Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02572
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/18/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 12/03/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PLANS DENIED FOR THE FOLLOWING: 1. Transformer TN to have grounding electrode conductor sizes per 2005 NEC 250.30(A)(6) & 250.66 based on combined circular mils of parallel sets of conductors. Not corrected from first review. 2. Transformer TN to have bonding jukper to metal piping systems sized per 2005 NEC 250.30(A)(6) , 250.104(D) & 250.66 based on combined circular mils of parallel conductors. Not corrected from first review. Rich Jiroudek Electric plns examining |
| 12/09/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/09/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/09/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/11/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Revise the ventilation calculations to include the common ventilation calculations for AC-3, AC-4, AC-6, and AC-7. Reference: Sections 403.1, 403.3, and 403.3.2, IMC 2006. 2. Comment not resolved. Show that the hood installation complies with Section 507.9, IMC 2006 for clearances. The wall adjacent to the hood appears to be constructed with wood studs and the stainless steel covering for that wall is noted as extending only 12" beyond the hood. |
| 12/11/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The review for the kitchen plumbing cannot be completed until an approved plan from Pima County Health Department has been received. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/16/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/16/2009 | SUE REEVES | REJECT SHELF | Completed |