Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2011 | MECHANICAL - HOODS | Approved | ||
| 06/18/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE HOOD OK TO COVER |
|
| 06/01/2010 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL WRAP PER INSTALL INSTRUCTIONS 2) PROVIDE BANDING PER INSTALL INSTRUCTIONS 3) BANDING IN CURB TO LOOSE 4) HAVE INSTALLER ON SITE WITH INSTALL INSTRUCTIONS AT NEXT INSPECTION |
|
| 05/26/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER OF WRAP OK, OK FOR 2ND LAYER |
|
| 05/21/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) WELD TEST ON TYPE I DUCT OK, UP TO CONNECTION AT FAN 2) OK FOR 1ST LAYER OF FIRE WRAP |
|
| 05/20/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) PROVIDE SMOKE TEST ON TYPE I DUCT 2) PROVIDE FULL RADIUS ON FLEX BENDS 3) SADDLES ON FLEX 4) EXPOSE DAMPER BLANDES AT TAPS OR PROVIDE ENGINEERS APPROVAL FOR BALANCING DAMPERS IN DIFFUSERS 5) ALL AREAS VERIFY DUCR SEALER |