEN'S HOUSING FACILITY
Start Date Submittal Complete Date Status  
01/05/2011 REVISION - WALK THRU 01/05/2011 COMPLETED Review Details
01/12/2010 RESUBMITTAL 01/25/2010 COMPLETED Review Details
01/26/2010 RESUBMITTAL 01/27/2010 COMPLETED Review Details
05/17/2011 REVISION - - 1ST 05/19/2011 COMPLETED Review Details
09/23/2009 PLANS OK TO SUBMIT - COMM 09/23/2009 COMPLETED Review Details
09/24/2009 COMMERCIAL NEW 11/10/2009 COMPLETED Review Details
11/10/2009 RESUBMITTAL 11/17/2009 COMPLETED Review Details
11/17/2009 RESUBMITTAL 12/16/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM02572
Permit Status: C of o
Permit Description: SUPPORT SERVICE BLDG FOR WOMEN'S HOUSING FACILITY
Total Outstanding Activity Conditions - 1
Date Name
09/23/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T09CM02572
Permit Description: SUPPORT SERVICE BLDG FOR WOMEN'S HOUSING FACILITY
Total Completed Inspections - 46
Date Description Inspector Results Comments
02/05/2010 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
1) ABS DWV UNDERSLAB OK TO COVER-GREASEWASTE AND SANITARY SEWER TO OUTSIDE BLDG
2) WATER TEST TO RISER TEN FEET
3) INTERCEPTOR IS SET
02/25/2010 FIRE SPKLR - UG, PIPING, HYDRO LThomas Approved Approved 2/25/10
02/26/2010 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
1) ALL THREADED CONNECTIONS REQUIRE APPROVED PIPE THREAD SEALANT
04/01/2010 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
1) REVISE PLAN TO SHOW NEW FEEDER FOR BLDGS #10 & 11 (2" PVC OK DEPTH)
04/05/2010 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection :*
4" ABS SERVER REQUIRES TRACER WIRE PROVIDE INSPECTION HISTORY FOR GI, INSTALL TRACER WIRE, THEN OK TO COVER
05/17/2010 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
1) YARDWATER EXTENED TO BLDG OK
OK TO COVER WITH CLEAN FILL
05/17/2010 FIRE - KITCHEN EXH HOOD FINAL DSIWARSKI Approved
06/09/2010 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
06/15/2010 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
06/18/2010 MECHANICAL - HOODS MRAMBER Approved IVRS - Inspection :*
1) DUCT ABOVE HOOD OK TO COVER
06/18/2010 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
1) OK KITCHEN WALLS
06/25/2010 BUILDING PRE-SLAB MHENSON Approved IVRS - Inspection :*
07/22/2010 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
07/27/2010 FRAMING AQUIROZ Approved IVRS - Inspection :*
07/27/2010 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
07/30/2010 TEP CLEARANCE - PM JWEATHER Approved TEC CLEARED PER D. SANTACRUZ
08/18/2010 STUCCO MESH AQUIROZ Approved IVRS - Inspection :*
08/23/2010 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
08/23/2010 ELECTRIC - OUTDOOR LIGHTING DSANTACR Approved IVRS - Inspection :*
08/23/2010 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection :*
08/26/2010 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
1) DUCT ABOVE CEILING OK TO COVER
08/26/2010 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
1) PROVIDE REVISED APPROVED PLAN FOR ROOF DRAINS
2) NEED TO SEE CLOSET FLANGES
3) OK TO COVER ALL OTHER AREAS S.T.O.I.
08/27/2010 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
08/27/2010 PLUMBING - ROOF DRAINS RMYERS Approved IVRS - Inspection :*
09/21/2010 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
11/05/2010 ELECTRIC - PROGRESS DSANTACR Approved IVRS - Inspection :*
1) COMPLETE TRIM OUT FOR FINAL INSPECTION
2) RECALL INSPECTION AND HAVE ELECTRICIAN ON SITE TO REMOVE COVERS FOR INSPECTION
3) NEED TO ADDRESS ALUM. CONDUCTORS
11/09/2010 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved
11/15/2010 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
1) CLOSET FLANGES OK
11/16/2010 OUTDOOR LIGHTING FINAL DSANTACR Approved IVRS - Inspection :*
11/16/2010 LANDSCAPE - FINAL MRUSSO Approved SITE HAS LANDSCAPE PLAN.

ENSURE LANSCAPING ON SITE IS INSTALLED PER THE APPROVED PLAN.
11/16/2010 ENGINEERING - FINAL MRUSSO Approved CONTRACTOR ASKING FOR HELP IN DESIGNING AND INSTALLING STORM DRAIN SYSTEM -SITE REQUIRES A GRADING PERMIT AND PLAN.

