Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/02/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT MC 12"-6' INTERVALS 2) SUPPORT LV CABLING TO STRUCTURE 3) MC RUN INSIDE CHANNEL MUST HAVE 1 1/4" DISTANCE FROM FACE OF STUD 4) SUPPORT CONDUIT WITHIN 3' OF TERMINATION AND AT 10' INTERVALS PER CODE |