Permit: T09CM02572

Parcel: 10705121A

Inspection Status: Denied

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
04/13/2011 FIRE - KITCHEN EXH HOOD FINAL Denied Not approved 4/12/11
1.) Gas supply did not shut down upon activation of system
04/13/2011 FIRE - KITCHEN EXH HOOD FINAL Approved CARD SIGNED ON REINSPECT 4-13-2011
04/11/2011 FIRE - KITCHEN EXH HOOD FINAL Not ready for Inspection Cintas was not on property to do hood final
04/09/2011 FIRE - KITCHEN EXH HOOD FINAL Denied Not approved 4/8/11 See Locks/Notes
1.) Gas supply must shut down upon activation of system.
2.) All othe components including Trip Test were tested and approved. Only need Gas Shut-Off.
04/06/2011 FIRE - KITCHEN EXH HOOD FINAL Cancelled Cancelled 4/6/11
03/30/2011 FIRE - KITCHEN EXH HOOD FINAL Denied Not approved 3/30/11
1.) Need "mechanical final"
2.) Must be called in for inspection by the installer
05/17/2010 FIRE - KITCHEN EXH HOOD FINAL Not ready for Inspection