ENSURE STORM DRAINAGE SYSTEM IS CERTIFIED BY A PE PRIOR TO FINAL
12/21/2010 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
1) OK TCO (ELECTRICAL)
2) PLEASE ADDRESS COURTYARD LIGHT POLES
3) OK REVISIONS FOR (LIGHT FIXTURES AND POWER PANELS)
01/25/2011 ELECTRIC - CABLE DROP RHOLLAND Approved IVRS - Inspection :*
01/25/2011 ELECTRIC - UFER RHOLLAND Approved IVRS - Inspection :*
02/23/2011 RIGHT OF WAY - FINAL MOTERO Approved
02/24/2011 FIRE SPKLR - FINAL LThomas Approved Approved 2/24/11
02/24/2011 FIRE SPKLR - OH PIPING & HYDRO LThomas Approved Approved
02/24/2011 FIRE SPKLR - UG PIPING FLUSH LThomas Approved Approved
02/25/2011 NPPO - FINAL MRUSSO Approved PROJECT DOES NOT HAVE NPPO PLAN.
03/30/2011 SIGN - FINAL JYBARRA Approved
04/06/2011 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
04/13/2011 FIRE - FINAL DRAMIREZ Approved CARD SIGNED ON REINSPECT
04/13/2011 FIRE - FINAL DRamirez Approved Not approved 4/12//
1.) Need hood final
2.) Life/safety inspection already conducted and approved
3.) OK for TCO. OK for kitchen opperations but not can not operate cooking appliances located under the hood.
4.) Must post bond for TCO.
04/14/2011 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
04/20/2011 HEALTH DEPT - FINAL 724-7908 NRAMIREZ Approved
05/19/2011 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*

Documents

File Name Document Type  
C OF O_05-19-2011.TIF CERT OF OCC VIEW
001_COVER.TIF CONSTRPLANS VIEW
002_D-1.TIF CONSTRPLANS VIEW
003_D-2.TIF CONSTRPLANS VIEW
004_D-3.TIF CONSTRPLANS VIEW
005_D-4.TIF CONSTRPLANS VIEW
006_D-5.TIF CONSTRPLANS VIEW
007_D-6.TIF CONSTRPLANS VIEW
008_D-7.TIF CONSTRPLANS VIEW
009_D-8.TIF CONSTRPLANS VIEW
010_D-9.TIF CONSTRPLANS VIEW
011_D-10.TIF CONSTRPLANS VIEW
012_L-1.TIF CONSTRPLANS VIEW
013_L-2.TIF CONSTRPLANS VIEW
014_A-1.TIF CONSTRPLANS VIEW
015_A-2.TIF CONSTRPLANS VIEW
016_A-3.TIF CONSTRPLANS VIEW
017_A-4.TIF CONSTRPLANS VIEW
018_A-5.TIF CONSTRPLANS VIEW
019_A-6.TIF CONSTRPLANS VIEW
020_A-7.TIF CONSTRPLANS VIEW
021_A-8.TIF CONSTRPLANS VIEW
022_A-9.TIF CONSTRPLANS VIEW
023_S-1.TIF CONSTRPLANS VIEW
024_S-2.TIF CONSTRPLANS VIEW
025_S-3.TIF CONSTRPLANS VIEW
026_S-4.TIF CONSTRPLANS VIEW
027_MP-01.TIF CONSTRPLANS VIEW
028_MP-02.TIF CONSTRPLANS VIEW
029_MP-03.TIF CONSTRPLANS VIEW
030_MP-04.TIF CONSTRPLANS VIEW
031_MP-05.TIF CONSTRPLANS VIEW
032_MP-06.TIF CONSTRPLANS VIEW
033_MP-07.TIF CONSTRPLANS VIEW
034_MP-08.TIF CONSTRPLANS VIEW
035_MP-09.TIF CONSTRPLANS VIEW
036_E-1.TIF CONSTRPLANS VIEW
037_E-2.TIF CONSTRPLANS VIEW
038_E-3.TIF CONSTRPLANS VIEW
039_E-4.TIF CONSTRPLANS VIEW
040_E-5.TIF CONSTRPLANS VIEW
041_E-6.TIF CONSTRPLANS VIEW
042_E-7.TIF CONSTRPLANS VIEW
001_U-1.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW
CERTIFICATION LETTER 05_18_2011.PDF DOCUMENTS VIEW
None DOCUMENTS VIEW